China Gfuve Energy Meter Calibration Test Setelectric Meter Testing System, Find details about China Energy Meter Field Calibration, Meter Field Calibrator from Gfuve Energy Meter Calibration Test Setelectric Meter Testing System
Test Voltage | |
Range | 30-560V |
Error | ± 0.05% |
Harmonic | 2 nd -- 51 st |
Test Current | |
Range (direct connection) | 0.01-10A |
Range (clamp CT) | 100A 5A, 500A, 1000A, 2000A (option) |
Error (direct connection) | ± 0.05% |
Error (clamp CT) | ± 0.2% (5A, 100A ) ± 0.5% (other) |
Harmonic | 2 nd -- 51 st |
Power measure error | |
Active power (direct connection) | ± 0.05% |
Active power (clamp CT) | ± 0.2% (5A, 100A) ± 0.5% (other) |
Reactive power (direct connection) | ± 0.1% |
Reactive power (clamp CT) | ± 0.2% (5A, 100A) ± 0.5% (other) |
Energy measure error | |
Active energy (direct connection) | ± 0.05% |
Active energy (clamp CT) | ± 0.2% (5A, 100A) ± 0.5% (other) |
Reactive energy (direct connection) | ± 0.1% |
Reactive energy (clamp CT) | ± 0.2% (5A, 100A) ± 0.5% (other) |
Phase angle | |
Range | 0º - 360º |
Error | ± 0.05º |
Frequency | |
Range | 45Hz - 65Hz |
Pulse output | |
Energy constant | 1~25000imp/kWh |
Pulse ratio | 1: 1 |
Output level | 5V |
Pulse input | |
Input channel | 2 |
Input level | 5 -- 10V |
Input frequency | Max. 100Hz |
Display | |
Resolution | 7" TFT color (480× 234) |
Function | |
Vector diagram | Yes |
Waveform | Yes |
Energy accumulation | Yes |
CT ratio test | Yes |
Local parameter input | Yes |
Wiring emulation | Yes |
Self-calibration | Yes |
Recorder check | Yes |
Data storage | Yes |
Data storage qty | 5000 |
External extend memory | Yes |
Screen printing | Yes |
Communication port | USB/RS232 |
Communication with PC | Yes |
Upload data | Yes |
External mini printer | Yes |
External keyboard | Yes |
Other | |
Voltage Supply way | External power test lead power |
Voltage Supply | 45-450V, 50/60Hz |
Ambient temperature | -25-- +45degrees |
Relative humidity | 30% -- 95% |
Dimensions (W × H × D) (mm) | 245× 168× 70 |
Weight (kg) | 1.8kg |