China Potable Pd Detector for Transformer Partial Discharge Test Equipment, Find details about China Partial Discharge Tester, Partial Discharge Detector Instrument from Potable Pd Detector for Transformer Partial Discharge Test Equipment
Prodcut Features
The product conforms to the following applicable regulations:
Product Technical Parameter1.Applicable scope: the non-intrusive mode is adopted to detect and locate the partial discharge defects of the high-voltage electric equipment.
2.Detection principle: UHF (Ultra High Frequency) method, UA (Ultrasonic Analysis) method and TEV (Transient Earth Voltage) method.
3.Detection frequency band: the UHF detection frequency band is 300~2000(MHz) and the ultrasonic detection frequency band is 20~200(KHz).
4.Measurement range: the UHF measurement range is -80~10dBm and the ultrasonic measurement range is -90~80dB.
5.Sensitivity: the minimum sensitivity is 10pC (specifically determined by the distance between the sensor and the discharge source).
6.Sensor:
a)UHF sensor: 300~2000(MHz), with directional reception characteristic;
b)Ultrasonic sensor: 20~200(kHz);
c)EV (Transient Earth Voltage) sensor: 5 ~ 100MHz.
7.Embedded ultrasonic sensor and TEV & UA integrated sensor: such components as transformer dedicated sensor, GIS dedicated sensor and cable dedicated sensor can be selected;
8.Software function:
a)Continuously detect UHF, TEV and ultrasonic signals to judge whether there is any partial discharge;
b)Display the variation tendency of the detected signal in a real-time manner to intuitionally judge the development of the partial discharge signal;
c)Field data storage function;
9.Instrument characteristics:
a)Screen display: high-contrast 3.5"TFT color screen.
b)Data storage: 4000 groups of test data can be stored.
c)Working power supply: embedded 8.4V lithium battery for 8h's continuous operation.
d)Power supply: input 100-240VAC, output 8.4V/3A, charging time 3~4h.
e)Boundary dimension: 220 * 100 * 40.
f)Instrument weight: 1.5kg.
g)Environment temperature: -25ºC~45ºC.
h)Storage temperature: -35ºC~60ºC.
10.Complete configuration: host machine, sensor, AC adapter, connecting cable and transport case.