Model | IPS9310 6-80KVA | |||||||||
6KVA | 10KVA | 15KVA | 20KVA | 30KVA | 40KVA | 50KVA | 60KVA | 80KVA | ||
Rated Capacity | 6KVA/4.8KW | 10KVA/8KW | 15KVA/12KW | 20KVA/16KW | 30KVA/24KW | 40KVA/32KW | 50KVA/40KW | 60KVA/48KW | 80KVA/64KW | |
Rated Voltage | 220V Single Phase (6-20KVA)/380VA | |||||||||
Rated Frequency | 50/60HZ | |||||||||
AC Input | ||||||||||
Voltage range | ± 20% | |||||||||
Frequency range | 50/60HZ± 10% | |||||||||
Soft start | 0-100% 5sec | |||||||||
Power factor | 0.95(with input filter) | |||||||||
Bypass input | ||||||||||
Voltage range | 15% | |||||||||
Frequency range | 50/60HZ± 5% | |||||||||
Output | ||||||||||
Voltage accuracy | 220V± 1%(Steady state load) 220V± 3%(load fluctuation) | |||||||||
Frequency accuracy | 50/60Hz± 0.05Hz (Battery supply power) | |||||||||
Power factor | 0.8 | |||||||||
Harmonic distortion | Linear load< 2%; non-linear< 4% | |||||||||
Dynamic state load voltage transient | < 5% | |||||||||
Current crest ratio | 3: 1 | |||||||||
Overload Capacity | 110%load work normally; 125% 10min; 150% 1min; | |||||||||
Efficiency | Double conversion mode: 94%, ECOmode: 98% | |||||||||
DC | ||||||||||
Nominal Battery Voltage | 220V | |||||||||
Cutoff voltage | 185V | |||||||||
Maximum discharge current | 21A | 36A | 55A | 73A | 109A | 145A | 181A | 218A | 291A | |
Panel display | ||||||||||
LCD | Chinese/English display UPS status, input voltage, output voltage, current, frequency, battery voltage, charge-discharge current value, fault and warning. | |||||||||
Working environment | ||||||||||
Temperature | 0-40 º C | |||||||||
Humidity | 0-90%, non-condensing | |||||||||
Storage temperature | -25º C-55º C | |||||||||
Altitude | < 1500mlower than sea level | |||||||||
Physical property | ||||||||||
Weight (KG) | N. W | 230 | 258 | 350 | 400 | 480 | 580 | 650 | 900 | 950 |
G. W | 250 | 285 | 280 | 425 | 500 | 600 | 675 | 925 | 988 | |
Size W × D× H(mm) | 800× 600× 2260 | |||||||||
Option | RS485/network adapter (SNMP)/harmonic compensation tank/input and output power distribution cabinet/input and output isolation cabinet/lightning protection device/bypass voltage regulation cabinet/ the cabinet size can be customized. |