Cotrust PLC 226I 24di/16do Relay Output CPU V5 Version with Ethernet Port

China Cotrust PLC 226I 24di/16do Relay Output CPU V5 Version with Ethernet Port, Find details about China Ethernet Port, PLC from Cotrust PLC 226I 24di/16do Relay Output CPU V5 Version with Ethernet Port

Model NO.
CTS7 216-2BD45-0X40
Customized
Non-Customized
Net Weight
0.8kg
Trademark
COTRUST
Transport Package
CTN
Specification
196× 80× 62mm
Origin
China
HS Code
853710119
Model NO.
CTS7 216-2BD45-0X40
Customized
Non-Customized
Net Weight
0.8kg
Trademark
COTRUST
Transport Package
CTN
Specification
196× 80× 62mm
Origin
China
HS Code
853710119

Order Data

Products data

Order No.

CTSC-200 V5 series CPU

CPU226I V5 version

CPU226I:72KB program memory/110KB data memory,220VAC power supply,24DI/16DO relay output,2A,2*PPI/FPORT,1*Ethernet port,data permanent storage when power-down,support analog expansion board,CAN expansion board and RS485 expansion board.

CTS7 216-2BD45-0X40

 

Performance Parameters

Physical Features
Dimension(W×H×D)196×80×62mm
Power dissipation11W
Memory Features
Program memory24KB+48KB
Data memory10KB+100KB
General Features 
Timers total
      1ms
      10ms
      100ms
256
4
16
236
Counters total256
Internal memory bits256
Stored permanently on power downData permanent stored
Sequential control relay (S)256
Time Interrupts2 with 1ms resolution 
Edge Interrupts4 rising edges and/ or 4 falling edges 
Analog adjustmentNon
Boolean execution speed≤0.15µs
Float execution speed≤8µs
Clock embedded ,precision ±120s/m
BD expansion board interface number1,Support CAN expansion board, analog expansion board
System indicator5,STOP,RUN,SF,RMC,LINK/ACT
RUN/STOP dial code Yes,2
Battery card interfaceSupport,power supply below 2V,alarm 
bit SM195.0
Programming card and Memory cardSupport
Rated input voltage85-264VDC(47-63HZ)
Power supply
Native and extended bus+5V
+24V
 
1000mA
400mA
Integrated Communication Function
Communication Interface 2 communication ports ,PORT0:PPI/Free port,RS485;FPORT0:PPI/Free port,RS485

After plugging in and restarting the RS485 board, PORT0 is fixed as PPI0 non-switchable and free-port FP0 is configured to the RS485 board.
PPI baud rates(baud)9.6k,19.2k and 187.5k
Freeport baud rates(baud)1.2k ~ 115.2k
Maximum number of sations32 stations per segment,126 stations per network
Maximum number of masters32  
Point-to-point (PPI master station mode)Yes(NETR/NETW), maximum 8 connections, and each connection has a maximum communication of 200 bytes
MPI connect(1PG/1OP) 8 in total, 2 reserved
Maximum cable length
    Isolated repeater applied
    Isolated repeater unapplied
When it is 1000 m, baud rate is 187.5k; when it is 
1200 m, 38.4k.
50m
Ethernet Function
Communication port1 Ethernet port
Communication standardIEEE802.3 standard
Communication speed10Mbps and 100Mbps self-adaption
Adaptive cross connectionNon support
Interface to industrial Ethernet(10/100Mbps)RJ45 port
Protocol typeUDP/TCP protocol
Support PDP_PPI, MODBUS_TCP, Socket, S7 protocols, support PLC Ethernet communication, support MiCo Ethernet programming.
Collocation methodSupport the upper computer through the 
Ethernet port search PLC,
support the mouth download system configuration.
Application interfaceSupport MiCo service, UDP_PPI, Modbus_TCP, S7 protocol, Socket programming.Support Ethernet port online firmware upgrade function.
Maximum number of connections8 UDP_PPI, no master or slave
8 Modbus_TCP, no master or slave
4 Socket connections, 2 UDP, 2 TCP
8 S7 protocol, no master and slave, COTRUST PLC only as slave station
User data numberUp to 200 bytes for UDP_PPI transmission.
Up to 240 bytes are used for ModBus_TCP transmission.
A maximum of 512 bytes is used for Socket  transmission
Up to 200 bytes for S7 transmission
Portlocal:1~65535
remote server:8888
Boot time or restart time after reset3 seconds
Indicator lampGreen RMC indicator: on: remote control in effect, 
off: remote control out

Green Ethernet indicator: on: connection,
 flicker: transmission; 
out: not connected
Maximum cable length100m
IsolationCommunication port isolation

 

Integrated Communication Function (CANopen) - use for CAN communication board model CTH2-CAN-01S2-EB

Communication Interface

1(8 Pin)

Communication speed (kbps)

1000

800

500

250

150

50

20

Maximum cable length(m)

25

50

100

250

500

1000

2500

Maximum station address quantity

127

Station address range

1-127

Maximum number of master stations connect to slave stations

32

Collocation method

CAN configuration blocks and EDS files

Maximum digital access

Nomal IO

CANopen IO

 

Byte

Memory starting address

 

Byte

Memory starting address

Input

16

IB0

Input

64

IB16

Output

16

QB0

Output

64

QB16

Maximum analog access

Nomal IO

CANopen IO

 

Channel

Memory starting address

 

channel

Memory starting address

Input

32

AIW0

Input

162

AIW64

Output

32

AQW0

Output

162

AQW64

Integrated Communication Function (CANopen) - use for CAN communication board model CTH2-CAN-01S2-EB

Protocol 

CanFree

Use method

Supported by internal library instructions

 

I/O Features
Number of integrated digital inputs24
Input typeSink/Source
Number of integrated digital outputs16
Output typeRelay,dry contact
 
Digital I/O mapping domain640DI/640DQ
Analog I/O mapping domain194AI/194AQ
Maximum number of expandable I/O module7
Maximum digital I/O configuration128DI/128DO
Maximum analog I/O configuration32AI/32AQ
Pulse catch inputs24
High-speed counters
    Total 
     Uniphase counters 
     Bi-phase counters 
 
6
6×30KHz
4×20KHz
Digital Input Features
Number of integrated digital input24
Input typeSink/ Source
Rated voltage24V DC
Maximum continuous permissible voltage30V DC
Logical 1 Signal (minimum)
Logical  0 Signal (Maximum)
15 VDC,2.5mA
5 VDC,1mA
Isolation(field side to logical circuit)500V AC,1min
Simultaneous input24
Maximum cable length
Shielded
Unshielded
500 M(standard input)
50 M(high-speed counters input)
300 M(standard input)
Digital Output Features 
Number of integrated digital output16
Output typeSolid-MOSFET,source
Rated voltage -
Output voltage range-
Logical 1 Signal (minimum)-
 
Logical  0 Signal (Maximum) -
 
Rated current per point2A
Rated current for each common point 
Leakage current (maximum)-
Surge current(Maximum) 7A
Lamp load (maximum)30W DC/200W AC
On resistance (contact)0.2Ω
Isolation(field side to logical circuit)
 
-
DelayOff to on:-
on to off:-
Contact life at rated load100000 times on and off
Simultaneous inputAll output point
Parallel outputOnly when the outputs are in the same group
Maximum cable length
Shielded
Unshielded
500m
150m

* Support new V2 programming card
* Ultracapacitors power-off protection time 10 hours and extended batteries for 200 days
* Alarm function for insufficient battery power of the battery card: when it is lower than 2V, the alarm bit SM195.0

RS485 communication port definition

Connector

PIN

PORT0(RS485)

FPORT0(RS485)

 

1

    Shell Grounded

 Shell Grounded

2

+24V Grounded

+24V Grounded

3

RS485+signal B

RS485+signal B

4

Send the application

Send the application

5

+5V Grounded

+5V Grounded

6

+5V,100Ω

+5V,100Ω

7

+24V

+24V

8

RS485-signal A

RS485-signal A

9

NC

NC

shell 

 Shell Grounded

 Shell Grounded

 

RS485 expansion board communication interface

Module interface and connector

PIN

FPORT0(RS485)

Cotrust PLC 226I 24di/16do Relay Output CPU V5 Version with Ethernet Port 

Note:when terminal resistors are needed,
short connect the 2 and 3 pins

1

RS485+signal B

2

RS485-signalA

3

Terminal resistance

4

Shell Grounded

5

RS485 signal GND

6

NC

7

NC

8

NC

9

NC