Suin Three Phases SA2200 Portable Power Quality Analyzer Class a

China Suin Three Phases SA2200 Portable Power Quality Analyzer Class a, Find details about China Power Meter, Power Analyzer from Suin Three Phases SA2200 Portable Power Quality Analyzer Class a

Model NO.
SA2200
Storage
32GB
PC Software Analysis
Yes
GPS/Beidou
Option
WiFi APP
Option
Interface
USB Host, LAN, WiFi
Trademark
Suin
Transport Package
Carton
Specification
370*240*280 mm
Origin
China
HS Code
90303900
Model NO.
SA2200
Storage
32GB
PC Software Analysis
Yes
GPS/Beidou
Option
WiFi APP
Option
Interface
USB Host, LAN, WiFi
Trademark
Suin
Transport Package
Carton
Specification
370*240*280 mm
Origin
China
HS Code
90303900

Overview

The critical importance of electrical power in today's society necessitates daily maintenance and management to ensure that problem's don't occur. When they do, for example due to an equipment failure or abrupt surge in demand, engineers face the need to analyze the cause quickly.

The Suin SA2100 and SA2200 help troubleshoot power quality problems in three- and single-phase power distribution systems. Especially the SA2200 can conduct tests according to the international IEC 61000-4-30 Class A standard.


Design Features

Class A compliance under international standards

Basic voltage measurement accuracy of±0.1%

Special waveform record function

200kS/s sample rate

Support multi language

32GB micro SD card

GPS time synchronization

Advance function interface

1. Track harmonics up to 100th

Suin Three Phases SA2200 Portable Power Quality Analyzer Class a

2. Phase Diagram

Suin Three Phases SA2200 Portable Power Quality Analyzer Class a3. Powerful logger function

Suin Three Phases SA2200 Portable Power Quality Analyzer Class a4. Data analyze in PC software

Suin Three Phases SA2200 Portable Power Quality Analyzer Class a
Product Shows 

Suin Three Phases SA2200 Portable Power Quality Analyzer Class a
Suin Three Phases SA2200 Portable Power Quality Analyzer Class a
Suin Three Phases SA2200 Portable Power Quality Analyzer Class a

Application

Suin Three Phases SA2200 Portable Power Quality Analyzer Class a
Suin Three Phases SA2200 Portable Power Quality Analyzer Class a
Suin Three Phases SA2200 Portable Power Quality Analyzer Class a

Package Shows

Suin Three Phases SA2200 Portable Power Quality Analyzer Class aSpecification              
                                         
                                                                            Standard compliance:IEC61000-4-30 Class A

Channel(Voltage/Current)4/4
Voltage Range1-1000Vrms, 6000V transient voltage
Current Rangedepends on supplied current clamp
PC software analysisYes
Micro SD card(bulid-in)32GB
BatteryLithium ion, 5200mAh/>8h
Time SynchronizationGPS/Beidou(option)
interfaceUSB Host, LAN, WIFI
WIFI App(option)
Screen5.6' TFT LCD with resolution640*480(SA2200)
Language14-Chinese, English, French, German, Italian, Japanese, Korean, Polish, Portuguese(Brazil/Portugal), Russian, Spanish (Latin/Spain), Turkish
Dimension/Weight        270*190*66mm/2.0kg
Wire Combinatios           1Ø+NEUTRAL,1Ø SPLIT PHASE,1Ø IT NO NEUTRAL,3Ø WYE,
 3Ø DELTA, 3Ø IT, 3Ø HIGH LEG, 3Ø OPEN LEG, 
2-ELEMENT, 2 1/2-ELEMENT
Electrical SafetyIEC61010-1 ,Safety Degree: 600V CAT IV    1000V CAT III
Measurement
Voltage/Current/FrequencyMeasurement RangeResolutionAccuracy
Vrms(AC+DC)1 ~ 120Vrms0.001Vrms±0.1% of nominal voltage
120Vrms~400Vrms0.01Vrms
400Vrms~1000Vrms0.1Vrms
Vpk1 ~ 1400Vpk0.01Vpk±0.5% of nominal voltage
V(Crest Factor)1.0 ~ >2.80.01±5%
Arms(AC)       10mV/A0~150A0.01A±0.1%±0.1A
       1mV/A1~2000A0.01A±0.1%±0.1A
       65mV/1000A 10~6000A0.01A±0.1%±0.2A
A(Crest Factor)1 ~ 100.01±5%
Frequency42.5~57.5(50Hz nominal)0.01Hz±0.01Hz
51~69(60Hz nominal)0.01Hz±0.01Hz
320~480(400Hz nominal)0.01Hz±0.01Hz
Dips & Swells
Vrms1/20 ~ 200% of nominal voltage 0.01Vrms±0.2%
Arms1/2depends on current clamps0.01A±1% 
Harmonic (IEC61000-4-7)
Harmonic Number1 ~ 100(50/60Hz) (IEC61000-4-7)   1~12(400Hz)
Harmonic Voltage %f0.0 ~ 100.0%0.01%±0.1% ± nx0.1%
Harmonic Current %f0.0 ~ 100.0%0.01%±0.1% ± nx0.1%
THD0.0 ~ 100.0%0.01%±2.5%
Phase-180° ~180°0.1°± nx0.1°
Power and Energy
P, S, Q1Max. 6000MW0.1kW±1%±10 digits
PF & cosФ0 ~ 10.01±0.01
kWh, kVAh, kvarhdepends on nominal voltage and current clamps±1%±10 digits
Flicker (IEC61000-4-15)
Pst(10min)/Plt (2 hrs)0.00 ~ 20.000.01±5%
Unbalance
Voltage0.0 ~ 20.0%0.10%±0.1%
Current0.0 ~ 20.0%0.10%±1%
Voltage Phase-360° ~ 0°0.1°±0.1°
Current Phase-360° ~ 0°0.1°±0.5°
Voltage Transient
Vpk±6000Vpk0.01V±15%
Vrms10 ~ 1000Vrms0.01V±2.5%
Min. Test Time5us
Inrush Current
Armsdepends on current clamps0.01A±1% ± 5digits
Inrush Duration1 ~ 32min selectable10ms±20ms
Mains Signaling
Signaling Frequency60-3000Hz0.1Hz 
Relative V%0%-100%0.10%±0.4%
Absolute V3s (3s average)0.0-1000V0.1V±5% of Nominal voltage
Logger
Recordinguser-defined parameters for 4 phases at the same time
MemoryData stored in Micro SD card, 32GB
Duration Time2 hrs to 1 year, depends on the recording items and time interval
Interval1s to 60 minutes
Monitor
Support EN50160 in default or user-defined standard

About SUIN

Shijiazhuang SUIN Instruments Co., Ltd is a high-tech company and concentrates on R&D, production, test, sales and service of test & measurement instruments, electrical products, application software, etc.
Suin Three Phases SA2200 Portable Power Quality Analyzer Class a