Flange Type Cast Iron Material Ultrasonic Heat Meter DN50~DN300

China Flange Type Cast Iron Material Ultrasonic Heat Meter DN50~DN300, Find details about China Flange Heat Meter, Ultrasonic Heat Meter from Flange Type Cast Iron Material Ultrasonic Heat Meter DN50~DN300

Model NO.
213D
Type
Ultrasonic Flow Meter
Measuring Media
Liquid
Measuring Principle
Ultrasonic
Measurement Object
Closed Pipeline
Certification
ISO
Trademark
ZPMETER
Origin
China
HS Code
9026100000
Model NO.
213D
Type
Ultrasonic Flow Meter
Measuring Media
Liquid
Measuring Principle
Ultrasonic
Measurement Object
Closed Pipeline
Certification
ISO
Trademark
ZPMETER
Origin
China
HS Code
9026100000
-Product application in heating metering
-Pipe material: ductile iron/stainless steel
-Ultrasonic metering, no mechanical wear, with excellent reliability, stability
-Accuracy level: Class 2
-Range ratio: R25/R50/R100
-Temperature range: (5~95)ºC
-Temperature range: (2~90)K
-Compliance with standards: GB/T 32224 / EN1434
-Communication interface diversity: MBUS, RS485, pulse, LoRJA, NB-IoT, Zigbee
DiameterMin.FlowNominal FlowMax. FlowLength
qmin(m³/h)qp(m³/h)qmax(m³/h)mm
DN 500.61530200
DN 651.02550200
DN 801.64080225
DN 1002.460120250
DN 1254100200250
DN 1506150300300
DN 20010250500350
DN25016400800450
DN300246001200500
Accuracy ClassClass 2
ConnectionFlange Connection
Pressure Loss≤20KPa
Max.Working Pressure≤1.6MPa
Temperature Sensor3m standard two-wire PT1000 paired temperature sensor(Wire length adjustable)
Data Storage24 months history data 
Power outage protectionAfter a power failure, the accumulated flow rate recorded before the power failure and the corresponding time can be saved, and the metering function will be automatically restored after the power is restored.
Interface & CommunicationInfrared,M-Bus,RS485
Infrared,NB-IoT
PowerBuild in ER34615 Water Proof Lithium Battery /DC24V 
Protection ClassIP68
Environmental Class B
Temperature range(4~95)ºC
Temperature difference range(2~90)K
Installation MethodWater inlet or return (default water inlet)
InstallationLarge LCD monitor
DurabilityDistribution by a magnetic field with an intensity of less than 100 kA/m, no effective to the metering and remote transmission characteristics of the heat meter
Communication line wiring instructionsM-BUS wiring: black, white (no polarity), input voltage DC24~42V
RS-485 wiring: red wire to vcc, blue wire to GND, yellow wire to A, green wire to B