Super High Efficiency (SHE) Rectifiers Flatpack2 48V She Rectifiers for Telecom Applications (PART NO. 241115.106 &241119.106)

China Super High Efficiency (SHE) Rectifiers Flatpack2 48V She Rectifiers for Telecom Applications (PART NO. 241115.106 &241119.106), Find details about China Flatpack2 48V She, Rectifier Module from Super High Efficiency (SHE) Rectifiers Flatpack2 48V She Rectifiers for Telecom Applications (PART NO. 241115.106 &241119.106)

Model NO.
FLATPACK2 48V SHE
Weight
1.950 Kg [4.3lbs]
Dimensions
109X41.5X327mm
Trademark
Eltek
Transport Package
Plywood Case
Specification
Brand New
Origin
Wuhan
HS Code
8504409190
Model NO.
FLATPACK2 48V SHE
Weight
1.950 Kg [4.3lbs]
Dimensions
109X41.5X327mm
Trademark
Eltek
Transport Package
Plywood Case
Specification
Brand New
Origin
Wuhan
HS Code
8504409190

Short Description:

 

The Flatpack2 48V Super HE rectifiers are contributing to setting the new industry standard for efficiency in the DC power market.

With an efficiency of 97.8% the Super HE is a premium rectifier particularly suitable for markets and applications where the energy is costly. In grid connected applications the payback time is down to 2 years compared to standard HE rectifiers, and in hybrid applications even faster.

The Flatpack2 Super HE is fully compatible with Flatpack2 and Flatpack2 HE systems and can replace any Flatpack2 48V rectifier module.

 

Applications

Telecom - Wireless
•radio Base Station / Cell Sites
•lte / 4g / Wimax
•mobile Switching Center (mcs)
•microwave
•broadband

Telecom - Fixed
•central Office
•telephony Servers / Switches
•fiber Optics
•microwave
•broadband
•broadcast
•data Center

Key Features
•super High Efficiency - 97.8%
•high Power Density - 33 W/in3
•compatible With Existing Systems
•global Compliance
•patented Technology
•hot Pluggable

Specification

Model48/2000 SHE48/3000 SHE
Part number241115.106241119.106
INPUT DATA
Voltage (nominal range)185 - 264 VAC206 - 264 VAC
Voltage (operating range)85 - 264 VAC
Frequency45 - 66 Hz
Maximum current11.6 ARMS16 ARMS
ProtectionFuse in Live, varistor for transient protection, shutdown when VIN is out of range
OUTPUT DATA
Voltage (default)53.5 VDC
Voltage (adjustable range)43.21) - 57.6 VDC
Max power, nominal input2000 W3000 W
Max power, de-rated @VIN = 85 VAC850 W1000 W
Max current, @VOUT = 48 VDC41.7 A62.5 A
Current sharing±5.0% of max current
Static voltage regulation (10-100% load)±0.5%
Dynamic voltage regulation±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms
Hold up time (3000W load)>10ms; output voltage > 42 VDC
Ripple<150 mVPP , 30 MHz bandwidth
ProtectionOvervoltage shutdown, short circuit proof, high temperature, hot plug-in inrush current limiting, fuse
OTHER SPECIFICATIONS
Peak Efficiency97.8 %
Isolation3.0 kVAC - input to output
1.5 kVAC - input to protective earth
0.5 kVDC - output to protective earth
Alarms (Red LED)Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low voltage alarm, CAN bus failure
Warnings (Yellow LED)Rectifier in power derate mode, Remote current limit activated, Input voltage out of range, flashing at overvoltage
Normal (Green LED)Input and output ok
MTBF (Telcordia SR-332 Iss.3 method II Case L1)1 900 000 hours
Operating temperature (5 - 95% RH non-cond.)-40 - 75°C [-40 - 167°F ]
Max output power de-rates above temp / to45°C [+113°F] / 1350 W45°C [+113°F] / 1800 W 2)
Storage temperature-40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing
Dimensions[WxHxD] / Weight109 x 41.0 x 327mm [4.25 x 1.61 x 13"] / 2.050 kg [4.5lbs]
DESIGN STANDARDS
Electrical safetyEN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013, UL 60950-1:2014
EMCEN 61000-6-1:2019, -6-2:2019, - 6-3:2007 + A1:2011, - 6-4:2019
ETSI EN 300 386 V.2.1.1, FCC CFR 47 Part 15:2013
EnvironmentETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3) EU 2015/863 (RoHS) & 2012/19/EU (WEEE)
Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other operating conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised
Stand-by / test operation (VOUT < 48VDC) limited for VIN > 230 VAC
When input mains voltage is below 210 VRMS temperature derating will start at 40 °C and 1500 W will be available at 75 °C