Evapco Cooling Tower Infills

1) Features

EFFICIENT
The patented EVAPAK fi ll was developed in EVAPCO's heat transfer laboratory through thousands of hours of thermal performance testing. EVAPAK's unique cross- fl uted, counterfl ow fi ll pattern is designed to induce highly turbulent mixing of the air and water to provide superior heat transfer.

WORKING PLATFORM
Due to the unique way in which the crossfl uted sheets are bonded together, the structural integrity of the fi ll is greatly enhanced, making the fi ll useable as a working platform and providing a safe working environment to perform preventative maintenance or service.

CUSTOM DESIGN
EVAPCO will custom design and manufacture PVC fi ll for all forced draft equipment regardless of the original manufacturer. EVAPCO's patented EVAPAK fi ll is guaranteed to fi t your existing cooling tower.

EASY INSTALLATION
The light weight, easy to handle PVC fi ll bundles simplify installation thereby saving labor hours and cost.

NON-CORROSIVE
EVAPAK fi ll is constructed of inert polyvinyl chloride (PVC). It will not rot or decay and is formulated to withstand water temperatures of 130o F. Higher temperature fi ll is available upon request. In tests conducted according to ASTM-E84-81A, the EVAPAK fl ame spread rating was 5.

2) Specification
Sheet Dimension:
                 305 x 1220 mm, 12" x 48" (inch)
                  305 x 1540 mm, 12" x 61" (inch)
                  305 x 1830 mm, 12" x 72" (inch)  
                  305 x 2440 mm, 12" x 96" (inch)
                  305 x any , 12" x any (inch)
Sheet spacing: 13mm, 15mm, 19mm
Sheet thickness: 0.2-0.5 mm
Material available: PVC, CPVC, PP
Color: Black, Blue, Green, White
Applicable water temperature: 90ºC ~ -35ºC

Packing and Loading. LCL cargo: wood pallet, wood case / Container Loading:
Trade Terms: EXW, FOB, CIF, CFR, DDU.
Payment term: T/T, L/C, West Union
Minimum Order Quantity: 1000 pcs

Service for assembling well the infills into block shape is available.
 
3) Evapco Infills shipment and boned well pictures
 


4) Physical and mechanical property 
PVC Plastic sheet(before molding) Physical and mechanical property 
No.ItemsymbolunitIndextest method
1densityρg/cm3≤1.55GB/T 1033
2Heat the longitudinal shrinkage rateS%≤3.0 
3tensile strengthlengthwaysσtMPa≥42.0GB/T 13022
crosswise≥38.0
4elongation at breaklengthwaysεt%≥60GB/T 13022
crosswise≥35
5tear strengthlengthwaysσtrkN/m≥150GB/T 1130
crosswise≥160
6Folded in half Coldness Resistance Temperature ordinary typetbºC≤-22 
Frigostabile type≤-35
*7Folded in half Coldness Resistance 
Temperature after hygrothermal aging 
ordinary typetb (W·H)ºC≤-8 
Frigostabile type≤-18
*8oxygen indexOI  --≥40GB/T 2406
 
PVC Plastic sheet(after molding) Physical and mechanical property 
No.ItemsymbolunitIndextest method
1densityρg/cm3≤1.55GB/T 1033
2tensile strengthlengthwaysσtMPa≥42.0GB/T 13022
crosswise≥38.0
3tear strengthlengthwaysσtrkN/m≥150GB/T 1130
crosswise≥160
4Folded in half Coldness 
Resistance Temperature
ordinary typetbºC≤-8 
Frigostabile type≤-18
*5oxygen indexOI  --≥40GB/T 2406
 
Cooling tower plastic parts code and standard
GB/T 1033-1986 plastic density and relative density experiment method
GB/T 1040-1992 plastic tensile performance test methods
GB/T 1633-1979 thermoplastic softening point (d) test method
GB/T 1843-1996 plastic cantilever beam impact test method
GB/T 2406-1993 plastic combustion performance test method, oxidation index
GB/T 13022-1991 plastic film tensile performance test methods
GB/T 1190-1991 plastic rectangular tear performance test methods