1.Mainly used to indicate the status of a (sub)part of the
installation, heater, motor, fan and pump etc.
2.Rated voltage: 230VAC
3.Lamp: Neon lamp, LED
4.Lens color: Red, green, orange and transparent
5.Degree of protection: IP20
6.Connection:1-25mm rigid conductor
7.Mounting: DIN rail EN60715
8.Size:
1. Low service duration, minimum power consumption |
2. Compact design in modular size, easy installation |
| |
3. Rated voltage: | 230V AC, 50/60Hz |
4. Colour: | Red, green, yellow |
5. Connection terminal: | Pillar terminal with clamp |
6. Connection capacity: | Rigid conductor 10mm2 |
7. Installation: | - On symmetrical DIN rail |
- Panel mounting |
8. Illumination type: | A. Illumination: LED |
- Max power: 0.6W |
- Service duration: 30, 000 hours |
B. Illumination: Neon bulb |
- Max power: 1.2W |
- Service duration: 15, 000 hours |
Technical data:
Standard: | IEC 60947-5-1 |
Frequency: | 50 or 60Hz |
Operational current: | ≤20mA |
LED life: | ≥30000hours |
Rated impulse withstand voltage Uimp: | 5000V |
Dielectric test voltage at ind.Freq.For 1min.: | 2.8KV |
Mounting category: | II ,III |
Pollution degree: | 2 |
Protection class: | IP20 |
Tightening torque: | 1.2N.m |
Standard mounting: | 35mm DIN rail |
Ambient temperature: | -5ºC to +40ºC |
Storage temperature: | -25ºC to +70ºC |