380VAC 10K- 80kVA Pure Sine Wave Power Supply Hf Online UPS

China 380VAC 10K-80kVA Pure Sine Wave Power Supply Hf Online UPS, Find details about China Pure Sine Wave UPS, High Frequency Online UPS from 380VAC 10K-80kVA Pure Sine Wave Power Supply Hf Online UPS

Model NO.
Queen Star Plus 33Q10K-80K
Standby UPS
Sine Wave Output UPS
Output Capacity
Large Type
Equipment Mode
Decentralized
Brand
Upsen
Communication Interface
RS232
Output Socket
Terminal
Warranty
1year
Color
Black
Trademark
UPSEN
Transport Package
Cartons & Wooden Pallet
Specification
CE & ISO Certificate
Origin
China
HS Code
8504402000
Model NO.
Queen Star Plus 33Q10K-80K
Standby UPS
Sine Wave Output UPS
Output Capacity
Large Type
Equipment Mode
Decentralized
Brand
Upsen
Communication Interface
RS232
Output Socket
Terminal
Warranty
1year
Color
Black
Trademark
UPSEN
Transport Package
Cartons & Wooden Pallet
Specification
CE & ISO Certificate
Origin
China
HS Code
8504402000
380vac 10K-80Kva pure sine wave power supply HF online ups
High Frequency Online UPS Queen Star Plus Strar Series 33Q10K-80K(3Ph in/3Ph out)
 
Key Features       

1:True double-conversion on line UPS
2:Programmable power management outlets
3:DSP technology guarantees high performance  
4:Low initial investment and flexible for future expansion
5:Standard backup UPS and long backup UPS in one integrated unit
6:Input L and N lines reverse wiring detection, Auto start when AC back
7:Large blue ground LCD digital display shows Detailed Real-Time UPS Status and parameters
8:Nominal voltage, nominal frequency and bypass voltage range can de adjusted via LCD panel
9:Advanced MCU microprocessor control technology and DSP technology, ensure long life reliability

Applications:
CNC machines,Textile machinery,Air conditioning package units and plants,Large deep freezers,Medical equipments,Server,Critical network devices, Telecom  etc.
 
Technical Specification:
Index33Q 10KL33Q 20KL33Q 30KL33Q 40KL 33Q 60KL 33Q 80KLComments
Input
Input voltage
Rated voltage380VAC/220VAC380VAC 
Phasethree phase with ground 
Turn on 
voltage range
(120±5~274±5)VAC(207±9~475±9)
VAC
 
Bypass 
voltage range
(60±5~300±5)VAC(105±9~518±9)
VAC
Could be 
adjusted 
by software.
Bypass 
low loss
60VAC~220VAC(default 60VAC)105VAC~380VAC
(default 105VAC)
 
Bypass
 low comeback
Low loss +5VACLow loss 
+17VAC
 
Bypass 
high loss
220VAC~300VAC(default 300VAC)380VAC~475VAC
(default 475VAC)
 
Bypass 
high comeback
High loss -5VACHigh loss -17VAC 
Line low loss
comeback
(120±5) VAC /(140±5) VAC(207±9) VAC 
(242±9) VAC
load≤50%
(140±5) VAC /(160±5) VAC(242±9) VAC
(276±9) VAC
50%≤90%
(160±5) VAC /(175±5) VAC(276±9) VAC
(302±9) VAC
load>90%
Line high loss
comeback
(275±5)VAC/(260±5)VAC(475±9)VAC
(449±9)VAC
 
Input frequency
Rated 
frequency
50Hz 
Frequency 
low loss
(40~49) ±0.2Hz(default:46Hz)Could be 
adjusted
 by software.
Frequency 
low comeback
Frequency low loss +0.5Hz
Frequency 
high loss
(51~60)±0.2Hz(default:54Hz)
Frequency 
high comeback
Frequency high loss -0.5Hz
Input power factor
Could be 
adjusted 
by software.
> 0.9933Q 10-40KL:
220VAC,full R load
33Q 60-80KL: 
380VAC,full R load
Generator Support generator inputGenerator rating
≥2*UPS rating
Input current
Rated current 14A28A42A67A80A105A 
Input THDI<= 10% 
Output protection
Rating 
protection
32A 
Breaker
50A 
Breaker
60A 
Breaker
80A 
Breaker
100A 
Breaker
125A 
Breaker
 
Output power
VA/watt10KVA/8KW20KVA/16KW30KVA/24KW40KVA/32KW60KVA/
48KW
80KVA/
64KW
 
Rated voltage220VAC380VACSine wave
Voltage range200/208/220
/230/240VAC
345/359/380
/397/415 VAC
33Q 10-40KL: 
Could be 
adjusted 
by software. 
10% derating 
for 
208VAC
/200VAC.
33Q 60-80KL: 
Could be 
adjusted 
by software. 
10% derating 
for 345VAC
/359VAC.
Voltage regulation±1% 
Voltage distortion≤5%≤10%Full RCD load
≤3%Full R load
DC offset≤200mV 
Transient response≤9%R load 
0%~100%~0%
 ≤6%R load 20%
~100%~20%
Transient recovery≤60ms voltage recovery to 90%Full RCD load
Bypass output 
before turn-on
YES 
Crest ration3:1 
Output frequency range
Normal mode1,Same as input frequency(46Hz~54Hz)
2,50Hz(Input frequency>54Hz or Input frequency<46Hz)
 
Battery mode(50±0.1) Hz 
Slew rate1 Hz/Sec 
Efficiency
Normal  mode> 93%> 90% 
Battery mode> 90%> 90% 
Overload
Normal mode
battery mode 
Overload warning only105%±5%≤load
1min,then transfer to bypass and alarm.105%±5%<
load≤125%±5%
30S,then transfer to bypass and alarm.125%±5%<
load≤150%±5%
300mS, then transfer to bypass and alarm.load>150%±5%
Automatically
 retransfer
YES 
Short protection
Normal
battery mode
YES 
Transfer time
Normal to 
battery mode
0mS 
Battery to 
normal mode
0mS 
Normal to 
bypass mode
<4mS0mS 
Bypass to 
normal mode
<4mS0mS 
Battery and charger
Battery
Rated voltage192VDC240VDC192VDC*2192VDC*2480VDC 
Type/Rating      
Battery 
quantity
162016*216*240 
Backup time      
Protection
Low alarm voltage 
comeback voltage
(180.8V±4V)/ (188.8V±4V)(226V±4V)/ (236V±4V)(180.8V±4V)
(188.8V±4V)
(226V±4V)/ (236V±4V)(452V±4V)
(472V±4V)
33Q 30KL 
use two 
Shutdown voltage
comeback voltage
160V±4V/
168V±4V
(200V±4V)/ (210V±4V)160V±4V/
168V±4V
(200V±4V)/ (210V±4V)(400V±4V)
(420V±4V)
 
DC protection
Overcharge 
protection
comeback voltage
(249.6V±4V)
(216V±4V)
(312V±4V) (270V±4V)(249.6V±4V)
(216V±4V)
(312V±4V) (270V±4V)(624V±4V) 
(540V±4V)
 
Leakage current< 500uA 
Over 
discharge
 protection
14.5h Could be 
set by software
Battery test
Battery weakYES 
Battery faultYES 
Charger
Output voltage(219.2±3)VDC(277±3)VDC(219.2±3)VDC(277±3)VDC(554±3)VDC 
Charge timeDepends on the external battery capacity 
Charge current7.5A6A5A4A10A 
Interface
Alarm silenceYES 
DC power 
turn-on
YES 
Automatically
 retransfer
YES 
Audio alarm
Battery modeBeep/4s 
Battery low
charger fault
Beep/1s 
UPS faultContinue beep 
OverloadBeep/1s 
Bypass modeBeep/2Min 
L/N inverseBeep/2Min 
Communication
RS232 interfaceYES 
Intelligent slotYES 
Monitor softwareAppending with UPS 
Cooling
Force air cooling 
Display
LCD/LED displays UPS status
Environment
Work 
temperature
0ºC~40ºC 
Altitude<1000m 
Audible
 noise
≤60dB 
Storage 
temperature
-15ºC~45ºC 
Work humidity20%~95% 
Standard
EMS
ESDIEC61000-4-2Level4
RSIEC61000-4-3Level3
EFTIEC61000-4-4Level4
SurgeIEC61000-4-5Level4
EMI
ConductedEN55022Class A
RadiatedEN55022Class A
Safety
SafetyGB4943-2001/IEC62040-1 
Machinery features
Size
Outline dimension and net weight
L*W*H (mm)710*260*717840*515*1135 
Net weight(Kg)45/9350/98  195208 
Optional functions
60Hz  OptionalSet by software
Converter mode  OptionalSet by software
ECOOptionalOptionalAvailable and 
set by software
EPOOptionalOptional 
LCD displayOptional  
 
Competitive Advantages:
1: Three Years' warranty for Online UPS, and 1% free UPS or 2% free PCB Boards
2: Good after-sales service, we will be full responsible for any faults caused by our side
3: Professional experience in power field more than 10 years
4: Professional technical support before and after sales                                              
5: Timely response, fast delivery time and flexible operations to satisfy any customers' special requests.   
6: Free OEM & ODM Service                                       
7: Competitive price, quality and mature products

380VAC 10K-80kVA Pure Sine Wave Power Supply Hf Online UPS