China 400A Hall Effect Current Sensor Current Transformer Module C3t Current Transducer, Find details about China Current Sensor, Open Loop Hall Current Sensor from 400A Hall Effect Current Sensor Current Transformer Module C3t Current Transducer
C3T series dismountable hall effect current Sensor is an open loop device based on the measuring principle of the hall effect, with a galvanic isolation between primary and secondary circuit. It provides accurate electronic measurement of DC currents.
Type | C3T- 400A | C3T- 600A | C3T- 800A | C3T- 1000A | C3T- 2000A |
Unit |
Rated current(Ipn DC) | 400 | 600 | 800 | 1000 | 2000 | A |
Measure range(Ip DC) | 0-800 | 0-1200 | 0-1600 | 0-2000 | 0-3000 | A |
Rated output | @Ip=±Ipn ±2±1% | V | ||||
Zero voltage | @Ip=0 5±0.5% | V | ||||
Supply voltage | +12 | V | ||||
Power Consumption | ≤15 | mA | ||||
Zero offset voltage | @Ip=0 ±20 | mV | ||||
Magnetic offset | @Ip=±Ipn-0 ±15 | mV | ||||
Offset drift | @ -40~+85ºC ≤±0.5 | mV/ºC | ||||
Output drift | @ -40~+85ºC ≤±0.5 | mV/ºC | ||||
Linearity | @Ip=0-±Ipn ≤1 | %FS | ||||
Response time | @50A/μS, 10%-90% ≤7 | μs | ||||
Galvanic isolation | @ 50HZ,AC,1min 2.5 | KV |
Applications
Variable speed drives
Welding machine
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Electrochemical
Mechanical dimension (for reference only)
Remarks:
1. All dimensions are in mm.
2. General tolerance ±1mm
3. Elucidation: 1:+12V 2: 0V 3:V0UT 4:0V
Directions for use
1. When the current will be measured goes through a Sensor, the voltage will be measured at the output end.(Note: The false wiring may result in the damage of the Sensor)
2. The output amplitude of the Sensor can be adjusted according to users' requirements.
3. Custom design in the different rated input current and the output voltage are Sensor.
Standards
·UL94-V0.
·EN60947-1:2004
·IEC60950-1:2001
·EN50178:1998
·SJ 20790-2000
General date
| Value | Unit |
Operating temperature (TA) | -40 to +85 |
|
Storage temperature (TS) | -40 to +125 |
|
Mass(approx) (M) | 300 | g |