Power System Over Voltage Protection Test Device GDYZ -30C

China Power System Over Voltage Protection Test Device GDYZ-30C, Find details about China Over Voltage Protector, Over-voltage Protection Test Set from Power System Over Voltage Protection Test Device GDYZ-30C

Model NO.
GDYZ-30C
Power Source
AC220V
Ambient temperature
-10ºC~50ºC
Altitude
<1000M
Relative humidity
≤80%
Warranty
1 year
Delivery time
10 working days
Trademark
HV Hipot
Transport Package
Standard Export Wooden Box
Specification
380*280*210mm
Origin
Wuhan, China
HS Code
9031809090
Model NO.
GDYZ-30C
Power Source
AC220V
Ambient temperature
-10ºC~50ºC
Altitude
<1000M
Relative humidity
≤80%
Warranty
1 year
Delivery time
10 working days
Trademark
HV Hipot
Transport Package
Standard Export Wooden Box
Specification
380*280*210mm
Origin
Wuhan, China
HS Code
9031809090
GDYZ-30C Over-voltage Protection Test Set Over Voltage Protector
 

General Information

GDYZ-30C Over-voltage protection device is widely used in the power system 35kV and below. It can make AC discharge voltage current and DC 1mA reference voltage test, so as to earlier find dangerous flaw of internal insulation moisture or valve aging.

 

Features

  • Using high-strength, high-insulation and wear-resistant hard plastic sealed box, which is sturdy and durable, with good shockproof performance, convenient for on-site handling.
  • Directly input 220V main power, suitable for various testing site.
  • With HV output switch, after OUT circuit can be connected with high voltage output circuit, which can effectively avoid the output high voltage caused by mis-operation. Once there is high voltage output, it will alarm to remind operator.
  • Built-in 32bit high speed processor, with data processing capability.
  • LCD display, user-friendly.
  • Flexible configuration. The main unit can output DC high voltage directly for testing the gapless 3-phase over-voltage protection device and surge arrester. It also can be equipped with testing transformer for power frequency discharge test with series gap over-voltage protector. A set of instruments can complete test items of common over-voltage protectors.
  • Test parameters include AC action voltage test of series gap over-voltage protector and DC voltage 1mA reference voltage test of gapless over-voltage protectors and zinc oxide surge arresters. The data is reliable and accurate.

Specification

1. Power frequency Discharge Voltage Test

Output voltage

AC 0.00-30.0kV

Resolution

0.1kV

Measurement accuracy

±1.5%±2digits.

Test interval time

≥15s

Function

Automatic calculation of the three average values after the test is completed.

Print

Test result can be printed.

2. DC 1mA reference voltage test

Rated output

DC 0-30kV, current 0-1000μA

Measurement range

Current 0-1000μA, voltage 0-30.0kV

Resolution

Current 1μA, voltage 0.1kV

Accuracy

±1.5%±1digit.

Function

With function of residual voltage automatic discharge.

Print

Test result can be printed.

3. Other parameters

Power supply

220V±10%

Ambient temperature

-10ºC~50ºC

Relative humidity

≤80%

Altitude

<1000M

Size & Weight

Main unit: 380*280*210mm, 5.8kg

Testing transformer: 255*150*255mm, 8.7kg

Power System Over Voltage Protection Test Device GDYZ-30C
Power System Over Voltage Protection Test Device GDYZ-30C
Power System Over Voltage Protection Test Device GDYZ-30C
Power System Over Voltage Protection Test Device GDYZ-30C