Filter efficiency ranges from E10 to U17. |
H13≥99.99% @0.3μm |
H10≥95% @0.5μm |
F8≥80% @1.0μm |
Adopt computer-controlled automatic production line for manufacture of mini pleat filter materia; |
Using special fiberglass paper or PP paper as the filter media, good stability of filtration efficiency. |
USe aluminum foil or PVC as serapratorm SUS316Lor plastic as filter frame; |
With double sides face guard to ptotect media, with good strength; |
Each filter is tested according to EN1822:2009. |
common size:
Model | Dimensions | Media Area | Rated Air FLow | Initial Pressure Drop (Pa) |
|
(m2) | (m3/h) |
W×H×D | Standard | High Capacity | Standard | High Capacity | F8 | E10 | H13 |
(mm) |
HHS 610/03 | 305×305×150 | 2.4 | 3.6 | 250 | 375 | ≤85 | ≤175 | ≤235 |
HHS 610/05 | 305×610×150 | 5 | 7.5 | 500 | 750 |
HHS 610/10 | 610×610×150 | 10.2 | 15.3 | 1000 | 1500 |
HHS 610/15 | 915×610×150 | 15.4 | 23.1 | 1500 | 2250 |
HHS 610/20 | 1220×610×150 | 20.6 | 30.9 | 2000 | 3000 |
HHS 610/05X | 305×610×292 | 10.1 | 15.1 | 1000 | 1500 |
HHS 610/10X | 610×610×292 | 20.9 | 31.3 | 2000 | 3000 |
Note: 1. In case of specifications, structural changes, HEFIL will provide up-to-date data on website:
hefilter.en.made-in-china.com. 2. HEFIL makes various other models of
HMV filter not listed the above table. Please consult with us if you need.
Suitable for air conditioning and air cleaning equipments of high performance ventilation, usually apply in medium and terminal filtration in air air-conditioning systems.