China German Standard Industrial Cables PVC Insulated Sheathed Copper Conductor Nycwy Screened Power Electric Cables, Find details about China Electric Wire, Electrical from German Standard Industrial Cables PVC Insulated Sheathed Copper Conductor Nycwy Screened Power Electric Cables
In dry, humid and wet locations, cable ducts, outdoors, underground and in Water.
1 ..... solid or stranded bare copper wire
2 ..... core insulation of polyvinylchloride (PVC)
3 ..... PVC core covering
4 ..... concentric conductor of copper wires and copper tape applied helically
5 ..... outer sheath of polyvinylchloride (PVC), black
DIN VDE 0276-627
HD 627 S1:1996 part 1 4H1, 4H2.7H
DIN EN 60228 class 1 and 2 (construction)
HD 308 S2 (core identification)
AWG | NO. OF CORES X NOMINAL CROSS SECTIONAL AREA # X MM² | STRANDED CONDUCTOR TYPE | NOMINAL OVERALL DIAMETER MM | NOMINAL COPPER WEIGHT KG/KM | NOMINAL CABLE WEIGHT KG/KM |
---|---|---|---|---|---|
8 | 2 x 10.0 | re / 10.0 | 19 | 312 | 650 |
6 | 2 x 16.0 | re / 16.0 | 21.5 | 489 | 850 |
4 | 2 x 25.0 | rm / 25.0 | 24.5 | 763 | 1210 |
8 | 3 x 10.0 | re / 10.0 | 19.5 | 408 | 730 |
6 | 3 x 16.0 | re / 16.0 | 22 | 643 | 1000 |
4 | 3 x 25.0 | rm / 16.0 | 26 | 902 | 1550 |
4 | 3 x 25.0 | rm / 25.0 | 26 | 1003 | 1600 |
2 | 3 x 35.0 | sm / 35.0 | 27.5 | 1402 | 1850 |
2 | 3 x 35.0 | sm / 16.0 | 27 | 1190 | 1750 |
1 | 3 x 50.0 | sm / 50.0 | 29.5 | 2000 | 2450 |
1 | 3 x 50.0 | sm / 25.0 | 29 | 1723 | 2250 |
2/0 | 3 x 70.0 | sm / 70.0 | 34 | 2796 | 3350 |
2/0 | 3 x 70.0 | sm / 35.0 | 33 | 2410 | 2950 |
3/0 | 3 x 95.0 | sm / 95.0 | 38.5 | 3791 | 4550 |
3/0 | 3 x 95.0 | sm / 50.0 | 38 | 3296 | 4100 |
4/0 | 3 x 120.0 | sm / 70.0 | 41 | 4236 | 5050 |
4/0 | 3 x 120.0 | sm / 120.0 | 42 | 4786 | 5550 |
300mcm | 3 x 150.0 | sm / 70.0 | 45 | 5100 | 6000 |
300mcm | 3 x 150.0 | sm / 150.0 | 46 | 5970 | 6900 |
350mcm | 3 x 185.0 | sm / 95.0 | 50 | 6383 | 7550 |
350mcm | 3 x 185.0 | sm / 185.0 | 51 | 7363 | 8500 |
500mcm | 3 x 240.0 | sm / 120.0 | 57 | 8242 | 9950 |
8 | 4 x 10.0 | re / 10.0 | 20.5 | 504 | 890 |
6 | 4 x 16.0 | re / 16.0 | 23.5 | 796 | 1250 |
4 | 4 x 25.0 | rm / 16.0 | 28 | 1142 | 1800 |
2 | 4 x 35.0 | sm / 16.0 | 29 | 1526 | 2050 |
1 | 4 x 50.0 | sm / 25.0 | 33 | 2203 | 2700 |
2/0 | 4 x 70.0 | sm / 35.0 | 37 | 3082 | 3750 |
3/0 | 4 x 95.0 | sm / 50.0 | 43.5 | 4208 | 5000 |
4/0 | 4 x 120.0 | sm / 70.0 | 47 | 5388 | 6350 |
300mcm | 4 x 150.0 | sm / 70.0 | 51 | 6540 | 7650 |
350mcm | 4 x 185.0 | sm / 95.0 | 56 | 8159 | 9350 |
500mcm | 4 x 240.0 | sm / 120.0 | 62.5 | 10546 | 11600 |
Nominal voltage Uo/U | [V] | 600 / 1000 volt | |
Test voltage | [V]AC | 4000 | |
Temperature range | in motion | -5°C till +70°C | |
fixed | -20°C till +70°C | ||
Operating temperature | short circuit | °C | 160 |
Short circuit time | max. | [sec] | 5 |
Bending radius | one time / fixed | x diameter | 12 |
in motion | x diameter | 15 | |
Flammability | standard | EN 60332-1-2 |