| Weight | Approx.22kg | | Working Temperature Range | Charge: 0°C--45°C Discharge: -20°C--60°C | | Storage Temperature | -10°C--50°C | | - BMS BMS Parameters
- main parameters setting
No. | Item | Default parameters | Setting or not | note |
1 | Cell overcharge protection | Alarm voltage | 3600mV | Yes | | Protection voltage | 3700mV | Yes | Protection time delay | 4.0S | Yes | Cell overcharge protection released | Released voltage | 3380mV | Yes | Released Capacity | SOC<96% | Yes | Discharging released | Discharging current > 1A |
2 | Cell over discharge protection | Alarm voltage | 2800mV | Yes | After 30 seconds of over‐discharge protection, if it still cannot be recovered, it will enter the low | Protection voltage | 2500mV | Yes | Protection time delay | 1.0S | Yes | Cell over discharge protection released | Released voltage | 2900mV | Yes | Charging | Connect with charger |
3 | Pack overcharge protection | Alarm voltage | 54V | Yes | | Protection voltage | 55.5V | Yes | Protection time delay | 4.0S | Yes | Pack overcharge protection released | Released voltage | 50.7V | Yes | Released Capacity | SOC<96% | Yes | Discharging released | Discharging current > 1A |
4 | Pack over discharge protection | Alarm voltage | 42V | Yes | After 30 seconds of over‐discharge protection, if it still cannot be recovered, it will enter the low | Protection voltage | 37.5V | Yes | Protection time delay | 1.0S | Yes | Pack over discharge protection released | Released voltage | 43.5V | Yes | Charging | Connect with charger |
5 | Over charge current protection | Alarm current | 55 A | Yes | 10 times consecutive occurrences will lock this state and will no longer be automatically released | Protection current | 60 A | Yes | Protection time delay | 1.0S | Yes | Released over charge current protection | Automatic release | After 1min | | | Charging | Discharging current > 1A | |
6 | Over discharge current protection 1 | Alarm current | 55 A | Yes | 10 times consecutive occurrences will lock this state and will no longer be automatically released | Protection current | 60 A | Yes | Protection time delay | 1.0S | Yes | Released over discharge current protection 1 | Automatic release | After 1min | | | | | | | |
| | Charging release | Discharging current > 1A | |
7 | Over discharge current protection 2 | Protection current | ≥80A | Yes | 10 times consecutive occurrences will lock this state and will no longer be automatically | Protection time delay | 100mS | Yes | Released over discharge current | Automatic release | After 1min | Charging release | Discharging current > 1A | |
8 | short‐circuit protection | Protection current | ≥200A | | Protection time delay | ≤300μS | Protection released | charging | Off load | 9 | MOS High temperature protection | Alarm temperature | 90ºC | Yes | | Protection Temperature | 110ºC | Yes | Released temperature | 85ºC | Yes |
10 |
Cell temperature protection | Low temperature charging | 0ºC | Yes | | Low temperature charging Protection | ‐5ºC | Yes | Low temperature charging Protection released | 0ºC | Yes | High temperature charging alarm | 55ºC | Yes | High temperature charging Protection | 60ºC | Yes | High temperature charging Protection released | 50ºC | Yes | Low temperature discharging alarm | ‐15ºC | Yes | | Low temperature discharging Protection | ‐20ºC | Yes | Low temperature discharging Protection | ‐15ºC | Yes | High temperature discharging alarm | 60ºC | Yes | High temperature discharging Protection | 65ºC | Yes | High temperature discharging Protection | 55ºC | Yes |
11 | Ambient temperature protection | Low temperature alarm | ‐15ºC | Yes | | Low temperature protection | ‐20ºC | Yes | Low temperature protection released | ‐15ºC | Yes | high temperature alarm | 65ºC | Yes | High temperature | 75ºC | Yes | High temperature protection released | 65ºC | Yes | | Current consumption | Working self‐consumption | ≤45mA(with display) | |
12 | | current | ≤40mA(without display) | | Low Energy running mode | ≤100μA | 13 | Balancing | Pack voltage difference | 3500mV | Yes | open | Cell Voltage difference | 30mV | Yes | 14 | Default capacity | Low capacity alarm | SOC<5% | Yes | There is no alarm when charging | 15 | Sleep feature | sleep Voltage | 3150mV | Yes | | Time delay | 5min | Yes | | 3.2.LED LED instruction
Table 1 LED Working status indicator Status | Normal/Alarm /Protection | ON/ OFF | RUN | ALM | LED status | Note | | | | | | | | | | Shutdown | Sleep | Off | Off | Off | Off | Off | Off | Off | Off | Off | All off | Standby | Normal | Normally on | flicker 1 | Off | The battery capacity status | | Alarm | Normally on | Flicker1 | Flicker3 | Low voltage |
Charging | Normal | Normally on | Normally on | Off | The battery capacity status ( max capacity LED flicker 2) | Over charge status, the ALM light will not flicker | Alarm | Normally on | Normally on | Flicker3 | Over charge protection | Normally on | Normally on | Off | on | on | on | on | on | on | If no charging, the LED status will be standby | Temperature,over current , failure protection | Normally on | Off | Normally on | Off | Off | Off | Off | Off | Off | Stop charging |
Discharging | Normal | Normally on | Flicker3 | Off | The battery capacity status | | Alarm | Normally on | Flicker3 | Flicker3 | Low voltage protection | Normally on | Off | Off | Off | Off | Off | Off | Off | Off | Stop discharging | Temperature,over current , failure protection | Normally on | Off | Normally on | Off | Off | Off | Off | Off | Off | Stop discharging | Failure | | Off | Off | Normally on | Off | Off | Off | Off | Off | Off | Stop charging or discharging |
Table 2 battery capacity status specification status | | charging | discharging |
Capacity LED light | L6 | L5 | L4 | L3 | L2 | L1 | L6 | L5 | L4 | L3 | L2 | L1 |
capacity(%) | 0~16.6% | Off | Off | Off | Off | Off | F2 | Off | Off | Off | Off | Off | ON 1 | 16.6~33.2% | Off | Off | Off | Off | F2 | On 1 | Off | Off | Off | Off | On 1 | On 1 | 33.2~49.8% | Off | Off | Off | F2 | On 1 | On 1 | Off | Off | Off | On 1 | On 1 | On 1 | 49.8~66.4% | Off | Off | F2 | On 1 | On 1 | On 1 | Off | Off | On 1 | On 1 | On 1 | On 1 | 66.4~83.0% | Off | F2 | On 1 | On 1 | On 1 | On 1 | Off | On 1 | On 1 | On 1 | On 1 | On 1 | 83.0~100% | F2 | On 1 | On 1 | On 1 | On 1 | On 1 | On 1 | On 1 | On 1 | On 1 | On 1 | On 1 | Running LED | Normally on | F3 | Note: F2: flicker 2 ; On 1: normally on ; F3: flicker 3 | Table 3 LED flicker statusFlicker model | on | off | Flicker 1 | 0.25S | 3.75S | Flicker 2 | 0.5S | 0.5S | Flicker 3 | 0.5S | 1.5S |
- Description of buzzer action
Fault: Every second, Buzzer works 0.25S; Protection: Every 2 seconds, Buzzer works 0.25S;(except over voltage protection) Alarm: Every 3 seconds, Buzzer works 0.25S;(except over voltage protection) The buzzer function can be enabled or disabled by the host computer, and the factory default is disabled.- Buttons Description
When the BMS is in the sleep state, press the button (3~6S) and release, the protection board is activated, and the LED indicator lights up in sequence from "RUN" for 0.5 seconds. When the BMS is activated, press the button (3~6S) and release it, the protection board is dormant, and the LED indicator lights up in order from the lowest battery light for 0.5 seconds. When the BMS is in the activated state, press the button (6~10S) and release it, the protection board is reset, and the LED lights are all lit simultaneously for 1.5 seconds. After the BMS is reset, the parameters and functions set by the host computer are retained. If you need to restore the initial parameters, you can use the "restore default value" of the host computer to achieve, but the related operating records and stored data remain unchanged (such as power, cycle number, Record protection, etc.)- Sleep and wake up status
- Sleep status
When any of the following conditions are met, the system enters a low‐power mode:- The single or overall over‐discharge protection has not been released within 60 seconds.
- Press the button (3~6S) and release it.
- The lowest monomer voltage is lower than the sleep voltage, and the duration reaches the sleep delay time (at the same
time, no communication, no protection, no balance, no current).- Standby time exceeds 24 hours (no communication, no charge and discharge, no commercial power).
- Forced shutdown by the host computer software. Before entering sleep, make sure that the input terminal is not connected to an external voltage, otherwise it will not be able to enter the low power consumption mode.
- Wake up status
When the system is in low‐power mode and meets any of the following conditions, the system will exit low‐power mode and enter normal operation mode:- Connect the charger, and the charger output voltage must be greater than 48V.
- Press the button (3~6S) and release it.
- RS232 communication is activated (this method cannot wake up the motherboard due to over‐discharge).
Remarks: After single or total over‐discharge protection enters low power consumption mode, it wakes up regularly every 4 hours and turns on charge and discharge MOS. If it can be charged, it will exit the sleep state and enter normal charging; if it can not be charged after 10 consecutive automatic wakeups, it will no longer automatically wake up. When the system is defined as the end of charging, the recovery voltage has not been reached after 2 days of standby (standby time setting value), and the charging is forced to resume until the end of recharging. - Appearance
,,,,,,. It shall be free from any defects such as scratch, distortion, contamination and leakage. - Performance
- Standard Test Condition
,,: :20±5ºC,: 65±20%,,15A ,, 5 , The battery shall be evaluated within 1 month from the arrival date. Unless otherwise stated in these specifications, the following test shall be carried out in an ambient temperature of 20±5ºC, relative humidity of 65±20% Discharge capacity when the battery is discharged at 15A to 37.5V after being standard charged. Five cycles are permitted for this test. The test shall be terminated at the end of the first cycle which meets the requirement. - Testing Instrument or Apparatus
- Dimension Measuring Instrument
0.01mm. The dimension measurement shall be implemented by instruments with equal or more precision scale of 0.01mm specified. - Voltmeter and Ammeter
10K/V, 0.01. Voltmeters and ammeters shall be equal or more precision instruments of 10K/V and 0.01. - Impedance Meter
(1kHz LCR) Impedance shall be measured by a sinusoidal alternating current method (1kHz LCR meter) - Electrical Performance
Item | Condition | Specification | Open-Circuit Voltage | ,24 The open-circuit voltage shall be measured within 24hours after standard charge | ≥49.5V |
Battery Capacity | , 1 , 15A , The discharge time at 15A shall be measured after standard charge at 20±5ºC and rest 30mins |
≥100% |
Cycle Life | 20±5ºC, 25A ,≤0.02C; 1 , 25A ; 1 , 4000 ,The discharge time on standard discharge shall be measured after 4000 cycles of standard charge and discharge at 20±5ºC,at 0.5C charge and discharge. |
≥80% | Charge(capacity) retention | 20±5ºC,, 28 , 15A , The discharge time at 15A shall be measured after standard charge and then storage at 20±5 ºC for 28days |
≥80% | 1 Temperature Characteristic1 | , 55±2ºC 5h, 15A , After standard charging at 20±5ºC, laying the battery at 55ºC for 2hour, then discharge at 15A to 37.5V, record the discharge time |
≥80% | 2 Temperature Characteristic2 | ,-10±2ºC 16-24h, 15A , After standard charging at 20±5ºC, laying the battery at -10 ºC for 4hour, then discharge at 15A to 37.5V, record the discharge time |
≥60% | - Mechanical Performance
Item | Condition | Specification |
Crush Test | ,32mm , 17.2Mpa, 13KN, A battery is to be crushed between two flat surfaces. The force for the crushing is to be applied by a hydraulic ram with a 32mm diameter piston. The crushing is to be continued until a pressure reading of 17.2mmPa is reached on the hydraulic ram, applied force of 13kN. Once the maximum pressure has been obtained it is to be released. |
, No fire, No explosion |
Drop Test | 1m ,() 1 The battery has only two axes of symmetry in which case only two directions shall be tested. The battery is to be dropped from a height of 1 meter twice onto concrete ground. | ,, No explosion, No fire, No smoke |
Vibration | , X,Y,Z 30 , 1.6mm A full-charged battery is to be subjected to simple harmonic motion with an amplitude of 1.6mm total maximum excursion. The frequency is to be varied at the rate of 1 hertz per minute between 10 and 55 hertz. The cell shall be vibrated for 30 minutes per axis o XYZ axes. |
,, No leakage, No Fire, No explosion | - Cell Safety Performance
Item | Condition | Specification |
Over charge | 20±5ºC, 1C 4V,4V 0A,, 10ºC,. At 20±5ºC, charging battery with constant current 1C to voltage 4V, then with constant voltage 4V till current decline to 0. |
, No explosion, No fire |
Over discharge | .20±5ºC, , 30mΩ 24 . At 20±5ºC, according to the requirement of the standard of discharge after discharge to termination voltage, 30 m Ω external load discharge within 24 hours. |
,, No explosion, No fire |
Short-circuit | 20±5ºC,, 50mΩ, 6 . At 20±5ºC, Standard charge, across the electrodes of the battery with a less than 50 m Ω wire connection, 6 hours | , 150ºC No explosion, No fire The temperature of the surface of the cell are lower than 150ºC |
Heating | , 5±2ºC, 130ºC, 30 Battery is heated in a circulating air oven at a rate of 5±2ºC per mins to 130ºC, an then placed 30 mins at 130ºC |
, No explosion, no fire | - Delivery Conditon
, 20-50%,,,:48.75-50.1V Approx. 20-50% charged Shipment voltage: 48.75-50.1V - Pack Drawing
Remarks:- Dimension: L482(L1 442)x W410xH100mm
- :UES0601LBNBA ,25 mm2 ,,6.0 ,
Charge and discharge port: UES0601LBNBA socket, 25 square copper bar, no key position, 6.0 bus bar socket, orange positive and black negative :UES063 / UES0631LCNAA ,25 ,=180mm() Mating plug-in cord: UES063 plug cord/UES0631LCNAA plug at both ends, 25 mm2 orange cable, cord length=180mm (including plug) - Rocker switch KCD1-101 2 pin 6A250V
- . Iron box color: Black
| GRE Model | ****** | | File No. | ****** | | Signature | Date | Revision | A0 | Drawed by | Zhong | 2020-05-25 | Unit | mm | Checked by | Allen Cao | 2020-05-25 | - Warnings
,,,: To prevent the possibility of the battery from leaking, heating, fire, Please READ this specification carefully before usage and observe the following precautions: . ,, . ,,.
,,.
,, ,. .
When recharging, use the LiFePO4 battery charger specifically for that purpose Do not strike battery with any sharp edge parts, such as Ni-tabs, pins and needles Do not immerse the battery in water and seawater Do not use and leave the battery near a heat source as fire or heater Do not reverse the position and negative terminals Do not connect the battery to an electrical outlet Do not discard the battery in fire or heat it The battery tabs are not so stubborn especially for aluminum tab. Do not bend tab. Do not short-circuit the battery by directly connecting the positive and negative terminal with metal object. Do not transport and store the battery together with metal objects such as necklaces, hairpins etc. Do not directly solder the battery and pierce the battery with a nail or other sharp object.- Battery operation instruction
-
Charging :: : ,..Charging current:Do not surpass the biggest charging current which in this specification.Charging voltage:Do not surpass the highest voltage which in this specification. Charge temperature:The charge temperature is in according to this specification. - Discharging
, . Discharge current: Do not surpass the biggest discharge current which in this specification. Discharge voltage: Do not be less than the lowest voltage which is in this specification. Discharge temperature: The discharge temperature is in according to this specification, - Over-discharges
,,, .. After the short time excessively discharges charges immediately cannot affect the use, but the long time excessively discharges can cause the battery the performance, battery function losing. The battery long-term has not used, has the possibility to be able to be at because of its automatic flashover characteristic certain excessively discharges the condition, for prevented excessively discharges the occurrence, the battery should maintain the certain electric quantity.- Storing the Batteries
,,. The battery should store in the product specification book stipulation temperature range. If has surpasses above for 3 months the long time storage, suggested you should carry on additional charge to the battery.- 8 .
Please do not continuously charge the battery over 8hours. ,,,. , The customer is requested to contact us in advance, if and when the customer needs other applications or operating conditions than those described in this document. Additional experimentation may be required to verify performance and safety under such conditions. We will take no responsibility for any accident when the battery is used under other conditions than those described in this Document. We will inform, in a written form, the customer of improvement(s) regarding proper use and handing of the battery, if it is deemed necessary. | | |