China Fln36 24kv Sf6 Load Break Switch, Find details about China Load Break Switch, Load Switch from Fln36 24kv Sf6 Load Break Switch
++++General:
RLS-36 an indoor high-voltage SF6 load switch, an swi tchgear wi ththe rated voltage of 36kV/40.5kV, adopted wi th SF6 gas as an arc-extinguishing and insulation medium, including the three contactors for switching-on and switching-off andto-ground, and is characteristic in its small volume, its convenient installation and operation and itsthe great adaptability with surroundings. RLS-36 of an indoor high-voltage SF6 load switch and RLS-36 of SF6 load switch plus fuse combination canfunctionto protect and controlthe electric equipmentsfor power supply andtransformer substations especially being suitable for ring net cabinet, cable branch cabinet and distribution switching substation.
RLS-36 of an indoor high-voltage SF6 load switch and RLS-36 load switch plusfuse combination are complied withthe standards of GB3804-1990, IEC60256-1,1997, GB16926, IEC60420 etc..
++++Service environment:
a) Airtemperature Maximumtemperature: +40ºC; Minimumtemperature:-5ºC
b) Humidity Monthly average humidity 95%; Daily average humidity 90%.
c) Altitude above sea level Maximum installation altitude: 2500m
d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
e) Nofrequent violent shake
++++ Main technical specifications:
No | Item | Unit | Parameter |
1 | Rated voltage | kV | 36 |
2 | Rated frequency | Hz | 50/60 |
3 | Rated current | A | 630 |
4 | wet 1min Power frequency withstand voltage dry | kV
kV | 95
110 |
5 | Lightning impulse withstand voltage | kV | 185/215 |
6 | Rated short circuit breaking current (peak) | kA | 50 |
7 | Rated activeload and close circuit breaking current | A | 50 |
8 | Rated transferring current | A | 1000 |
9 | Rated short circuit making current (peak) | kA | 50 |
10 | Rated cable(line) charging breaking current | A | 50 and 10 |
11 | Cable charge breaking current in earthing fault | A | 20 |
12 | Rated withstand current (peak) | kA | 50 |
13 | Short time withstand current (2s) | kA | 20 |
14 | Mechanism life | times | 2000 |