China Kyn Port-24 AC Metal-Enclosed Switchgear, Find details about China Switch Cabinet, Gis from Kyn Port-24 AC Metal-Enclosed Switchgear
S/N | Item | Unit | Parameter | |||
1 | Rated voltage | kV | 24 | |||
2 | Rated frequency | Hz | 50 | |||
3 | Rated current | A | 630~3150 | |||
4 | Rated insulation level | 1min power-frequency withstand voltage | Phase-to-ground and phase-to-phase | kV | 65 | |
Isolation clearance | kV | 79 | ||||
Lightning Impulse Withstand Voltage | Phase-to-ground and phase-to-phase | kV | 125 | |||
Isolation clearance | kV | 145 | ||||
1min power-frequency withstand voltage of secondary circuit | kV | 2 | ||||
5 | Rated short-circuit breaking current (effective value) | kA | 31.5, 40 | |||
6 | Rated short-circuit making current (peak) | kA | 80, 100 | |||
7 | Rated short-time withstand current | Main circuit | kA | 31.5 | ||
Earthing circuit | kA | 27.3 | ||||
8 | Rated peak withstand current | Main circuit | kA | 80 | ||
Earthing circuit | kA | 69.3 | ||||
9 | Rated short-circuit duration | Main circuit | s | 4 | ||
Earthing circuit | s | 4 | ||||
10 | Number of breaking of rated short-circuit current | Class E2 | ||||
11 | Rated operating sequence | o -0.3s-co-180s-co | ||||
12 | Mechanical life | times | 20000 (M2 level) | |||
13 | Category of loss of service continuity | LSC2B-PM |