China Hv Impulse Voltage Generator for Lightning Impulse Full Wave Testing, Find details about China Impulse Generator, High Voltage Tester from Hv Impulse Voltage Generator for Lightning Impulse Full Wave Testing
Impulse Voltage Generator for Lightning Test
General Information:
This impulse test system is used for carrying out standard lightning impulse voltage full wave and operation wave tests on HV apparatus such as power capacitors, clearance, bushings, power transformers and CT/PT at 10kV or below.
Main Parameters for System
Nominal voltage: ±200kV
Impulse capacitance: 0.5µF
Number of stages: 2
Rated stage voltage: ±100kV
Rated energy: 10kJ
Rated stage capacitance: 1µF(each impulse capacitor 1µF at 100kV, total 2pcs)
Impulse voltage waveform: generated when load capacitance is 300-3000pF.T1=1.2µs±30%, T2=50µs±20%, standard lightning impulse voltage full waveform of peak voltage deviation≤3%;
Standard operation waveform 250±20%/2500±60%. These 2 Impulse voltage waveform parameters and error are accorded with national requirements of GB311.1and GB16927.1 standard and IEC standard.
Voltage utilization factor: Standard lightning impulse voltage waveform ≥90% when load capacitance is below 1000pF, standard operation impulse voltage waveform≥80% when load capacitance is below 2000pF. Standard operation impulse voltage waveform ≥70%.
Locking range: level voltage is within the range of 20%-100% rated voltage, positive and negative locking range no less than 25%.
Out-of-control rate of synchronous discharge: <5%
Min. output voltage: ≥±20% of rated voltage.
Instability of discharge voltage: <±1.0%
Continuous time: Above 2/3 of rated voltage, continuous working when charge and discharge once every 120s. Below 2/3 of rated voltage, continuous working when charge and discharge once every 60s.
Above information for reference using, please contact us for further technical details.
Impulse Voltage Generator
More details please contact Sansion Power by email for further information.