China Control Relay for Time Relay Overvoltage and Undervoltage Adjustment Phase Sequence and Lack of Phase Detection Display by LEDs, Find details about China Time Relay, Control Relay from Control Relay for Time Relay Overvoltage and Undervoltage Adjustment Phase Sequence and Lack of Phase Detection Display by LEDs
1Potentionmeter for asymmetry thresshold adjustment |
2Time delay adjustment |
3Function selection |
4Dispaly by LEDs |
5Potentionmeter for overvoltage adjustment |
6Potentionmeter for undervoltage adjustment |
A motor that continues to turn despite lass of a phase can regenerate a voltage.If this voltage exceeds the sensing threshold,the relay will not detect phase loss. |
In this case,we recommend use of RM4 TA's. |
These device have a fixed hysteresis of 50%. |
"Hysteresis "here means the voltage difference(unbalance the closing and opening of the output relay(as a percentage of the preset unbalance threshold). |
For example,with a 10% unbalance setting on a 400-V network |
The relay opening threshold is:400-10%=360V |
The relay closiong threshold is:360V+(50%x10%) of 360V=380V |
Model Number | LRM4TG20 | Rated Viltage | 220-440V |
Theory | Digital | Rated Current | 8A |
Usage | Multifunctional | Sample | Sample available |
Type | Mini | Rated Frequency | 50/60Hz |