China Googol 800kw 1000kVA High Voltage Diesel Generator with Marathon Alternator, Find details about China High Voltage Generator, 50hz High Voltage Generator from Googol 800kw 1000kVA High Voltage Diesel Generator with Marathon Alternator
Engine Model | PTAA1780G9-HV | |
Speed | rpm | 1500 |
Frequency | Hz | 50 |
Rating Output | ||
Engine Standby Output ( LTP) | kW | 967 |
Engine Prime Output (PRP) | kW | 883 |
Engine Continuous Power (COP) | kW | 671 |
Fan Quantity | 1 | |
Fan Reduction | kW | 36 |
Single Fan Reduction | kW | 36 |
All Fans Reduction | kW | 36 |
Engine Net Standby Output ( LTP) | kW | 931 |
Engine Net Prime Output (PRP) | kW | 847 |
Engine Net Continuous Output (COP) | kW | 635 |
BMEP for Standby Output | bar | 26.48 |
BMEP for Prime Output | bar | 24.16 |
BMEP for Continuous Output | bar | 18.37 |
Typical Generation Standby Output | kVA | 1100 |
Typical Generation Standby Output | kW | 880 |
Typical Generation Prime Output | kVA | 1000 |
Typical Generation Prime Output | kW | 800 |
Typical Generation Continuous Output | kVA | 750 |
Typical Generation Continuous Output | kW | 600 |
Typical Alternator Efficiency | ≥ | 94.5% |
Voltage of Genset | 11000 | |
MECC alte Generator's Model | * | |
MARATHON Generator's Model | MXH800-4 | |
Coupler Model | ZL7-01 | |
Power Factor | 0.8 | |
Speed droop (static) elect. Gov. | 0-5% | |
Governing standards to ISO 8528 Parts 1 and 5 | G3 | |
Max. step load acceptance, 1st step ( % Prime Output ) | 60% | |
Basic Performance Datasheet | ||
Aspiration Type | Turbocharger, air-air aftercooler | |
Injection Type | Direct Injection | |
Configuration | Vee | |
No. of Cylinders | 16 | |
Displacement | l | 29.2 |
Bore | mm | 128 |
Stroke | mm | 142 |
Compression Ratio | 14.6:1 | |
Piston Speed | m/s | 7.1 |
Rotation Direction (from flywheel) | Counter Clockwise | |
Number of Flywheel Teeth | 204 | |
Flywheel House Size | SAE0-18 | |
Lubrication System | ||
Lube Oil Specification | API-CF4 | |
Oil Capacity | l | 72 |
Max. Permissible Oil Temperature | °C | 110 |
Oil Pressure Warning | kPa | 200 |
Oil Pressure Shutdown | kPa | 160 |
Cooling System | ||
Coolant Capacity for Engine | l | 26 |
Max. Permissible Temperature | °C | 90 |
Max. Coolant Warning Temperature | °C | 95 |
Max. Coolant Shutdown Temperature | °C | 105 |
Thermostat Open Temperature | °C | 71 |
Radiator Cooling Flow | m³/min | 1512 |
Flow of Coolant pump | m³/h | 51.96 |
Flow of Aftercooler pump | m³/h | * |
Heat dissipation (engine radiator) | kW | 462 |
Heat dissipation (CAC) | kW | 244 |
Heat dissipation (convection) | kW | 70 |
Mode of Radiator(cooper core , 40 C environment's temp ) | 6300300 | |
Fuel System | ||
Governor Type | Electrical | |
Engine Output at genset prime output | kW | 883 |
Fuel Consumption at 25% of genset prime output | l/h | 57.83 |
Fuel Consumption at 50% of genset prime output | l/h | 104.25 |
Fuel Consumption at 75% of genset prime output | l/h | 153.59 |
Fuel Consumption at 100% ofgenset prime output | l/h | 205.47 |
Lowest Fuel Consumption Ratio | g/kW.hr | 198.40 |
Intake & Exhaust System ( On Standby Output ) | ||
Combustion Air Consumption | m³/min | 72.54 |
Max. Intake Restriction | KPa | 5 |
Exhaust Temperature (Before Turbo) | °C | 688 |
Exhaust Temperature (After Turbo) | °C | 493 |
Max. Exhaust Back Pressure | Kpa | 5 |
Exhaust Gas Flow | m³/min | 88.66 |
Exhaust Flange Diameter | mm | 2*150 |
Electrical System | ||
Charging Alternator Voltage | V | 28 |
Charging Alternator Capacity | A | 35 |
Starting Voltage | V | 24 |
Starting Motor Capacity | kW | 9 |
Minimum Battery Capacity | Ah | 2*200 |
Quantity of generator set's Bearing (( For 400-660VAC generator ) | 1 | |
Quantity of generator set's Bearing (( For Above 3300VAC generator ) | 2 | |
Engine Dimension | ||
Length | mm | 1950 |
Width | mm | 1389 |
Height | mm | 1162 |
Engine Dry Weight w/o Cooling System | kg | 2350 |