China Low Cost AC Variable Frequency Drive 220V 60Hz to 220V 50Hz, Find details about China AC Variable Frequency Drive, Drive 220V 60Hz from Low Cost AC Variable Frequency Drive 220V 60Hz to 220V 50Hz
Item | Z900E | |
tandard Function | Control mode | Sensorless flux vector control(SFVC) Voltage/Frequency(V/F) control |
Maximum frequency | Vector control:0-320Hz V/F control:0-3200Hz | |
Carrier frequency | 1-16kHz The carrier frequency is automatically adjusted based on the load features. | |
Input frequency resolution | Digital setting:0.01Hz Analog setting:maximum frequency x 0.025% | |
Startup torque | G type:0.5 Hz/150%(SFVC) P type:0.5 Hz/100% | |
Speed range | 1:100(SFVC) | |
Speed stability accuracy | ±0.5%(SFVC) | |
Torque control accuracy | ± 5% (CLVC) | |
Overload capacity | G type:60s for 150% of the rated current,3s for 180% of the rated current. P type:60s for 120% of the rated current,3s for 150% of the rated current. | |
Torque boost | Fixed boost Customized boost 0.1%-30.0% | |
V/F Curve | Straight-line V/F curve Multi-point V/F curve N-power V/F curve(1.2-power,1.4-power,1.6-power,1.8-power,square | |
V/F separation | Two types:complete separation;half separation | |
Ramp mode | Straight-line ramp S-curve ramp Four groups of acceleration/deceleration time with the range of 0.0-6500.0s | |
DC braking | DC braking frequency:0.00 Hz to maximum frequency Braking time:0.0-100.0s Braking action current value:0.0%-100% | |
JOG control | JOG frequency range:0.00-50.00Hz JOG acceleration/deceleration time:0.0-6500.s | |
Onboard multiple | It implements up to 16 speeds via the simple PLC function or combination of X terminal states | |
Onboard PID | It realizes process-controlled closed loop control systerm easily | |
Auto voltage regulation(AVR) | It can keep constant output voltage automatically when the main voltage changes | |
Overvoltage/Overcurrent stall control | The current and voltage are limited automatically during the running process so as to avoid frequent tripping due to overvoltage/over current | |
Torque limit and control | It can limit the torque automatically and prevent frquent over current tripping during the running process | |
Instantaneous stop doesn't stop | The load feedback energy compensates the voltage reduction so that the AC drive can continue to run for a short time | |
Rapid current limit | It helps to avoid frequent over current faults of the AC drive | |
High performace | Control of asynchronous motor is implemented throgh the high-performance current vector Control technology | |
Timing control | Time range:0.0-6500.0 minutes | |
Communication methods | RS485 | |
Running command channel | Given by the panel,control terminals.Serial communication port,can be switched by many ways | |
Frequency source | 10 kinds of frequency source,given by Digital analog voltage,analog current,Pulse,serial port.can be switched by man ways. | |
Auxiliary frequency source | 10 kinds of Frequency source,can easily realize Micro ajustment,frequency Synthesizer. | |
Input and output | Input terminal | 6 digitak input terinals,one of which supports up to100kHz high-speed pulse input. 2 analog input terminal,one of which only supports 0-10v voltage input and the other supports 0-10v voltage input or 4-20 mA current input |
Output termianl | 1 digital output terminal 1 relay output terminal 1 analog output termianl:that supports 0-20 mA current output or 0-10V voltage ouput | |
Operation on the operation panel | LED display | It displays the parameters |
Key locking and cuntion selection | It can lock the keys partially or completely and define the function range of some keys so as to prevent mis-function | |
Protection mode | Motor short-circuit detection at power-on,output phase loss protection,over-curent protection,over-voltage protection,under voltage protection,overheat protection and overload protection. | |
Environment | Installation location | Indoor,avoid direct sunlight,dust,corrosive gas,combustible gas,oil smoke,vapour drip or salt |
Altitude | Lower than 1000m(Lower the grades when using higher then 1000m) | |
Ambient temperature | -10°C~40°C(Lower the grades if the ambient temperature is between 40°C and 50°C) | |
Humidity | Less than 95%RH,without condensing | |
Vibration | Less than 5.9 m/s² (0.6g) | |
Storage temperature | -20°C~60°C |
Model | Rated output power | Rated Output Current | Overload Capacity | Applicable motor |
(KW) | (A) | (60s)(A) | (KW) | |
Z900-2S0.4GE | 0.4 | 5.4 | 3.75 | 0.4 |
Z900-2S0.75GE | 0.75 | 7.2 | 7.5 | 0.75 |
Z900-2S1.5GE | 1.5 | 10 | 10.5 | 1.5 |
Z900-2S3.7GE | 3.7 | 16 | 10.0 | 3.7 |
Z900-2S5.5GE | 5.5 | 21 | 20 | 5.5 |
Z900-2S7.5GE | 7.5 | 31 | 30 | 7.5 |
Model | Rated output power | Rated Output Current | Overload Capacity | Applicable motor |
(KW) | (A) | (60s)(A) | (KW) | |
Z900-4T0.4GE | 0.4 | 3.4 | 1.2 | 0.4 |
Z900-4T0.75GE | 0.75 | 3.8 | 2.5 | 0.75 |
Z900-4T1.5GE | 1.5 | 5 | 3.7 | 1.5 |
Z900-4T2.2GE | 2.2 | 5.8 | 5.0 | 2.2 |
Z900-4T3.7GE/5.5PE | 3.7/5.5 | 10.0/15.0 | 9.0/13.0 | 3.7/5.5 |
Z900-4T5.5GE | 5.5 | 15 | 13 | 5.5 |
Z900-4T7.5GE/11PE | 7.5 | 20 | 17 | 7.5 |
Z900-4T11GE/15PE | 11/15 | 26/35 | 25/32 | 11/15 |
Z900-4T15GE/18.5PE | 15/18.5 | 35/38 | 32/37 | 15/18.5 |
Z900-4T18.5GE/22PE | 18.5/22 | 38/46 | 37/45 | 18..5/22 |
Z900-4T22GE/30PE | 22/30 | 46/62 | 45/60 | 22/30 |
Z900-4T30GE/37PE | 30/37 | 62/76 | 60/75 | 30/37 |
Z900-4T37GE/45PE | 37/45 | 76/90 | 75/90 | 37/45 |
Z900-4T45GE/55PE | 45/55 | 90/105 | 90/110 | 45/55 |
Z9010-4T55GE | 55 | 105 | 110 | 55 |
Z900-4T75PE | 75 | 140 | 150 | 75 |
Z900-4T75GE/90E | 75/90 | 140/160 | 150/176 | 75/90 |
Z900-4T90GE/110PE | 90/110 | 160/210 | 176/210 | 90/110 |
Z900-4T110GE/132PE | 110/132 | 210/240 | 210/253 | 110/132 |
Z900-4T132GE/160PE | 132/160 | 240/290 | 253/300 | 132/160 |