Intelligent Constant Pressure Pump Controller IP54

China Intelligent Constant Pressure Pump Controller IP54, Find details about China Water Supply Controller, Constant Pressure Water Supply Controller from Intelligent Constant Pressure Pump Controller IP54

Model NO.
B603
Model NO.
B603
B603 Series
Intelligent Constant Pressure 
Water Supply Controller
Intelligent Constant Pressure Pump Controller IP54

With high quality, multi-functional, low noise and strong commonality etc. characteristics, B603 multi-function energy-saving controller is suitable to full-automatic operation.
  1. Professional design based on users' needs, simplicity of operation and suitable for all kinds of applications;
  2. According to the water condition to supply constant pressure water without manual operation after parameters were set correctly;
  3. Stop running automatically when no water consumption;
  4. Alarm automatically when faults occurred;
  5. Alternate running automatically in the multiple pump system, prolong the using life of pumps.
Features
  1. Input & Output
Input Voltage Range: 220/380V±15%
Input Frequency Range: 47~63Hz
Output Voltage Range: 0~rated input voltage
Output Frequency Range: 0~50/60Hz
  1. I/O Features
Digital Switch Input: 3 input
Analog Signal Input: AI1: 0~10V or 0~20mA input; AI2: 0~10V or 0~20mA input
Relay Output: A pair of switch Output 
  1. Function Characteristics
Multi-Pump Control: Can realize 1 master and Max.5 auxiliaries combine work
Sleep Function: Sleep down when have no water consumption, to earn a better energy saving
Freeze-Proofing Function: Suitable to low temperature area, prevent pump from freezing
Anti-clogging Function: Take precaution against pipe clogging and clean the pipe dirt
Power On Restart: Running automatically when power on
Master Fault Shift Automatically: Keep on working when the master break down
Alternate Running: Balance every pump's running time, prolong service life of the whole unit machine
Day-Part Function: 3 independent day-part control, up to 7 day-part achieved when define separated
Two Running Mode: Synchronous control mode, master-slave control mode
Terminal Control Mode: Terminal Run/StopManual/Auto ControlElectronic Contact Gauge Control
Various of water supply Fault Alarm Function: High-Pressure, Low-Pressure, Low-Level, Transducer Error etc.
As many as 22 kinds of fault protection function: Over-Current, Over-Voltage, Low-Voltage, Phase-Failure, Over-Load etc.

Selection Guide

Table2.3.1 B603 list
Model No.Rated Input Voltage (V)Input Current (A)Max. Output Current (A)Motor Power (kW)
B603D(B)-20011AC: 220V
-15%~+15%
8.24.50.75
B603D(B)-200214.27.01.5
B603D(B)-200323.010.02.2
B603D-2001
3AC: 220V
-15%~+15%
5.04.50.75
B603D-20027.77.01.5
B603D-200311.010.02.2
B603D(B)-200517.016.03.7
B603D(B)-200721.020.05.5
B603D-201031.030.07.5
B603D-201543.042.011
B603D-202056.055.015
B603D-202571.070.018.5
B603D-203081.080.022
B603D-2040112.0110.030
B603D-2050132.0130.037
B603D-2060163.0160.045
B603D-2075200.0200.055
B603D(B)-40013AC: 380V
-15%~+15%
3.42.50.75
B603D(B)-40025.03.71.5
B603D(B)-40035.85.02.2
B603D(B)-400510.09.04.0
B603D(B)-400715.013.05.5
B603D(B)-401020.017.07.5
B603D(B)-401526.025.011
B603D(B)-402035.032.015
B603D-402538.037.018.5
B603D-403046.045.022
B603D-404062.060.030
B603D-405076.075.037
B603D-406090.090.045
B603D-4075105.0110.055
B603D-410014015075
B603D-412016017690
B603D-4150210210110
B603D-4180240250132
B603D-4215290300160
B603D-4250330340185
B603D-4270370380200
B603D-4300410415220
B603D-4340460470250
B603D-4380500520280
B603D-4430580600315
B603D-4470620640350

INSTRUCTIONS OF PARAMETERS GROUP
Function CodeNameSetting RangeFactory SettingDescription
Br00 Group Application Function
b00.00Debugging Password0~6553565535Decide by b06.09, default is 65535
b00.01Pressure Setting Value0.0~100.0bar3.0barSet according to the actual requirements of user
b00.02Motor Rotating Direction0~100: Forward     1: Reverse
b00.03Freeze-proofing0~10Used in cold areas  
0: Invalid      1: Valid
b00.04Anti-clogging0~10Prevention measures  
0: Invalid      1: Valid
b00.05Anti-clogging
Rotating Cycle
1.0~300.0s20.0sSet the forward/reverse rotating direction cycle and corresponding output frequency (should not be higher than the rated frequency of the pump) of anti-clogging.
b00.06Anti-clogging Output Frequency0.00~600.00
Hz
15.00Hz
Br01 Group Application Function
b01.00High Water Pressure/Level Alarm Value0.0~100.0bar8.0barWhen pressure is higher than this preset value, the controller halts, alarms and displays HP.
b01.01Low Water Pressure/Level Alarm Value0.0~100.0
bar
0.5barWhen pressure is lower than the preset value for a low pressure running time, the controller halts,alarms and displays LP
b01.02Low Pressure/Level Running Time0~300s20s
b01.03Minimum Freeze-proofing Frequency1.00~30.00Hz5.00HzBe valid when b00.03 was set to 1, whenever sleeps, running with the setting frequency in case of freezing.
b01.04Anti-clogging FWD./REV. Dead Time0.0~3600.0s1.0sWhen anti-clogging is valid, b01.04 set the FWD./REV. transition time
b01.05Maximum Transducer Setting Range0.0~100.0bar10.0barE.g. If the rated max. range of transducer is 10bar, b01.05 should be set to 10.0
b01.06AI1 Lower Limit0.00~10.00V1.00VLower limit use to transducer zero setting
•Higher limit use to accordant display and transducer pressure.
When display smaller than gauge, increase higher limit; When display greater than gauge, decrease higher limit.
•When analog input is interfered, prolong filtering time so as to increase the ability of anti-interference, but decrease the sensitivity.
•Corresponding relationship of transducer parameter setting:

Figure6.1.1 Transducer parameters
b01.07Corresponding Setting of AI1 Lower Limit-100.0~100.0%0.0%
b01.08AI1 Higher Limit0.00~10.00V5.00V
b01.09Corresponding Setting of AI1 Higher Limit-100.0~100.0%100.0%
b01.10AI1 Filtering Time0.00~10.00s0.10s
b01.11AI2 Lower Limit0.00~10.00V1.00V
b01.12Corresponding Setting of AI2 Lower Limit-100.0~100.0%0.0%
b01.13AI2 Higher Limit0.00~10.00V5.00V
b01.14Corresponding Setting of AI2 Higher Limit-100.0~100.0%100.0%
b01.15AI2 Filtering Time0.00~10.00s0.10s
b01.16Restart After Power-on0~100: invalid    1: valid
b01.17Control Mode0~110: Synchronous  1: Master-slave
Br02 Group Application Function
b02.00PID Source Selection0~100: Keypad  1: Reserved
b02.01PID Feedback
Source Selection
0~100: AI1     1: Reserved 
b02.02PID Output
Characteristics
0~100: Water supply  1: Pumping
b02.03Proportional
Gain (KP)
0.00~100.002.50Determining the strength of PID regulation, KP is bigger, regulation is stronger, but fluctuate easier too. 
b02.04Integral Coefficient (KI)0.00~10.001.00Bias between the feedback and the given, determining the speed of regulation, KI is bigger, regulation is stronger. 
b02.05Derivative Coefficient (KD)0.00~10.000.00Variable ratio between the feedback and the given, KD is bigger, regulation is stronger. Be cautious use, for differential regulation amplifies interference of system.
b02.06Sampling
Cycle (T)
0.01~100.00s0.10sCalculating time of regulator, when increased, response sluggishly. 
b02.07PID Control Bias Limit0.0~100.0%0.0%Max. bias of PID output value corresponding to closed loop given value:

Figure6.2.1 PID control curve
Corresponding System Diagram of Max. Limit and Output Frequency.
Properly set the value can regulate the accuracy and stability of PID system. 
b02.08AI1 Feedback
Lost Detecting
Value
0.0~100.0%1.0%Transducer fault detecting setting value, corresponding to full range (100%), when the detecting time exceeds feedback lost time, it is deemed as malfunction by
transducer, the system will report E022 as transducer fault code.
b02.09AI2 Feedback
Lost Detecting
Value
0.0~100.0%0.0%
b02.10Feedback Lost
Detecting time
0.0~3600.0s1.0s
Br03 Group Application Function
b03.00Communication Address0~310200: Master controller 
01~05: Auxiliary controller
06~31: Reserved
b03.01Baud Rate Selection0~53Data of master and slave comes into the rate.
0: 1200BPS    1: 2400BPS
2: 4800BPS    3: 9600BPS
4: 19200BPS   5: 38400BPS
b03.02Data Format0~50Data format (parity check)
b03.03Communication Delay Time0~200ms15msInterval of data responding.
b03.04Communication Timeout Delay 0.0: invalid0.0~100.0s0.0sIf the interval time exceeds the setting value, the system will report E018 as fault.
b03.05Communication Error Action0~100: Halt and alarm 
1: Don't alarm and continue
b03.06Communication Response Action0~100: Responding to write operation 
1: Un-responding to writer operation
b03.07Data Transmission Time Interval0.05~2.00s0.10sEnsure the effects of data transmission, long-time setting will slow down data transmission and short-time setting will easily make mistakes.
b03.08Slave Quantity0~500: None
b03.09Fault Shift0~22Fault Master Shift 
Invalid: Factory setting: 2
Valid: Master set as 0;
       Salve 1 set as 1.
Remarks: Fault shift demands the salve to connect a backup transducer.
Br04 Group Application Function
b04.00Sleeping Function0~11No consuming auto stop. 
0: Invalid  1: Valid
b04.01Sleeping Waiting Time0.0~300.0s5.0sDelay time, seconds unit
b04.02Sleeping Test0.0~10.0%4.0%Water consuming test frequency rate.
b04.03Wake-up Pressure Bias0.0~20.0bar0.5barDuring sleeping the wake-up pressure bias, e.g. the setting value (L)=3.0bar, bias (b04.03)=0.5bar, practical pressure (P)<L-0.5=2.5bar, the pump will restart again.
b04.04Sleeping Bias0.0~1.0bar0.0barThe pressure fluctuation which allows sleeping
Br05 Group Application Function
b05.00Water Level Control0~22Water level switch style,
0invalid  1NC  2NO
b05.01Low Lever Restart Delay Time0~300min1minDelay time of restart after water level switch recover.
b05.02Terminal S1S2 Control0~320: Invalid
1: Electric contact control
 S1-COM on: Frequency rise
 S2-COM on: Frequency drop
2: Manual/auto control 
 S2-COM off: Auto control
 S2-COM on: Manual control
3: Terminal run/stop
 S1-COM on: Run
 S1-COM off: Stop
S2-COM off: Auto control
 S2-COM on: Manual control
b05.03Acceleration Time0.1~3600.0sModel SetThe setting time from zero to max. frequency
b05.04Deceleration Time0.1~3600.0sModel SetThe setting time from max. frequency to zero
b05.05Maximum Output Frequency10.00~600.00
Hz
50.00HzDetermine the Acc./Dec. rate
b05.06Up limit of Output Frequencyb05.07~b05.05(Maximum Frequency)50.00HzMaximum running frequency
b05.07Lower Limit of Output Frequency0.00Hz~b05.0620.00HzThe minimum running frequency of pump. 
b05.08Carrier Frequency1.0~15.0kHzModel SetUse to ameliorate the noise of motor and controller's interference to the surroundings. A high carrier makes a low motor noise, but leads to a big temperature rise and interference.Should not be altered if unnecessary.
b05.09Low Pressure (LP) Restart Delay Time00~60min10minIn case of low pressure, b05.09≠0, the controller restarts to work according to the setting time automatically, without artificial restart. b05.09=0, restart invalid.
b05.10Alternating Time0.00~300.00h8.00hIn order to balance and prolong the pump service life to set the parameter, unit: hour. When the parameter is set to 0.0, it means in-execution. Operational time of master and auxiliary pump switches over according to the setting alternating time. 
Br06 Group Application Function
b06.00Running Status Display Selection0~0x1FF0x01Fbit0: Operational frequency 
bit1: The actual pressure of pump outlet
bit2: The setting pressure of pump outlet 
bit3: Output current
bit4: DC bus voltage
bit5: Output voltage
bit6: Present time
bit7: The actual pressure of pump inlet
bit8: Input terminal status
b06.01Stop Status Display Selection0~0x1FF0x00Fbit0: The setting pressure of pump outlet 
bit1: The actual pressure of pump outlet
bit2: Giver frequency
bit3: DC bus voltage 
bit4: Input terminal status
bit5:Output terminal status
bit6: AI1 input voltage
bit7: The actual pressure of pump inlet
bit8: Present time
b06.02Keypad Display Selection0~330: External keypad prior enable
1: Both display enable, only external keypad control;
2: Both display enable, only on board keypad control;
3: Both display enable and keypad control
b06.03Relay Output Selection0~500: Error or external fault
1: Forward running
2: Frequency reaching
3: Stop status
4: Lower limit of output frequency reaching
5: The frequency is not equal to zero
b06.04Third Latest Fault Type Read OnlyE000~E022
Refers to chapter 9.
b06.05Second Latest Fault Type 
b06.06Latest Fault Type 
b06.07Parameters Storage Condition0~200: Power-off storage   
1: Power-off default storage
2: Invalid
b06.08Accumulated Running Time0~65535hRead OnlyDisplay accumulated running time
b06.09Set the Password of b00.000~6553565535Password set prevent user from modifying the parameters randomly, avoiding running abnormally and damages.
Br07 Group Application Function
b07.00Day-part Function Selection0~300: Invalid
1: Day-part A  
2: Day-part A and B 
3: Day-part A, B, C
b07.01Day-part A Starting Time00:00~24:0000-00Setting starting time and finishing time to 0 is invalid.
Pressure setting determines the steady state value of outlet pressure.
Once actual pressure from inlet pipe network lower than inlet pressure lower limit, the pump stops.
When regardless of the inlet water pressure, just set the lower limit as 0.
b07.02Day-part A Pressure Setting0.0~20.0bar3.0bar
b07.03Day-part A Finishing Time00:00~24:0000-00
b07.04AI2 Lower Limit of Day-part A0.0~20bar2.0bar
b07.05Day-part B Starting Time00:00~24:0000-00
b07.06Day-part B Pressure Setting0.0~20bar3.0bar
b07.07Day-part B Finishing Time00:00~24:0000-00
b07.08AI2 Lower Limit of Day-part B0.0~20.0bar3.0bar
b07.09Day-part C Starting Time00:00~24:0000-00
b07.10Day-part C Pressure Setting0.0~20.0bar3.0bar
b07.11Day-part C Finishing Time00:00~24:0000-00
b07.12AI2 Lower Limit of Day-part C0.0~20.0bar2.0bar
b07.13Lower Limit of Inlet Pressure0.0~100.0bar0.0barValid all day, especially for the use of taking account of inlet water pressure. When not needed,, set as 0.
b07.14Restore Defaults0~200: No action
1: Set to default
2: Clear error records
b07.15Password of Group Br080~6553565535 
Br08 Group Application Function
b08.00G/P Option0~110: G model  1: P model
b08.01Motor Rated Power0.4~350kWModel SetDepend on model, setting parameters according to nameplate of motor
b08.02Motor Rated Frequency0.00~600.00Hz50.00Hz
b08.03Motor Rated Speed0~36000RPMModel Set
b08.04Motor Rated Voltage0~460V
b08.05Motor Rated Current0.0~2000.0A
b08.06Reserved0~6553500000 
b08.07Set the Password of b07.150~6553565535Modify password of b07.15
b08.08Password of Factory Parameters0~65535xxxxxDon't try to enter or will cause abnormal operation and damages.