China Red Silicone Rubber Overhead Line Cover for Cable Insulation, Find details about China Red Silicone Rubber Overhead Line Cover, Overhead Conductor Animal Guard Cover from Red Silicone Rubber Overhead Line Cover for Cable Insulation
Serial No. | Properties | Unit | Standard Data | Test Results | Test Methods |
1 | Electrical Strength Test | KV/mm | 20 | 22 | GB/T 1408.1-2006 |
2 | Volume Resistivity | Ω.cm | 1×10 14 | 2×10 14 | GB/T 1410-2006 |
3 | Dielectric Constant | 2-3 | 2.3 | GB/T 1409-2006 | |
4 | Shore Hardness | 70±5 | 7.1 | GB/T 531 | |
5 5.1 5.2 | Mechanical Properties Before ageing Tensile Strength Elongation at break After Heat ageing(180degrees C, 7d) Tensile Strength Change Elongation Change | MPa % | 200 ±30 ±30 | 5.5 243 13 -22 | GB/T 528 |
6 | Low Temperature Elongation(-15degree C , 2h) | % | 20 | 190 | GB/T 2951.4-1997 |
7 | Low Temperature Flexibility(-50degree C , 4h) | - | No cracks | No cracks | UL224-2004 |
8 | High Temperature Crack Resistance(155degree C, 2h) | - | No cracks | No cracks | GB/T2951.6-1997 |
LJ Stranded Wire Cross-sectional Area(Nominal) | O.D. Of LJ Stranded Wire(mm) | Silicone Rubber Sleeving Covers Models |
16 mm²ID | ||
ID10 | ||
35 mm² | 7.50 | ID10 |
50 mm² | 9.00 | ID12 |
70 mm² | 10.80 | ID12 |
95 mm² | 12.48 | ID17 |
120 mm² | 14.25 | ID17 |
150 mm² | 15.75 | ID20 |
185 mm² | 17.50 | ID20 |
210 mm² | 18.75 | ID24.2 |
240 mm² | 20.00 | ID24.2 |
300 mm² | 22.40 | ID24.2 |
400 mm² | 25.90 | ID30 |
500 mm² | 29.12 | ID32 |
630 mm² | 32.67 | ID35 |
800 mm² | 36.90 | ID39.8 |
Voltage(kV) | ≤10kV | ≤35kV | ≤110kV | ≤220kV |
Thickness(mm) | 2.3mm | 2.3-3.0mm | 4.0-6.0mm | 6.0-8.0mm |