6kv/12kv/15kv/24kv/38kv, 50Hz/60Hz, Indoor 50Hz/60Hz PCM Protection and Control Vacuum/Sf6 Gas /Switchgear Panel

China 6kv/12kv/15kv/24kv/38kv, 50Hz/60Hz, Indoor 50Hz/60Hz PCM Protection and Control Vacuum/Sf6 Gas /Switchgear Panel, Find details about China Switchgear, Control Panel from 6kv/12kv/15kv/24kv/38kv, 50Hz/60Hz, Indoor 50Hz/60Hz PCM Protection and Control Vacuum/Sf6 Gas /Switchgear Panel

Model NO.
KYN
Trademark
HEMG
Transport Package
Wooden
Specification
15KV/27KV/38KV, 50HZ/60HZ,
Origin
China
Model NO.
KYN
Trademark
HEMG
Transport Package
Wooden
Specification
15KV/27KV/38KV, 50HZ/60HZ,
Origin
China
Summary
HKYN61-33KV Type Removable AC Metal-clad Switchgear (short for HKYN61) is complete set distributing equipment for 33kV, 3 phase, 50Hz single bus-bar and single bus-bar section system. It main used for electric power network used as receiving and distributing power energy and also for control,monitor,and protection.
The main switch adopts HZN85-33 Vacuum circuit breaker or Schneider SF series,ALSTOM FP series SF6 circuit breaker, have the advantages such as compact structure,superior performance,high reliability.
HKYN61 meet IEC298,GB3906-91 standard, have the "five Prevention" function,high structural strength,Component arrangement reasonable,have complete scheme,can extensible, is a ideal new type distributing equipment.


1.     Service Conditions
   a. The ambient air temperature: +40ºC to -15ºC.
b. Altitude ≤ 4500 M
c. The relative humidity :
Daily average value is not more than 95%
Monthly average value is not more than 90%
d. The earthquake intensity does not exceed  8 degrees,
f. Around air isn't polluted by corrosive or combustibility gas,Vapor.
If the service conditions of products is not under above conditions, it will be negotiated by user and manufacture.
2.     Technical data and requirement
2.1 Technical data for KYN61
NoItem UnitData
1Rated voltagekV33KV
2Rated frequency Hz 50/60
3Rated current of the main bus-barA630,1250,1600,2000
4Rated current of the branch bus-barA 630,1250,1600,2000
5Rated insulation level 1 min Power frequency withstand voltagekVPhase to phase
Phase to earth
Primary insulation breakers
95115
Lighting impulse withstand voltage 185215
1 min Power frequency withstand voltage for auxiliary Control circuit V2000
6Rated Short circuit breaking currentKA25, 31.5
7Rated short circuit making current (peak)kA63, 80
8 Rated short-time peak withstand current kA63, 80
94 S short-time withstand currentkA25, 31.5
10Power frequency withstand voltage for auxiliary Control circuitV 110 ,≈220
11Protecting level  Enclosure IP 4X, Compartments IP2X
12Dimension (W*D*H)mm1200 or 1400*2800*2600
 
2.2 Technical Data for ZN85-40.5 Vacuum Circuit Breaker
NoItem Unit Data
1Rated voltagekV 33KV
2. Rated frequency Hz 50/60
3Rated insulation levelI min power frequency withstand voltage  
 
kV
95
lightning impulse withstand voltage (peak) 185
4 Rated currentA 630 1250 1600 2000
5Rated short-time withstand current kA 25  31.5
6Rated peak withstand currentkA 63   80
7Rated short circuit duration time s4
8Rated short circuit Breaking Current kA 25   31.5
9Prospective transient recovery voltage kV With GB1984
10Rated short circuit Making CurrentkA63  80
11Open-close rated capacitor bank current A 400  630
12 Rated operation sequence  0-0.3s-CO-180s-co
13Rated short circuit breaking current breaking times Times 20
14 Opening time ms35~60
15 Closing time ms40~80
16Mechanical life Times 10000
17Open distance of contact mm 18~22
18Over travel mm6±1
19Contact allowed wear thickness mm3
20Average closing speed m/s 0.6~0.9
21Average opening speed (run 10mm) m/s1.6~2.0
22Contact closing bounce timems2
23 Three phase contact opening asynchronismms2
24 Three phase contact closing asynchronismms2
25 Every phase circuit DC resistance 60
26 Rated contact spring pressure under closing condition N3100
 
2.3  Technical Data for Schneider SF Type and ALSTOM series SF6 circuit break
NoItem Unit Data
1Rated voltagekV 33
2. Rated frequency Hz 50
3Rated insulation levelI min power frequency withstand voltage  
 
kV
95
lightning impulse withstand voltage (peak) 185
4 Rated currentA 630 1250 2000
5Rated short-time withstand current kA 25  31.5
6Rated short-time duration time s3
7Rated short circuit Breaking Current kA 25   31.5
8Rated short circuit Making CurrentkA 63    80
9Open-close rated capacitor bank current A 400~1750
12 Rated operation sequence  0-0.3s-CO-180s-co
O-180s-CO-180s-CO
13Rated short circuit breaking current breaking times Times 20
14 Opening time ms45±4 (SF)65 (FP)
15 Closing time ms68±4 (SF)70 (FP)
16Mechanical life Times 10000
 
2.4  Technical data and Accurate grade combination for LZZB9-35 Current Transformer
Primary current(A) Accurate grade combinationRated output {COS¢=0.8(lag), (VA)}Rated short time thermal current (kA)Short time dynamic stability current  (kA)
0.20.510P/1010P1510P20
30-1000.2/10P10
0.2/10P15
0.2/10P20
0.5/10P10
0.5/10P15
0.5/10P20
 
1530503020150 Iin375 Iin
15031.580
20044.580
300-500153050302054.580
600-80030505040306380
1000-2000405050503080100
 
2.5 Technical data and Accurate grade combination for LDBJ8-40.5 contact type current transformer.
Primary current(A) Accurate grade combination and the corresponding rated output Rated short time thermal current (kA)short time dynamic stability current  (kA)
0.2/10P100.5/10P100.2/0.510P10/10P10
5-30010/3020/3010/2020/20150 Iin2.5 Iin
40010/4015/4010/1520/2063160
50010/4015/4010/1525/2563160
60010/5030/5010/3030/3063160
750-80020/5030/5020/3030/3063160
1000-150030/5050/5030/5040/4080180
2000-315030/5050/5050/5050/50100180
2.5   Technical data for JN22-40.5 Earth Switch
NoItem Unit Data
1Rated voltagekV 33
2Rated insulation levelI min power frequency withstand voltage  
 
kV
85
lightning impulse withstand voltage (peak) 95
34s short-time withstand current kA 31.5
4Rated peak withstand current(peak) kA 80
5Rated short circuit Making Current (peak)kA80
 
3,Structure
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Scheme No 01020304
Main connecting diagram    
Main electrical
element
Circuit Breaker ZN85/SF/FP1111
Earth switch JN22-331111
CT- LZZB9-33 123
Electric Display DSN6-33 111
     
Function Overhead entry (out) Overhead entry (out)Overhead entry (out)Overhead entry (out)
Note  
 
 
Scheme No 05060708
Main connecting diagram    
Main electrical
element
Circuit Breaker ZN85/SF/FP1111
Earth switch JN22-331111
CT- LZZB9-33 123
Electric Display DSN6-331111
     
Function Cable entry (out) Cable entry (out) Cable entry (out) Cable entry (out)
Note  
 
 
 
 
 
 
 
Scheme No 09101112
Main connecting diagram    
Main electrical
element
Circuit Breaker ZN85/SF/FP1111
CT- LZZB9-33 123
     
     
     
Function Right(left)
connectiong
Right(left)
connectiong
Right(left)
connectiong
Right(left)
connectiong
Note  
 
 
 
Scheme No 13141516
Main connecting diagram    
Main electrical
element
CT- LZZB9-331123
     
     
     
     
Function Right(left)
connectiong
Right(left)
connectiong
Right(left)
connectiong
Right(left)
connectiong
Note  
 
 
 
 
 
 
 
Scheme No 17181920
Main connecting diagram    
Main electrical
element
CT- LZZB9-33 123
Earth switch JN22-331111
Electric Display DSN6-331111
     
     
Function Cable Entry (out) Cable Entry (out)Cable Entry (out)Cable Entry (out)
Note  
 
 
 
 
Scheme No 21222324
Main connecting diagram    
Main electrical
element
CT- LZZB9-33 123
Earth Switch JN22-331111
Electric Display DSN6-331111
     
     
     
Function Cable Entry (out)Cable Entry (out)Cable Entry (out)Cable Entry (out)
Note  
 
 
 
 
 
Scheme No 25262728
Main connecting diagram    
Main electrical
element
Circuit Breaker ZN85/SF/FP1111
CT-LDBJ8-33 (Q)1231
CT- LZZB9-331231
Earth switch JN22-331111
Electric Display DSN6-331111
Function Overhead entry (out) Overhead entry (out)Overhead entry (out)Cable entry (out)
Note  
 
 
 
Scheme No 29303132
Main connecting diagram    
Main electrical
element
Circuit Breaker ZN85/SF/FP11  
CT-LDBJ8-33(Q)2312
CT- LZZB9-332312
Earth switch JN22-331111
Electric Display DSN6-331111
Function Cable Entry (out)Cable Entry (out)Overhead Entry (out)Overhead Entry (out)
Note  
 
 
 
 
 
 
 
 
 
 
Scheme No 33343536
Main connecting diagram    
1Main electrical
element
CT-LDBJ8-33 (Q)3123
CT- LZZB9-333123
Earth switch JN22-331111
Electric Display DSN6-331111
     
Function Overhead Entry (out)Cable Entry (out)Cable Entry (out)Cable Entry (out)
Note  
 
 
 
 
Scheme No 37383940
Main connecting diagram    
1Main electrical
element
Voltage Transformer JDZX9-333123
Fuse XRNP-333123
Surage arrest HY5WZ-51/1341111
 1111
     
Function Overhead Entry (out)Cable Entry (out)Cable Entry (out)Cable Entry (out)
Note  
 
6kv/12kv/15kv/24kv/38kv, 50Hz/60Hz, Indoor 50Hz/60Hz PCM Protection and Control Vacuum/Sf6 Gas /Switchgear Panel
6kv/12kv/15kv/24kv/38kv, 50Hz/60Hz, Indoor 50Hz/60Hz PCM Protection and Control Vacuum/Sf6 Gas /Switchgear Panel
6kv/12kv/15kv/24kv/38kv, 50Hz/60Hz, Indoor 50Hz/60Hz PCM Protection and Control Vacuum/Sf6 Gas /Switchgear Panel
6kv/12kv/15kv/24kv/38kv, 50Hz/60Hz, Indoor 50Hz/60Hz PCM Protection and Control Vacuum/Sf6 Gas /Switchgear Panel