China Power Fault Indicator Differential Current Transformer, Find details about China Rogowski Coil, Flexible Current Senor from Power Fault Indicator Differential Current Transformer
MODEL | Y-FCT-200 | Y-FCT-350 | Y-FCT-510 | Y-FCT-800 | |
Coil length | 200mm | 350mm | 510mm | 800mm | |
Window size | 50mm | 100mm | 150mm | 240mm | |
Reference Rated current | 600A | 1000A | 3000A | 6000A | |
Coil Resistance | 140 (+/-10) Ω | 210 (+/-10) Ω | 290 (+/-10) Ω | 430 (+/-10) Ω | |
Weight | 140g | 150g | 160g | 180g | |
Ratio | Calibrated | 85mV/kA@50Hz | 50mV/kA@50Hz | ||
Uncalibrated | 110mV/kA@50Hz | ||||
Read Accuracy | Calibrated <0.5% (central position, 25ºC) Uncalibrated < 5% tolerance (central position, 25ºC) | ||||
Maximum current measurable | 100kA | ||||
Coil Resistance | from 100 to 250 Ω | ||||
Coil Section | 8mm | ||||
Lead length | 2meter | ||||
Temperature | Uncalibrated 200ppm/C | ||||
Calibrated 300ppm/C | |||||
Position Error | ±1% maximum | ||||
Output on 0A (zero drift) | ≤0.05mV | ||||
Phase error | ≤0.5° | ||||
Linearity | ±0.2% of reading | ||||
Bandwidth | 1Hz to 100kHz(-3dB) | ||||
Operating temperature | -30ºC to 80ºC | ||||
Storage temperature | -40ºC to 90ºC | ||||
Other requirements, please contact us to OEM. |
Coil & cable | Thermoplastic rubber flame retardant UL 94 V-0 rated |
Couplings | PA6 UL 94 V-O rated |
Color(coil) | Black, Yellow, Red, Green, Blue |
Shielded | 100% coil, 100% output cable |
Certifications | CE marked |
Complies with LVD EN 61010-1:2010 EMC EN 61326-1:2013 | |
IP68 | |
Voltage insulation | Coil: 3000V |
Signal cable:1000V | |
Safety | 1000V CATIII ,600V CATIV |
Dimensions(mm) | Y-FCT-200 | Y-FCT-350 | Y-FCT-510 | Y-FCT-800 | |||
A.Windows size A | 50 | 105 | 155 | 245 | |||
B.Windows size B | 60 | 100 | 150 | 240 | |||
C.Coil O.D. | 66 | 121 | 171 | 261 | |||
D.Coil section | 8 | ||||||
E.Lead Cable Total Length | 2000 | ||||||
F:Coil length | 200 | 350 | 510 | 800 |