China Eaton Blade UPS Power System Scalable Double-Conversion Backup Power, Find details about China Online UPS, Eaton Blade UPS from Eaton Blade UPS Power System Scalable Double-Conversion Backup Power
Power Rating | 8-60 kW |
Voltage | 208 Vac and 400 Vac models |
Frequency | 50/60 Hz |
Topology | Double conversion on demand |
Efficiency | Up to 98% |
Configuration | Rackmount |
Product Series | Eaton |
GENERAL | |
Power rating | 12 kW per UPS module |
Efficiency | up to 98% |
Heat dissipation | 371W/1266 BTU/hr at 100% rated load |
Cooling | Fan cooled, temperature microprocessor monitored; front air entry, rear exhaust |
Audible noise, normal operation | <60 dBA at 1 meter |
OPERATION | |
Nominal Input Voltage | 220/230/240 |
Input Voltage Range | +15%, -20% |
Operating Frequency | 50 Hz Nominal (adjustable limits +_ 0.01 Hz to +_ 3Hz |
Nominal Output Voltage | 220/230/240 |
Output Voltage Regulation | ± 3% for input voltages of +15% to -20% |
Output Voltage Waveform | Sine wave |
Output Voltage THD | 5% or less at rated kW load |
Overload Capacity | 150% surge and 125% for10 min. on line, 150% surge and 110% for 10 minutes on inverter |
Transfer Time | 0 ms |
Lightning, Surge & Noise Protection | 2000:1 spike attenuation using ANSI/IEEE C62.41 and C62.45 Category A and Category B tests. Common Mode - >120 dB. Normal Mode - >60dB |
Efficiency | 85 / 88 / 91 / 90 |
Safety Certification | UL, CSA (cUL), Complies with European Low Voltage Directive 73/23/EEC |
EMI Compliance | FCC Class A, Complies with European Electromagnetic Compatibility Directve 89/336/EEC |
Testing Standards | ANSI/EEE C62.41 (1991); ANSI/EEE C62.45 (2002); EN62040-2 |
Communication | RS-232 serial port (DB-25), plus contact closures |
ENVIROMENTAL | |
Operating Temperature | 0 to 40° C |
Storage | -20° C to +60° C |
Relative Humidity | 0 to 95% without condensation |
Audible Noise at 1m | 47 / 49 / 51 / 51 |
Altitude | 3, 050m (10,000 ft.) maximum |