China Clamp on (D-K3NT) DC Current Sensor Hall Effect Current Transducer, Find details about China Current Sensor, Open Loop Hall Current Sensor from Clamp on (D-K3NT) DC Current Sensor Hall Effect Current Transducer
D-K3NT series hall effect current Sensor is an open loop device based on the measuring principle of the hall effect, with a galvanic isolation between primary and secondary circuit. It provides accurate electronic measurement of DC currents.
Electrical data (Ta=25ºC±5ºC) |
Type | D-K3NT- 30A | D-K3NT- 50A | D-K3NT- 100A | D-K3NT- 150A | D-K3NT- 200A | Unit |
Rated current(Ipn DC) | 30 | 50 | 100 | 150 | 200 | A |
Measure range(Ip DC) | 0-45 | 0-75 | 0-150 | 0-225 | 0-300 | A |
Rated output | @Ip=±Ipn DC 4 | V | ||||
Supply voltage | +12V,+15V,+24V | V | ||||
Power Consumption | <25 | mA | ||||
Offset voltage | @Ip=0 ±20 | mV | ||||
Magnetic offset | @Ip=±Ipn-0 ±20 | mV | ||||
Offset drift | @ -40~+85ºC ≤±1 | mV/ºC | ||||
Output drift | @ -40~+85ºC ≤±1 | mV/ºC | ||||
Linearity | @Ip=0-±Ipn ≤1 | %FS | ||||
Response time | @50A/μS, 10%-90% ≤7 | μs | ||||
Galvanic isolation | @ 50HZ,AC,1min 2.5 | KV |
Applications |
Directions for use |
Standards |
General date |
Value | Unit | |
Operating temperature(TA) | -40 to +85 | ºC |
Storage temperature(TS) | -40 to +125 | ºC |
Mass(approx) (M) | 26 | g |