GF333V2 Three Phase Power and Energy Reference Standard

China GF333V2 Three Phase Power and Energy Reference Standard, Find details about China Three Phase Power and Energy Reference Standard, Power and Energy Reference Standard from GF333V2 Three Phase Power and Energy Reference Standard

Model NO.
GF333V2
Customized
Customized
Keyword
Three Phase Power and Energy Reference Standard
Model
Power and Energy Reference Standard
GF333V2
Reference Standard Three Phase
Accuracy Class 
0.02%, 0.05%
Power Consumption
30va
Harmonic
2ND-51st
Frequency Range
40-70Hz
Communication Port
RS232, USB
Weight (Kg)
7.5
Trademark
GFUVE
Transport Package
Standard Export Wooden Box
Specification
355*185*145
Origin
Beijing, China
Model NO.
GF333V2
Customized
Customized
Keyword
Three Phase Power and Energy Reference Standard
Model
Power and Energy Reference Standard
GF333V2
Reference Standard Three Phase
Accuracy Class 
0.02%, 0.05%
Power Consumption
30va
Harmonic
2ND-51st
Frequency Range
40-70Hz
Communication Port
RS232, USB
Weight (Kg)
7.5
Trademark
GFUVE
Transport Package
Standard Export Wooden Box
Specification
355*185*145
Origin
Beijing, China
GF333V2 Three phase power and energy reference standard
GF333V2 meter is a reference standard with the characteristics of wide-range, multifunction and high-precision. It has accuracy class of 0.02. By adopting techniques of DSP, embedded system and automatic temperature balancing and other compensation, it has not only advantages of light weight, small size, high precision, high performance, powerful function, original interface, ease-to-use, but also work stability.The product can be widely used in fields of electric energy measuring, electric energy laboratories and other relevant industry, not only in laboratories but also at the industrial field.
Features
High accuracy class up to 0.02%
High stability, high reliability
Measuring 2nd~51st harmonics
Metal structure, strong and reliable
Waveform display function
Vector diagram function
Energy accumulating function
Suit for testing in the lab
As a three phase reference standard
Parameters
Electrical parameters
Accuracy class 0.02%, 0.05%
Power supply220V±10% or 110V±10%, 50/60Hz
Power consumption30VA
Voltage measurement
Range40-560V
Error±0.02% (40V-560V)
±0.05% (5V-40V)
Harmonic2nd-51st
Current measurement
Range (direct connection)10mA-120A
Error (direct connection)±0.02% (100mA-120A)
±0.05% (10mA-100mA)
Harmonic2nd-51st
Power measurement error
Active power±0.02% (0.1A-120A)
±0.05% (0.02A-0.1A)
Reactive power±0.05% (0.1A-120A)
Energy measurement error
Active energy±0.02% (0.1A-120A)
±0.05% (0.02A-0.1A)
Reactive energy±0.05% (0.1A-120A)
Phase angle
Range0°-360°
Resolution0.005°
Error±0.02°
Frequency
Range40-70Hz
Resolution0.001
Error±0.002
Pulse output
Energy constant1-9999999
Pulse ratio1:1
Output level5V
Pulse input
Input channel1
Input level5-24V
Input frequencyMax. 2MHz
Display
Resolution6.4" inch 640x480 pixel TFT
Communication portRS232, USB
Mechanical parameters
Dimensions (W×H×D) (mm)355×185×145
Weight (kg)7.5
Environmental conditions
Ambient temperature10°C to 40°C
Relative humidity20%-85%