China 27V 20A, 9V 8A, 12V 2A Multi Output Power Supply, Find details about China Power Supply, 650W from 27V 20A, 9V 8A, 12V 2A Multi Output Power Supply
Item | Unit | Min | Typical | Max | Testing Conditions |
Input voltage range | Vac | 145 | 220 | 295 | |
Vac | 155 | 285 | |||
Input power factor | 0.9 |
Output voltage | Output voltage range | Output current range | Regulator precession | Load regulation | Voltage regulation | Ripple |
+27V | 26.8V~27.5V | 1A~20A | ≤±3% | ≤±2% | ≤±1% | ≤50mV |
+9V | 8.9V~9.25V | 0A~8A | ≤±3% | ≤±2% | ≤±1% | ≤50mV |
MODEM(+12V) | 11.85V~12.3V | 0A~2A | ≤±3% | ≤±2% | ≤±1% | ≤30mV |
charge24.6V | 24V~24.6V | 0A~0.3A | ≤±3% | ≤±2% | ≤±1% | ≤30mV |
Item | Unit | Min | Typical | Max | Testing Conditions |
Output Power | W | - | 640 | ||
Output Efficiency | % | 80 | - | Rated input/output | |
Temperature coefficient | /ºC | ±0.02% |
Item | Unit | Min | Typical | Max | Recovery characteristics |
Input over-voltage protection | V | 295 | 330 | ||
Recovery point for Input over-voltage protection | V | 285 | 315 | ||
Input under-voltage protection | V | 120 | 145 | ||
Recovery point for Input under-voltage protection | V | 135 | 155 | ||
Battery under-voltage protection | V | 17 | 18 | ||
+27V output over-voltage protection | V | 30 | - | 32.5 | Auto recovery |
+9V output over-voltage protection | V | 11 | 14 | Auto recovery | |
MODEM output over-voltage protection | V | 14 | 17 | Auto recovery | |
+27V output limited current protection | A | 22 | 25 | Auto recovery | |
+9V output limited current protection | A | 8.5 | 13 | Auto recovery | |
MODEM output limited current protection | A | 3 | 5.5 | Auto recovery | |
Over-heating protection | ºC | 95 | 105 | Auto recovery | |
Short-circuit protection | A | Auto recovery after long time |
Item | Level | Standards(or testing conditions) |
Insulation voltage (output to ground) | 500Vdc | 500Vdc/1Min / Leakage Current≤10mA |
Insulation voltage ( input to ground) | 1500Vac | 1500Vac/1Min / Leakage Current≤10mA |
Insulation voltage ( input to output) | 1500Vac | 1500Vac/1Min / Leakage Current≤10mA |
Insulation resistance | 10MΩ | Under normal atmospheric pressure, and when the relative humidity is 90%, and the testing voltage is DC 500v, for the power supply, the insulation resistance of input to output, input to ground, and output to ground is no less than 2MΩ. |
grounding resistance | 0.1Ω | It will be less than 0.1Ω for a single power supply. |
Tangent current | 1.75mA | It will be less than 1.75mA for a single power supply. |
Item | Index requirements | Standards |
CE | CLASS A | EN55022 |
RE | CLASS A | EN55022 |
CS | LEVEL 2:3V/m | IEC61000-4-6 |
RS | LEVEL 2:3V/m | IEC61000-4-3 |
ESD | LEVEL 3 | EN61000-4-2(CLASS B) |
ESD | There is no influence on the operation of power supply when charge on the case after power supply is encased Tangent discharge:±6KV Air discharge:±8KV | EN61000-4-2(CLASS B) |
EFT/B | LEVEL 3:2KV | IEC61000-4-4 |
SURGE | LEVEL 3:line-line2KV Line-ground4KV | EN61000-4-5 |
DIP | Drop to70%,40%,0% Holding time 10ms,100ms,500ms etc. | IEC61000-4-11 |
Item | Index requirements | Performance |
Noise | The noise of power supply should be less than 55dB(A), the condition is in the range of input voltage and output voltage and current, the distance is 1 meter from front , back, right and left, and 1.5 meter from upper and underside. | Pass |
MTBF | 100,000H | |
Vibration | >Frequency : 5 to 10 Hz >Amplitude : 3.5mm,9~200Hz >Direction : 3 directions >Sweep time : 50minutes(50minute per one way) > acceleration:10m/s2, > there is no influence on power supply. | Pass |
Shock | Half-sine wave,acceleration: 20G,Amplitude 11ms,Direction : 3 directions(X,Y,Z) 3 times per one direction | Pass |
Dustproof | Has some function of dustproof | Pass |
Odor | No peculiar smell and deleterious gas | Pass |