parameter name | Weight and Size | |||
Model no. | JN-MPPT-MINI | JN-MPPT-AL | JN-MPPT-BL | JN-MPPT-CL |
weight(kg) | 1.25Kg | 1.5kg | 2.3kg | 3.6kg |
Size L*D*H(mm) | 156*134*81mm | 186*146*81mm | 240*170*97mm | 340*208*95mm |
Protection function | instruction |
PV over voltage protection | When the PV array charging voltage exceeds the controller's rated input voltage range, charging will stop. |
Battery polarity reverse connection | When the polarity of the battery is reversed, the controller will not work and will not be damaged. After correcting the wiring error, re-open the opportunity to continue normal operation. |
Battery over discharge protection | When the battery voltage is lower than the set undervoltage value, the discharge of the battery will be automatically stopped to prevent the battery from being over-discharged and damaged. |
Battery overload protection | When the controller output current is greater than the set value, the load output will be automatically stopped to prevent the battery from being over-discharged and damaged. |
Battery over volatge protection | When the battery voltage reaches the overvoltage protection setting value, the battery will be automatically stopped to prevent the battery from being overcharged and damaged. |
Night anti-reverse protection | At night, since the battery voltage is greater than the voltage of the photovoltaic module, the automatic protection prevents the battery voltage from being discharged through the photovoltaic module; |
Equipment overheat protection | The controller has its own temperature sensor. When the temperature is higher than the set value, the charging will stop. When the temperature is lowered, it will automatically start to work. |
High voltage surge | This controller can only protect high-voltage surges with low energy. In areas with frequent lightning, it is recommended to install an external lightning arrester. |
ERROR | Indicator status and alarm icon | possible reason | Solution |
Array over voltage | Red light, icon flashes | More PV arrays in series | Disconnect the PV array, reduce the number of PV arrays connected in series, and ensure that the PV array open circuit voltage does not exceed the set value in the "Table 3-1 PV Electrical Parameters" table; |
Battery over voltage (overcharge) | Red light on,OVDandflashes | 1. The controller overvoltage protection point is lower than the highest charging range; 2. The battery is aging or over-discharged; 3. The battery is over-discharged; 4. Large dynamic changes in load; | 1. Reset the battery overvoltage protection point through the device button or PC host computer or APP; 2. The battery needs to be replaced after aging; 3. Over-discharge requires manual setting of battery voltage level; 4. Reduce large dynamic changes in load; |
Battery under voltage (over discharge) | Under and flashes | Battery voltage value is lower than the undervoltage protection setting | 1. Reduce or disconnect the load. If the alarm is released, the battery voltage returns to normal, indicating that the load power is too large or the battery voltage and capacity are low. It is easy to cause undervoltage protection with heavy load; 2. Disconnect the load controller and still alarm, the battery voltage does not return to the over-discharge recovery setting value, and the battery pack needs to be charged by PV or other means, so that the fault can be released after the battery pack voltage reaches the recovery point set value. |
The indicator light is off and the display is not displayed. | Battery voltage is lower than device startup voltage | ||
Heat sink overheating | Red light on, flashes | 1. The ambient temperature is too high, the heat dissipation of the equipment is poor, and the fan is not well ventilated; 2. The fan is damaged. | 1. Check the installation environment of the equipment, remove the debris of the equipment, and ensure that the fan is ventilated smoothly; 2. The fan needs to be replaced if it is damaged. |
Charge current | Red light on,Icharge flashes | Charging overcurrent protection check for abnormal current detection and malfunction | If you restart it several times, if you can't solve it, you need to go back to the factory for repair; |
Over loading | Red light on, flashes | Load power is too large | 1. Reduce the load power; 2. Restart and release the fault; 3. Without excessive sensibility and capacitive load; |
Remark: The above fault phenomenon can not be turned on except the battery under voltage, other faults can refer to the fault information through the PC background or mobile APP; |
parameter name | Parameter value (and adjustable range) | |||||||||||||||
MODEL | JN-MPPT-MINI | JN-MPPT-AL | JN-MPPT-BL | JN-MPPT-CL | ||||||||||||
Current rating (A) | 10 | 20 | 30 | 30 | 40 | 50 | 30 | 40 | 50 | 60 | 70 | 50 | 60 | 80 | 100 | 120 |
Maximum charging current (A) | 10 | 20 | 30 | 30 | 40 | 50 | 30 | 40 | 50 | 60 | 70 | 50 | 60 | 80 | 100 | 120 |
PV maximum input power (12V) (W) | 150 | 250 | 400 | 400 | 500 | 600 | 400 | 500 | 600 | 750 | 850 | 600 | 750 | 1000 | 1200 | 1450 |
PV maximum input power (24V) (W) | 300 | 500 | 800 | 800 | 1000 | 1200 | 800 | 1000 | 1200 | 1500 | 1700 | 1200 | 1500 | 2000 | 2400 | 2900 |
PV maximum input power (48V) (W) | 600 | 1000 | 1600 | 1600 | 2000 | 2400 | 1600 | 2000 | 2400 | 3000 | 3400 | 2400 | 3000 | 4000 | 4800 | 5500 |
PV maximum input power (96V) (W) | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- |
Output maximum current A | 10 | 15 | 15 | 15 | 20 | 25 | 15 | 20 | 25 | 30 | 35 | -- | -- | -- | -- | -- |
System identification voltage range v | 12V battery sysem | DC9V-DC16V | ||||||||||||||
24V battery system | DC18V-DC32V | |||||||||||||||
48V battery system | DC42V-DC60V | |||||||||||||||
96V battery system | 96V is a stand-alone system | |||||||||||||||
PV panel open circuit input voltage range v | 20V~100V(12V battery system) | |||||||||||||||
40V~145V(24V battery system) | ||||||||||||||||
80V~145V(48V battery system) | ||||||||||||||||
120V~250V (96V battery system) | ||||||||||||||||
MPPT efficiency | >99.5% | |||||||||||||||
Conversion efficiency | >98% | |||||||||||||||
Operating mode | The default is the household mode 24H |
Lead-acid batteries | |||||
System rated voltagev | 12V system(1 in series) | 24Vsystem(2in series) | 48Vsystem(4in series) | 96V system(8series) | 12Vdefault |
Over voltage (overcharge)(v) | 13~17V | 26~34V | 52~68V | 104~136V | 15.5V |
Over voltage return (v) | 13~17V | 26~34V | 52~68V | 104~136V | 15V |
Charge limit voltage(v) | 9~15V | 18~30V | 36~60V | 72~120V | 14.9V |
Boost charge(v) | 9~15V | 18~30V | 36~60V | 72~120V | 14.4V |
Boost charge return(v) | 9~15V | 18~30V | 36~60V | 72~120V | 13.9V |
Float voltage (v) | 9~15V | 18~30V | 36~60V | 72~120V | 13.8V |
Over discharge (v) | 7~13V | 14~26V | 28~52V | 56~104V | 10.8V |
Over discharge return(v) | 9~15V | 18~30V | 36~60V | 72~120V | 13.1V |
Ternary lithium battery (single section 3.7V) | |||||
System rated voltagev | 12Vsystem(default 3 in series) | 24V system(default 6 in series) | 48Vsystem(default 12 in series) | 96Vsystem (d efault24seires) | 3in series default value |
Over voltage (v) | 10.5~15V | 21~30V | 42~60V | 84~120V | 13.5V |
Over voltage return (v) | 10.5~15V | 21~30V | 42~60V | 84~120V | 12.6V |
Charge limit voltage(v) | 10.5~15V | 21~30V | 42~60V | 84~120V | 12.6V |
Boost charge(v) | 10.5~15V | 21~30V | 42~60V | 84~120V | 12.3V |
Boost charge return(v) | 10.5~15V | 21~30V | 42~60V | 84~120V | 12V |
Float voltage (v) | 10.5~15V | 21~30V | 42~60V | 84~120V | 12.3V |
Over discharge (v) | 6~12V | 12~24V | 24~48V | 48~96V | 9.3V |
Over discharge return (v) | 6~13.5V | 12~27V | 24~54V | 48~108V | 10.5V |
Lithium LIFEPO4(single section 3.2V) | |||||
System rated voltage | 12Vsystem(default 3 in series) | 24V system(default 6 in series) | 48Vsystem(default 12 in series) | 96Vsystemdefault24seires) | 3in series default value |
Over voltage (v) | 9~12V | 18~24V | 36~48V | 72~96V | 11.7V |
Over voltage return(v) | 9~12V | 18~24V | 36~48V | 72~96V | 11.1V |
Charge limit voltage(v) | 9~12V | 18~24V | 36~48V | 72~96V | 11.1V |
Boost charge limit (v) | 9~12V | 18~24V | 36~48V | 72~96V | 10.8V |
Boost charge return(v) | 9~12V | 18~24V | 36~48V | 72~96V | 10.2V |
Float voltage(v) | 9~12V | 18~24V | 36~48V | 72~96V | 10.8V |
Over discharge (v) | 6~9V | 12~18V | 24~36V | 48~72V | 8.4V |
Over discharge return(v) | 6~12V | 12~24V | 24~48V | 48~96V | 9.6V |
Storage temperature(ºC) | -40ºC~80ºC | ||||
Humidity(ºC) | 10% ~ 90% no condensation |