China Multi-Function Sf6 Gas Recovery and Purifying Device, Sf6 Filling Plant, Find details about China Multi-Function Sf6 Gas Recovery, Insulation Oil Treatment from Multi-Function Sf6 Gas Recovery and Purifying Device, Sf6 Filling Plant
Multi-function SF6 Gas Recovery and Purifying Device,SF6 Filling Plant's Features:
1.The design principle of the cryogenic liquefaction method is adopted, which reduces the working pressure of the system and greatly improves the working efficiency of recycling.
2.It equips with a self-regenerating drying filter, the moisture content is less than 40PPM (volume ratio) after one recovery.
3.It can liquefy SF6 gas into steel cylinders.
4.The flowchart is drawn on the operation panel, the operation is simple and clear.
5.The electrical system is provided with a phase sequence protection device. The phase sequence of the three-phase power supply can be adjusted directly by manual switching. The electrical system also has a phase loss protection function, which can effectively avoid the reverse operation of the vacuum pump and the phase loss operation of all the mainframes.
6.It's mobile type and air-cooled way, and can be used without water source.
7.Small dimensions: 1970 (L) × 1100 (W) × 1630 (H) mm.
8.Weight <1000Kg, low noise <75dB (A).
Model | SFP100 | |
Working temperature | -10ºC~40ºC | |
Recycling | Initial pressure(MPa) | 0.8 |
Final pressure(MPa) | ≤0.053 | |
Time required for 1m³ volume(h/m3)* | ≤0.4 | |
Filling | Initial pressure(Pa) | ≤133 |
Final pressure(MPa) | 0.7 | |
Time required for 1m³ volume (h/m3 ) | ≤0.2 | |
It takes time to evacuate from 0.1MPa to 133Pa (h/m3 ) | ≤0.25 | |
Ultimate Vacuum Degree(Pa) | ≤10 | |
Vacuum degree keeps rising from133Pa over 24 hrs(Pa) | ≤400 | |
Leakage rate | ≤0.5% | |
SF6 gas purity after recovery | Water content(PPM/V) | ≤40 |
Oil content(PPM/W) | ≤10 | |
Storage container | Storage method | Liquid |
Pressure(MPa) | 3.9 | |
Volume (L) | 300 | |
Storage capacity (kg) | 300 | |
Liquefaction method | Frozen liquefaction | |
Vaporization method | Electric heating | |
Dry filter regeneration method | Vacuum heating and regenerating | |
Power | 3Φ 380V | |
Total power(kW) | ≤12 | |
Noise dB(A) | ≤75 | |
Diemension(mm) | 1970×1100×1630 | |
Weight(kg) | ≤1000 |