Automatic Power Factor Controller for Power Capacitor 12 Step

China Automatic Power Factor Controller for Power Capacitor 12 Step, Find details about China Power Factor Controller, Power Factor Correction from Automatic Power Factor Controller for Power Capacitor 12 Step

Model NO.
JKL5CF-4
Type
Jkl5c
Automatic Power Factor Controller PCB
Relay Control Signal
Power Supply
Power Transformer 230V~400V
Power Control
Relay
Power Sensor
CT Type
Power Capacity
0~9999
Power Factor Controller Function
Correct Measure Reactive Current
Display
LED/LCD
Over Voltage Setting
230V~500V
Control Step
1~12 Step
Trademark
OEM
Transport Package
12PC/Per CTN 42*42*35cm
Specification
CE ROHS
Origin
Yueqing Zhejiang
HS Code
8537909000
Model NO.
JKL5CF-4
Type
Jkl5c
Automatic Power Factor Controller PCB
Relay Control Signal
Power Supply
Power Transformer 230V~400V
Power Control
Relay
Power Sensor
CT Type
Power Capacity
0~9999
Power Factor Controller Function
Correct Measure Reactive Current
Display
LED/LCD
Over Voltage Setting
230V~500V
Control Step
1~12 Step
Trademark
OEM
Transport Package
12PC/Per CTN 42*42*35cm
Specification
CE ROHS
Origin
Yueqing Zhejiang
HS Code
8537909000
Power Factor Correction 4step JKL5CF
The power factor approve state of user
To improve the utilization efficiency of electric transformer
Reducing line loss
To improve the voltage quality of power supply
Power Factor Correction 4step JKL5CF Specification
Item Name  Low Voltage Pfr Automatic Power Factor Controller Compensate Jkl5CF 
1LED/LCD Display will show  
a.three-phase voltage,current, active power, reactive 
b.power factor and power network frequency, control parameter
2Strong anti-interference ability can resist 2kv impulse test ,keep data 
3You can revise control data sheet ,it will save data no power 
4Auto analysis phase function 
5Current get signal resistor less than 0.05Ω
6Over voltage ,under voltage lack phase protection function 
7Input way: static ,Dynamic ,compound 
8Rated voltageAC 220V±10%  AC 380V±10%
9 Rated currentAC 0-5A
10Rated frequency50Hz±5%
11Sensitivity100mA
12COS φ Preset 0.80-0.99; step length 0.01; Factory preset 0.98 input and cutoff time
13Input Delaydynamic state 100ms-30S; Static state 1-250S;Factory preset dynamic state 5S; 
static state 30S.
14Over-voltage protection230-260V; step length 1V; Return difference 6V  reset 240V,
15Under-voltage protection180V;return difference 6V
16Auto Discriminating PhaseON/OFF; factory preset ON(Auto discriminating ON)
17Reactive thresholdOFF-4-100kvar; factory preset OFF (reactive threshold inefficiency)
18CT variation50/5A-3000/5A; step length 1; factory preset 500/5A
19Capacitance capacity0-99kvar factor preset of each branch 10kvar
20Contact capacitydynamic state output of each branch DC12V×50mA
Static state output of each branch 380V×7A/200V×5A
21size113*113   138*138
 
Power Factor Correction 4step JKL5CF advantage 
1.20 years global leading profession manufacture of energy meter  
2, the precision of measurement
The current identification: the controller can judge the sampling current polarity and automatic conversion.
3, the display of choice
4, parameter setting function
5, protection function
6. control strategy, capacitors
7. output circuit design 
8.Fast delivery : you will get the order when you need it 
9.OEM is warmly welcome 
10.Convenient : 45 minutes to wenzhou airport 
 
Power Factor Correction 4step JKL5CF  function 
Control signal: comprehensive control by using the power factor and reactive current of two physical quantities;
Step :step number selected by the user;
Data storage: after the loss of electricity parameter settings will not be lost, data save permanently;
Adaptability: automatically adapt to the distribution system of different parameters of the controller, does not need to provide the transformation ratio of current transformer and capacitor compensation capacity;
Overvoltage protection: the voltage is higher than the set value quickly over voltage, gradual resection capacitors have been put;
Strong anti-interference: unique design, crash, indiscriminately, indiscriminate cutting phenomenon can not occur in operation;
Switching shocks: can prevent the small current load and over voltage critical values appear repeated switching;
High sensitivity: compensator can work normally in the input signal when the current is 0.10A;
Display error: input signal power of current 0.10A to 5A changes due tonumerical error measurement showed minimal;
The current identification: the controller can judge the sampling current polarity and automatic conversion.
 
Power Factor Correction 4step JKL5CF Payment terms 
1. 30% T/T advance , the balance against to the copy B/Lor LC at sigh 
2. The other specific issues can negorate.
3. Pls confirm the details with us before do the prepayment.
 
Power Factor Correction 4step JKL5CF Packing information 
1. Inside foam package ,outside strong paper package 
2. 12pcs/per CTN 
3. G/N.W: 12/11kg
4. We can packing as your required,good looking design 
 
Why choose Power Factor Correction 4step JKL5CF 
1).ISO9001,SGS,Gold golden supplier 
2) Monthly Production Capacity -- 100000 Pcs 
3)All goods examined before delivery by 10 QC staff 
4)Prompt Reply Within 12 Hours 
5)8000 square meters work environment