Product introduction:Cubicle Fixed Indoor AC Metal-clad Ring Main Unit Switchgear (here in after shorted as "RMU") is a latest
version of high voltage equipment by absorbing and digesting advanced technology in domestic and abroad. It
is researched an designed an designed by our company itself for satisfying requirements of our country' s
power supply circles, specially suitable for municipal power supply net of improvement and reconstruction. After
a model approval test and a long-term running test, this product is certified to meet IEC298 standard Alternative
Current Metal-clad Switchgear and Control-gear form 1kV up to 52kV, including 52kVand meet the regulations
and specifications of reliable anti-error operation measures issued by the former State Mechanical Industry
Ministry and the former State Electricity Industry Ministry. Protection level of the product comes up to IP2X. It
features small volume, light-weight, easy operation, small operative force, safety, easy maintenance, stable and
reliable quality, free of fire disaster or explosion disaster, close to wall installation, small area occupied, etc. And
if required, a three-phases coupling function could be satisfied. Comparing and analyzing relevant foreign
documents, and through some experts evaluation, main technical data of this product comes up to the same
level as those of similar products abroad.
RMU with three phases, 10kV rated voltage, 50Hz rated frequency, is suitable for power transmission and
distribution system in places such as factory or mining enterprise, residential zone, high building, school, park,
etc. It could also be used in ring net or terminal power supply.
Brief introductionHXGT18(HXGN26)-12(L) Box type AC metal-clad Switchgear(RMU for shorts) is designed and developed by our
company, which introduce into foreign advance technique and accord with national power supply requirement.
After the type test and long trial operation check, the product performance index has reached IEC298 AC Metal-
clad switchgear and GB3906 3-35KV AC Metal-clad switchgear, and meet the reliable fault prevention operation
function of the two parts requirements, protection degree reached IP2X. This product features small bulk, light
weight, easy operation, safety operation, easy maintenance, etc. It is a newly type of high voltage switchgear
suitable formunicipal power net improvement and reconstruction.Switchgear Basic Technical Parameters
Service conditiona. Altitude≤1000m
b. Ambient air temperature: Maximum +40ºC Minimum -35ºC
c. Relative humidity: Diary average value shall be not more than 95%; monthly average value shall be not more
than 90%.
d. Ambient air should be with no corrosion, no apparent pollution with combustible gas and etc.
e. Earthquake prevent function: process ground horizontal acceleration0.2g and vertical acceleration0.1g at the
same time, adopt resonance,sine,whip wave test, safety factor should be more than 1.67
Technical parameterTechnical data of RMU
S/N | Description | Unit | Data |
1 | Rated voltage | kV | 12 |
2 | Rated frequency | Hz | 50 |
3 | Rated current of main busbar | A | 630 |
4 | Rated short-time withstand current of main circuit, earth circuit | kA/s | 25/2 |
5 | Rated peak withstand current of main circuit, earth circuit | kA/s | 63 |
6 | Rated short circuit making current of main circuit, earth circuit | kA/s | 63 |
7 | LBS full capacity breaking times | times | 100 |
8 | Fuse breaking current | kA/s | 31.5 40 |
9 | Mechanical endurance | times | 10000 |
10 | 1 min power frequency withstand voltage |
phase to earth | kV | 42 |
phase to phase/ between isolating clearance | kV | 48 |
11 | Lightning impulse withstand voltage (peak) |
phase to earth | kV | 75 |
phase to phase/ between isolating clearance | kV | 85 |
12 | 1 min power frequency withstand voltage of Secondary circuit | kV | 2 |
Performance data of SF6 LBS and SF6 LBS+fuse
S/N | Description | Unit | LBS | LBS+fuse |
1 | Rated voltage | kV | 12 |
2 | Rated frequency | Hz | 630 | 125 |
3 | Rated current of main busbar | A | 50 |
4 | 1 min power frequency withstand voltage |
phase to earth | kV | 42 |
phase to phase/ between isolating clearance | kV | 48 |
5 | Lightning impulse withstand voltage (peak) |
phase to earth | kV | 75 |
phase to phase/ between isolating clearance | kV | 85 |
6 | Rated short time withstand voltage | kA/s | 25/2 | -- |
7 | Rated peak withstand voltage | kA/s | 63 | -- |
8 | Rated short circuit making current | kA/s | 63 | 80 (peak) |
9 | Capacitor bank breaking current | A | 400 |
10 | Rated no load transformer breaking current | A | no load current of 1600kVA transformer |
11 | Main circuit resitance | uΩ | <85 |
12 | Rated short circuit breaking current | kA | -- | 31.5 |
13 | Rated transfer current | A | -- | 1500 |
14 | Mechanical endurance | times | 10000 |
15 | Rated SF6 gas pressure ( 20ºC surface pressure) | Mpa | 0.04 |
16 | Motor operation power voltage | V | AC 48, AC/DC 220 110 |
17 | Closing motor current | A | 0.5 |
18 | Opening current | A | 0.5 |
Our Services1. | Pre sale service |
a. | make technical solution |
b. | send quotation, technical data sheet and drawing |
c. | prepare power transmission plan, testing plan and shipment plan |
2. | In sale service |
a. | supervise the manufacturing schedule totally in accordance with the plan |
b. | send photos to customer during every manufacturing process(hold point) |
c. | inform the customer one week before testing. |
3. | After sale service |
a. | installation and commissioning, training the workers |
b. | quick response within 12 hours any time |
c. | provide 12 months guarantee period normally. |
FAQ1. Q: | What is your delivery time ? |
A: | Depend on the type of transformer. |
2. Q: | What is your payment term? |
A: | 30% advance by T/T , 70% before delivery by T/T or L/C or we can discuss about it. |
3. Q: | What kind of standard you follow? |
A: | IEC, ANSI, CSA, GB, etc |
4. Q: | What kind of supporting documentation you can provide normally |
A: | Quotation, outline drawing, manufacturing plan, quality control plan testing plan, financial report, type test report(KEMA, CESI),reference list, etc |
5. Q: | What is your normal warranty period? |
A: | 12 months after transformer operation. |
6. Q: | Can u do installation and commission in user's site? |
A: | Yes, we can send our installation team to user's country for service. |
7. Q: | Do you have any experience in this kind of transformer? |
A: | Yes, we can provide reference list for check. |
Our advantages:Quality Assurance
--From the very beginning, VILLE ensures quality in every step to achieve the best quality.
Experience Sharing
--With more than 30 years' experience in power industry, VILLE brings you an optimized solution.
Global Service
--Wherever you are, VILLE global network will support and provide you with value.
Quick Response
--In response to your needs without delay, VILLE knows the value of your time.
Thanks for choosing VILLE as your reliable partner and please trust both
of us will create a brilliant future!