China Easy UPS 3s 10 kVA 15kVA 20kVA 30kVA 40kVA 400 V 3: 3 UPS, Find details about China APC UPS, UPS Power from Easy UPS 3s 10 kVA 15kVA 20kVA 30kVA 40kVA 400 V 3: 3 UPS
Rated Power (kVA/kW) | 10/10 | 15/15 | 20/20* | 30/30* | 40/40* | |
Normal AC supply input | ||||||
Input Voltage (V) | 380/400/415 V (Three-phase + Neutral) | |||||
Frequency (Hz) | 45 - 65 Hz | |||||
Input Power Factor | Up to 0.99 | |||||
THDI | <3.5% at full load | |||||
Input Voltage Range | 304 V to 477 V at full load | |||||
Dual Mains Input | Yes (default: single main input) | |||||
Output | ||||||
Nominal Output Voltage (V) | 3:1 (coming soon) - 220/230/240 V | |||||
3:3 - 380/400/415 V | ||||||
Efficiency: Double Conversion Mode | Up to 96% | |||||
Efficiency: EcoMode | 0.99 | |||||
Overload Capacity in Utility Operation | 125% for 10 minutes, 150% for 60 seconds | |||||
Output Voltage Tolerance | +/-1.5% static | |||||
Communication and management | ||||||
Communication Interface | RS232, RS485, USB, Dry contact, Modbus TCP/IP, optional SNMP card | |||||
Control Panel | Multi-function LCD, status and display console | |||||
Weights and dimensions | ||||||
Low frame, unpackaged/shipping dimensions (H × W × D, mm) | 530 × 250 × 700 mm/772 × 400 × 857 mm | 530 × 250 × 700 mm/772 × 400 × 857 mm | 770 × 250 × 800 mm/1015 × 400 × 982 mm | 770 × 250 × 800 mm/1015 × 400 × 982 mm | 770 × 250 × 900 mm/1015 × 400 × 1050 mm | |
High frame (coming soon), unpackaged/ shipping dimensions (H × W × D, mm) | 1400 × 380 × 928 mm/1640 × 563 × 1014 mm | 1400 × 380 × 928 mm/1640 × 563 × 1014 mm | 1400 × 380 × 928 mm/1640 × 563 × 1014 mm | 1400 × 500 × 969 mm/1640 × 683 × 1114 mm | 1400 × 500 × 969 mm/1640 × 683 × 1114 mm | |
Low frame, unpackaged/shipping weight (KG) | 36/50 | 36/50 | 58/75 | 60/77 | 70/86 | |
High frame (coming soon), unpackaged/ shipping weight (KG) | 130/155 | 130/155 | 150/175 | 185/220 | 195/230 | |
Battery Catridge (coming soon) (1 string/4 modules), unpackaged/shipping weight | 27 KG per module/28 KG per module | |||||
Regulatory | ||||||
Safety | IEC/EN62040-1-1 | Performance | IEC 62040-3 | |||
EMC/EMI/RFI | IEC 62040-2 | Environmental | IEC 62040-4 |