China Indoor High Voltage Vacuum Circuit Breaker (VS1) Switch, Find details about China Switch, Circuit Breaker from Indoor High Voltage Vacuum Circuit Breaker (VS1) Switch
S.N | Name | Unit | Data | |||||||
1 | Rated voltage | kV | 12 | |||||||
2 | Rated frequency | Hz | 50 | |||||||
3 | Rated insulation level | Rated power frequency withstand voltage | kV | 42 | ||||||
Rated lighting impulse withstand voltage | kV | 75 | ||||||||
4 | Rated current | A | 630 | 1250 | 1600 | 2000 | 2500 | 3150 | 4000 | |
5 | Rated short circuit breaking current Rated thermal stability current (effective value) | kA | 20 | 20 | ||||||
25 | 25 | 25 | ||||||||
31.5 | 31.5 | 31.5 | 31.5 | |||||||
40 | 40 | 40 | 40 | 40 | 40 | |||||
50 | ||||||||||
6 | Rated short circuit making current Dynamic stability rated current | kA | 50 | 50 | ||||||
63 | 63 | 63 | ||||||||
80 | 80 | 80 | 80 | |||||||
100 | 100 | 100 | 100 | 100 | 100 | |||||
125 | ||||||||||
7 | Breaking operations of rated short circuit breaking current | Cycle | 50,30(above 40kA) | |||||||
8 | Rated short-circuit duration | s | 4 | |||||||
9 | Rated operating sequence | 0-0.3s-CO-180S-CO/0-180s-CO-180s-CO(above 40kA) | ||||||||
10 | Mechanical endurance | Cycle | 30000 | |||||||
11 | Rated breaking current of single capacitor bank | A | 630 | |||||||
12 | Rated breaking current of back to back capacitor bank | A | 400 | |||||||
13 | DC component | 50% |