China Transformer Oil Power Factor Test Set / Tan Delta Analyzer, Find details about China Tan Delta Tester, Tan Delta Meter from Transformer Oil Power Factor Test Set / Tan Delta Analyzer
2. Tan delta meter Specifications
Accuracy: Cx ±(reading×1%+1pF)
PF ±(reading×1%+0.00040)
Interference Ratio: Interference current is no more than 2 times of the test current
PF Range: No limit, Resolution 0.001%, C/L/R specimen test
Input current range: 10μA~1A
Internal HV: 0.5~10kV / 200mA (max)
HV Adjust: Rise or fall smoothly
HV Accuracy: ±(reading×1%+10V) Resolving 1V
Frequency select: 60Hz single point, locked 55Hz/65Hz double point, locked
Test Time: 40S typical
Power Supply: 180V~270V 50Hz/60Hz auto
Operating Temperature: 0ºC~60ºC
storage Temperature: -20ºC~60ºC
Humidity: <90%
3.tan delta meter
Tan Delta (TD) - also referred to as Dissipation Factor or sometime even Power Factor - is an excellent diagnostic test that provides an indication as to the quality of the dielectric insulation used in electrical apparatus. By analyzing the dielectric losses in theinsulation, the GDGS Series of Tan Delta test instruments provide the testing engineer with a versatile high voltage diagnostic system that is suitable for testing MV cable such as XLPE, EPR, PE and PILC. In addition, other electrical apparatus such as capacitors, transformers and large rotating machines can also be diagnosed