ISO 834 Vertical Fire Resistance Testing Equipment

China ISO 834 Vertical Fire Resistance Testing Equipment, Find details about China Fire Resistance Test Furnace, Fire Resistance Furnace from ISO 834 Vertical Fire Resistance Testing Equipment

Model NO.
AIC-834
Maximum Consumption of LPG
260m3/H
Maximum Air Consumption
2690 M3/H
Air Pressure
6000PA
Thermocouple
8 PCS
Delivery Time
About 3 Months
Test Object
Building Materials
Trademark
AI
Transport Package
Plywood Case
Specification
White
Origin
China
HS Code
9031809090
Model NO.
AIC-834
Maximum Consumption of LPG
260m3/H
Maximum Air Consumption
2690 M3/H
Air Pressure
6000PA
Thermocouple
8 PCS
Delivery Time
About 3 Months
Test Object
Building Materials
Trademark
AI
Transport Package
Plywood Case
Specification
White
Origin
China
HS Code
9031809090

urnace name:Fire resistance test system -Vertical furnace
The use of furnace: Fire resistance tests of single wall, various doors and partition.

  • Charging:armoured concrete slab,steel-concrete composite slab and kinds of doors and roller blinds.
  • Specification of Charging:Size of frame or wall(Maximum fire surface):3000×3000mm
  • Maximum temperature in furnace:1150ºC
  • Inside dimension of furnace:3000×3000×1500mm
  • Observation hole:3 φ200mm
  • Data acquisition: types and channels

The air temperature in furnace is 8 channels

  • Gas:Liquefied petroleum gas.

Calorific value:4.18×8500KJ/m3

  • Maximum consumption of liquefied petroleum gas:260m3/h
  • Maximum air consumption:2690 m3/h
  • Air pressure:6000Pa
  • Pressure from liquefied petroleum gas to the front manifold:15000Pa
  • Burner's name and quantity:High speed thermostat burner(Automatic ignition, flame monitoring) 8 units
  • Liquefied petroleum gas pressure before burner:5000Pa
  • Air pressure before burner:5000Pa
  • Loading and unloading method of heated workpiece:crown block
  • Outer surface temperature of furnace wall(When the inner furnace temperature is 1150ºC):≤45ºC+room temperature
  • 8 thermocouples in the furnace .
  • Working system:Intermittent operation, each heating is not more than 3 hours.

 

TIME(min)TEMP(ºC)TIME(min)TEMP(ºC)TIME(min)TEMP(ºC)TIME(min)TEMP(ºC)TIME(min)TIME(ºC)TIME(min)TEMP(ºC)

 

0

 

20

 

40

 

878

 

80

 

963

 

120

 

1010

 

200

 

1066

 

280

 

1121

 

5

 

538

 

45

 

892

 

85

 

971

 

130

 

1017

 

210

 

1072

 

290

 

1128

 

10

 

704

 

50

 

905

 

90

 

978

 

140

 

1024

 

220

 

1079

 

300

 

1135

 

15

 

760

 

55

 

916

 

95

 

985

 

150

 

1031

 

230

 

1086

  

 

20

 

795

 

60

 

927

 

100

 

991

 

160

 

1038

 

240

 

1093

  

 

25

 

821

 

65

 

937

 

105

 

996

 

170

 

1045

 

250

 

1100

  

 

30

 

843

 

70

 

946

 

110

 

1001

 

180

 

1052

 

260

 

1107

  

 

35

 

862

 

75

 

955

 

115

 

1006

 

190

 

1059

 

270

 

1114

  


Factory overview

ISO 834 Vertical Fire Resistance Testing Equipment
Customer Feedback 

Germany
ISO 834 Vertical Fire Resistance Testing Equipment
USA
ISO 834 Vertical Fire Resistance Testing Equipment
Transporation
ISO 834 Vertical Fire Resistance Testing Equipment
FAQ

1.What's the delivery time?

About 3 months.

2.What's your payment terms?
30% paid by T/T in advance,70% paid by by T/T before shipping.

3.What's your guarantee terms?
The warranty of all products is 1 year.During this period,we are responsible for all faults caused by us.And we can supply life-long technical support. 

4.Can you supply training?
We can supply training in our factory and online training for free.If onsite installation and training are required,please pay for tickets,accommodation and salary USD150/Day for every person.