China Tc120kVA 3: 1 True on-Line Double Conversion Design UPS Providing All Power Protection, Find details about China Low Frequency Online UPS, UPS with Inverter Charger from Tc120kVA 3: 1 True on-Line Double Conversion Design UPS Providing All Power Protection
MODEL | TC10K | TC15K | TC20K | TC30K | TC40K | TC60K | TC80K | TC100K | TC120K | |
Capacity | 10KVA | 15KVA | 20KVA | 30KVA | 40KVA | 60KVA | 80KVA | 100KVA | 120KVA | |
Power | 8KW | 12KW | 16KW | 24KW | 32KW | 48KW | 64KW | 80KW | 96KW | |
Power Factor | 0.8 | |||||||||
Input | Phase | 3 phase 4 wire and ground | ||||||||
Voltage Range | 380V±20%(3 phase), phase voltage 220V | |||||||||
Frequency Range | 45 - 65Hz | |||||||||
Rectifier | 3 phase 6 pulses, 12 pulses is optional | |||||||||
Output | Phase | 3 phase 4 wire and ground | ||||||||
Wave form | Pure sine wave | |||||||||
Crest Factor | 3:01 | |||||||||
Rated voltage | 380/400/415Voptiona+ -1% for static load, 5% forfluctuant load | |||||||||
Phase voltage setting | 200 - 244VAC, pls confirm when order | |||||||||
Transient response | +/-5%, 10ms | |||||||||
Frequency | 50 / 60 Hz + / - 0.05% | |||||||||
Total harmonic distortion | < 3%(linear load, < 5%( nonlinear load) | |||||||||
Short circuit current | Short current for 0.1s (200% current) | |||||||||
Overload capacity | Overload 125% for 10 Mins, 125%-150% for 1min .automatically resume when load become normal | |||||||||
Battery | Battery | Maintenance free lead-acid cell | ||||||||
DC Voltage | 384VDC | 396VDC | ||||||||
Max Charge Current | 6-30A adjustable | |||||||||
Bypass | Type | Static state + manual maintenance bypass | ||||||||
Input Phase | 3 phase 4 wire and ground | |||||||||
Input voltage range | 15% - 25% (the front control panel selectable) | |||||||||
Transfer time | Inverter / bypass transfer switch time(Overload): 0ms inverter / bypass transfer switch time (fault inverter) 1ms | |||||||||
Efficiency | Whole unit | >80% | ||||||||
Inverter | 91 | 91 | 92 | 92 | 93 | 93 | 95 | 95 | 95 | |
Remote signaling | Dry contact (battery low, battery discharging, bypass/ fault); output 12Vdc/80mA,Optional parts | |||||||||
Communication interface | RS232 ( SNMP , modem optional ) | |||||||||
Running temperature | 0-40 degree Celsius | |||||||||
Relative Humidity | Less than 95% (without condensing) | |||||||||
Noise at 1 M | less than 60 dB | |||||||||
Degree of protection | IP20 | |||||||||
Applicable Standards | EN50091-1-EMC EN50091-2liv.A | |||||||||
Product size(mm) | 780*580*1170 | 1000*660*1450 | 1200*900*1820 | |||||||
product weight(Kg) | 180.00 | 280 | 380 | 440 | 520 | 670 | 690 | 790 | 790 | |
Package size(mm) | 945*745*1395 | 1135*810*1755 | 1450*1110*1880 | |||||||
Package weight(Kg) | 200.00 | 300 | 400 | 460 | 550 | 700 | 750 | 850 | 850 |