with Battery Portable Precision Current Transformer Testing CT PT Analyzer

China with Battery Portable Precision Current Transformer Testing CT PT Analyzer, Find details about China CT Analyzer, CT PT Analyzer from with Battery Portable Precision Current Transformer Testing CT PT Analyzer

Model NO.
GF1061
Customized
Customized
Keyword
Portable CT PT Analyzer
Model
Current Transformer Testing CT PT Analyzer
GF1061
CT PT Analyzer
Accuracy
0.05%
Automatic Frequency Variation Range
0.1-60Hz
Weight (Kg)
4
LCD
7 Inch Touch Color TFT LCD
Ratio
CT: 1-50000; PT: 1-10000
Phase Error
1 Min
Ratio Error
0.02%
Trademark
GFUVE
Transport Package
Standard Export Wooden Box
Specification
280 x 250 x 160
Origin
Beijing, China
HS Code
888550000
Model NO.
GF1061
Customized
Customized
Keyword
Portable CT PT Analyzer
Model
Current Transformer Testing CT PT Analyzer
GF1061
CT PT Analyzer
Accuracy
0.05%
Automatic Frequency Variation Range
0.1-60Hz
Weight (Kg)
4
LCD
7 Inch Touch Color TFT LCD
Ratio
CT: 1-50000; PT: 1-10000
Phase Error
1 Min
Ratio Error
0.02%
Trademark
GFUVE
Transport Package
Standard Export Wooden Box
Specification
280 x 250 x 160
Origin
Beijing, China
HS Code
888550000
GF1061 Portable Precision Current Transformer Testing CT PT Analyzer With Battery

GF1061 portable CT PT analyzer is mainly used for field or lab testing, it can finish the measurements (M) and protection (P) class CT, PT and TYP class CT. Adopt 7 inch touch TFT LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data. The CT PT Analyzer is the most complete and easy-to-use testing system for protection and metering CTs according to IEEE and IEC standards.
with Battery Portable Precision Current Transformer Testing CT PT Analyzer

Main functions
I. Current Transformer (CT)II. Voltage Transformer (PT)
1. Magnetization curve1. Excitation characteristic test
2. Transformation ratio test2. Transformation ratio test
3. Polarity3. Polarity 
4. 5% and 10% error curve4.  Ratio error, phase error
5. Accuracy limiting factor (ALF)5. Degauss
6. Degauss6. Calculation of knee point value
7. Ratio error, phase error7. Actual secondary load test (burden test)
8. Automatic calculation of excitation knee
point value
8. Resistance test
9. Actual secondary load test (burden test)
10. Resistance test
11. Secondary time constant (Ts)
12. Remanence coefficient (Kr)
13. Transient dimensioning factor (Ktd)
14. Peak instantaneous error (Er)
15. Magnetizing inductance (LU)
16. Instruments security factor(FS)
17. Composite error
Parameters
Electrical parameters
Accuracy0.05%
Power supplyAC 220V±10% or AC 120V±10%, 50/60Hz or Battery
Output voltage0-100Vrms
Output current0-5Arms (20A peak-value)
Output power0-400 VA (1500 VApeak)
Automatic frequency variation range0.1-60Hz
Equivalent excitation voltage≤5000V
Accuracy≤0.5%
Secondary winding DC resistance measurementRange0.1-1000Ω
Accuracy≤0.05%
Secondary actual load measurementRange5VA-1000VA
Accuracy≤0.5%±0.1VA
CT/PT phase error measurementAccuracy±1min (typical) / 3 min (guaranteed)
Resolution0.1min
CT ratio error measurementRange1-50000
Accuracy≤0.05%
PT ratio error measurementRange1-10000
Accuracy≤0.05%
Standards
Reference standardsGB1207-2006, GB1208-2006, GB16847-1997
IEC60044-1, IEC60044-6, IEC61869-2, ANSI/IEEE C57.13
Safety standardsGB 4793.1-2007
EMCEMC standard 89/336/EEC
FCC Subpart B of Part 15 Class A
IEC 1000-4-2 /3 /4 /6
Mechanical parameters
Overall dimension (L x W x H) (mm)280 x 250 x 160
Weight (kg)  ≤4
Environmental conditions
Relative humidity   Relative humidity 5%-95% not condensing
Operating temperature-10°C to +50°C
Storage temperature-20°C to +70°C
Altitude≤1000m
with Battery Portable Precision Current Transformer Testing CT PT Analyzer
http://guangfuhui.en.made-in-china.com