China New Generation Gas Insulated Metal-Enclosed Switch Cabinet, Find details about China Switchgear, Gis from New Generation Gas Insulated Metal-Enclosed Switch Cabinet
S/N | Item | Unit | Data | |||||
1 | Rated voltage | kV | 40.5 | |||||
2 | Rated insulation level | Short-time power frequency withstand voltage | Phase-to-phase, phase-to-ground | 95 | ||||
Vacuum gap, isolating gap | 118 | |||||||
Lightning impulse withstand voltage (crest) | Phase-to-phase, phase-to-ground | 185 | ||||||
Vacuum gap, isolating gap | 215 | |||||||
Short-duration power-frequency withstand voltage of auxiliary and control circuit | 2 | |||||||
3 | Rated frequency | Hz | 50 | |||||
4 | Rated current of master busbar | A | …2500 | |||||
5 | Rated current of branch busbar | …2500 | ||||||
6 | Rated short-circuit breaking current | kA | …31.5 | |||||
7 | Rated short-circuit making current (crest) | …80 | ||||||
8 | Rated short-time withstand current | Main circuit | …31.5 | |||||
Earthing circuit | …27.4 | |||||||
9 | Rated peak withstand current | Main circuit | …80 | |||||
Earthing circuit | …68.5 | |||||||
10 | Rated short-circuit duration | Main circuit | s | 4 | ||||
Earthing circuit | 2 | |||||||
11 | Insulating gas | N21) | SF62) | |||||
12 | Water content of gas chamber | ppm | ≤250 | |||||
13 | Annual leakage rate | ≤0.1% |