Xmt -9000 Cj Temperature Controller PT100

China Xmt-9000 Cj Temperature Controller PT100, Find details about China Temperature Controller, Temperature Meter from Xmt-9000 Cj Temperature Controller PT100

Model NO.
XMT-9000
Control Type
Digital
Control Method
Electronic Type
Usage
Temperature Control
Trademark
CJ
Transport Package
1PCS/Box
Specification
ISO 9001: 2008 Others
Origin
China
HS Code
9032900090
Model NO.
XMT-9000
Control Type
Digital
Control Method
Electronic Type
Usage
Temperature Control
Trademark
CJ
Transport Package
1PCS/Box
Specification
ISO 9001: 2008 Others
Origin
China
HS Code
9032900090
1. Input: Thermocouple: K\E\J\S; Thermal resistance: PT100 CU50
2. Range: K(0~400\0~1300)\E(0~400\0~800)\J(0~1000) S(0~1600)\PT100(-100.0~200.0\0~600)\CU50(-50.0~150.0)
3. Measure error: ± 0.5%F. S± Byte
4. Silicon control trigger signal(over zero): Range≥ 3V, Width≥ 40us
5. The output contact potential of the relay: Impedance load 7A
6. Input power: AC85~242V 50/60Hz
7. Entironment: Temperature: 0 to 50, Humidity: ≤ 85%RH
8. External dimension: 160× 80× 130 hole 152× 76

Size: XMT:80×160×110mm  hole: 76×152;  XMTA:96×96×110mm  hole: 92×92;
    XMTE:48×96×110mm   hole: 44×92;  XMTF:96×48×110mm   hole: 92×45;
    XMTD:72×72×110mm   hole: 68×68;  XMTG:48×48×110mm   hole: 45×45;

Setup flow chart
CodeDescriptionSetting rangeInstructionRemarks
SPSetting control pointWhole rangeºC or 1 defined unit 
AL1Alarm 1Whole rangeºC or 1 defined unit 
AL2Alarm 2Whole rangeºC or 1 defined unit 
SCMeasurement update-20.0 to 20.0Measuring value can be modified through
increasing or decreasing this data.
Note: It may be cause inaccurate racy of measuring value when you use this function . Please use the function carefully according to your situation.
0
PProportional band0 to 9999When the P↑,the proportion and differential function↑; if the P↓,the proportion and differential function↓. When P=0,the meter is ON/OFF control100
IIntegration time0 to 3000sIt's mainly used to adjust the static difference. To increase it, the static difference will be reduced, but when it is too high, the static difference will drift instability.500
dDifferential time0 to 2000sWhen the I↓,the calculus function↑;
I↑the calculus function↓.
When I=0, no calculus function, it is PD adjustment instrument
100
tControl period1 to 120sWhen the d↓,the proportion and calculus function↑; if d↑,the proportion and calculus function↓,but the differential function↑.
When d≤t, it has no differential function
20
HyDeadband0.1to 50.0ON/OFF control only1.0
AtAuto-man0 to 1
Close auto-man function
Open auto-man function

0
LockKey lock0 to 1
All the parameter can rework
Only SP value can rework
>1 All the parameter can not rework
0