China Trmf4 250A Single Phase Moulded Case Circuit Breaker, Ls Design MCCB, Find details about China MCCB, Moulded Case Circuit Breaker from Trmf4 250A Single Phase Moulded Case Circuit Breaker, Ls Design MCCB
Ampere frame size | TRMF4(250A) | ||||||
Breaking capacity code | S | H | |||||
Product code and poles | 1P | 3P | 4P | 1P | 3P | 4P | |
TRMF4-S1 | TRMF4-S3 | TRMF4-S4 | TRMF4-H1 | TRMF4-H3 | TRMF4-H4 | ||
Rated current, In(A) | 100, 125, 160, 180, 200, 225, 250 | ||||||
Adjustable part | Rated current setting(0.8In-1.0In) | χ | √ | √ | χ | √ | √ |
Lockup device for operating handle | χ | √ | √ | χ | √ | √ | |
Rated operational voltage, Ue(V), AC 50/60 Hz | 240/415 | ||||||
Rated insulation voltage, Ui(V) | 1000 | ||||||
Rated impulse withstand voltage, Uimp(kV) | 8 | ||||||
Standard | Conformity with IEC/EN 60947-2 | ||||||
Rated frequency(Hz) | 50/60 | ||||||
Rated short-circuit breaking capacity, Icu(kA) | |||||||
AC | 240V | 25 | 50 | 36 | 65 | ||
415V | - | 37 | - | 50 | |||
Ics=% * Icu | 50% | 100% | 50% | 100% | |||
Mechanical life(circle) | 7000 | ||||||
Electrical life(circle) | 1000 | ||||||
Dimension: Length*Width*Height | 1-pole | 150*38*60 | |||||
2-poles | - | ||||||
3-poles | 165*105*60 | ||||||
4-poles | 130*140*60 |