CT PT Ratio Testing Result Jack Manufacturers in UK USA

China CT PT Ratio Testing Result Jack Manufacturers in UK USA, Find details about China CT Test Jack, CT Ratio Test from CT PT Ratio Testing Result Jack Manufacturers in UK USA

Model NO.
GF106
Customized
Customized
Accuracy
0.05%, 0.1%
Excitation Output Voltage
0-220vrms
Excitation Output Current
0-5arms (20A Peak-Value)
CT Ratio Error Measurement
1-30000
Key Words
CT PT Tester
Automatic Frequency Variation Range
0.1-60Hz
Key Word
CT Test Result
Equivalent Excitation Voltage
≤5000V
Model
CT Ratio Test
PT Ratio Error Measurement
1-10000
Trademark
GFUVE
Transport Package
Standard Export Box
Specification
10kg
Origin
Beijing, China
Model NO.
GF106
Customized
Customized
Accuracy
0.05%, 0.1%
Excitation Output Voltage
0-220vrms
Excitation Output Current
0-5arms (20A Peak-Value)
CT Ratio Error Measurement
1-30000
Key Words
CT PT Tester
Automatic Frequency Variation Range
0.1-60Hz
Key Word
CT Test Result
Equivalent Excitation Voltage
≤5000V
Model
CT Ratio Test
PT Ratio Error Measurement
1-10000
Trademark
GFUVE
Transport Package
Standard Export Box
Specification
10kg
Origin
Beijing, China
product description
GF106 CT/PT tester is mainly used for field testing, it can finish the measurements (M) and protection (P) class CT, PT and TYP class CT. Adopt LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data, with simple and convenient operation.
Functions
1. Steady and transient state characteristic tests of various types of CT/PT.
2. The use of advanced power technology, the test knee point reaches up to 10kV.
3. No external other auxiliary equipment, stand-alone to complete all test items.
4. CT test, easy to test, all the tests are using the same wire connection except the load test.
5. It carries with it thermal printer, so it can print test results on site.
6. Parameters such as knee point current and voltage.
7. Parameters such as 10% error curve, 5% error curve.
8. The device can store 3000 groups of test data which would not be lost if the device loses its power.
9. The data can be displayed and analyzed after the test, or transferred to PC through USB disk and produce a Word
file report.
10. Portability: weight <12Kg.
Reference Standard
IEC 60044, ANSI/ IEEE C57.13, IEC61869, GB 1207-2006, GB 1208-2006
FUNCTION
I. Current Transformer (CT)II. Voltage Transformer (PT)
1.  Magnetization curve1.  Excitation characteristic test
2.  Transformation ratio test2.  Transformation ratio test
3.  Polarity3.  Polarity
4.  5% and 10% error curve4.  Ratio error, phases
5.  Current Injecting5.  Degauss
6.  Degauss6.  Calculation of knee point value
7.  Ratio error, phases7.  Actual secondary load (burden), test (burden)
8.  Automatic calculation of excitation knee point value8.  Resistance test
9.  Actual secondary load test (burden) (load test)
10.  Resistance test
11.  Secondary winding time constant (Ts)
12.  Remanence coefficient (Kr)
13.  Transient dimensioning factor (Ktd)
14.  Peak instantaneous error (Er)
15.  Magnetizing inductance (LU)

Parameters
Electrical parameters 
Accuracy0.05%, 0.1%
Power supplyAC 220V±10% or AC 110V±10%, 50/60Hz
Excitation output voltage0-220Vrms
Excitation output current0-5Arms (20A peak-value)
Automatic frequency variation range0.1-60Hz
Equivalent excitation voltage≤5000V
Accuracy≤0.5% (0.2%RD+0.3%RG)
Secondary winding DC resistance measurementRange0.1-300Ω
Accuracy≤0.5% (0.2%RD+0.3%RG)
Secondary actual load measurementRange5VA-1000VA
Accuracy≤0.5% (0.2%RD+0.3%RG)±0.1VA
CT/PT phase error measurementAccuracy±4min
Resolution0.01min
CT ratio error measurementRange1-30000
Accuracy≤0.5%
PT ratio error measurementRange1-10000
Accuracy≤0.5%
Standards
Reference standardsGB1207-2006, GB1208-2006, GB16847-1997 
IEC60044-1, IEC60044-6, IEC61869-2-2012
Safety standardsGB 4793.1-2007
EMCEMC standard 89/336/EEC
FCC Subpart B of Part 15 Class A
IEC 1000-4-2/3/4/6
Mechanical parameters
Overall dimension (L x W x H) (mm)410 x 250 x 300 
Weight (kg)  ≤10 
Environmental conditions
Relative humidity   90RH%
Operating temperature-10°C to +40°C
Altitude≤2000m
Ordering information
Be sure to the type, current ratio, accuracy class, rated load and use of the products when you plan to make an order.  Special specifications could be customized. All kinds of different specifications and parameters current transformers can be made according to your needs.
company introduction
Beijing GFUVE Electronics Co., Ltd. was established in 2005. It combined science, industry and trade together as one high-tech enterprise. GFUVE mainly produces high voltage ammeter recorder, IEC61850 test suite software, meter test equipment, reference standard meter, phantom load power source, electrical measurement instrument, relay test set, transformer test, handheld terminal and POS terminal, and power analyzer, intelligent digital meter, transducer and current transformer models etc. GFUVE is a leader manufacturer of energy meter test products and high voltage ammeter recorder in China. It is professional in energy meter test system, energy meter portable tester and related accessory. The product of high voltage ammeter recorder develops very quickly in the market. Our company has achieved certification to ISO9001. The products are sold to over 30 provinces in China and exported to overseas including South America, Middle East, South east and Africa. We have been contributing ourselves to developing the durable and stable products for the usage of the power system. Contact us now for further business relationship. We are here to provide you the best service.