China AC Contactor with 9-38A 3p+No+Nc, Find details about China Contactor, AC Contactors from AC Contactor with 9-38A 3p+No+Nc
Application
TSC7 series AC Contactor is suitable for using in the circuits up to the rated voltage 660V AC 50Hz or 60Hz, rated current up to 38A, for making, breaking, frequently start-ing & controlling the AC motor. Combined with the auxiliary contact block, delay timer & machine-interlocking device etc, it becomes the delay contactor, mechanical inter-locking contactor, star-delta starter. With the thermal relay, it is combined into the elec-tromagnetic starter. The products comply with IEC60947-4.
Specification
Model | 09 | 12 | 16 | 18 | 22 | 25 | 32 | 38 | ||
Rated working current(A) | 400(380)V | AC-3 | 9 | 12 | 16 | 16 | 22 | 25 | 32 | 38 |
AC-4 | 3.5 | 5 | 6.5 | 7.7 | 8 | 8.5 | 12 | 12 | ||
690(660)V | AC-3 | 6.6 | 8.9 | 11 | 18 | 16 | 34 | 39 | 39 | |
AC-4 | 1.5 | 2 | 3 | 4.4 | 4 | 9 | 12 | 12 | ||
Rated heat current(A) | 20 | 20 | 25 | 40 | 40 | 60 | 80 | 80 | ||
AC3 capacity of phase 3 squirrel-cage motor AC3 (KW) | 230(220)V | 2.2 | 3 | 4 | 5 | 5.5 | 11 | 15 | 15 | |
400(380)V | 4 | 5.5 | 6.5 | 11 | 10 | 18.5 | 22 | 22 | ||
690(660)V | 5.5 | 7.5 | 10 | 15 | 18.5 | 30 | 37 | 37 | ||
Mechanical life x104 | 1200 | 1200 | 1200 | 1200 | 1200 | 600 | 600 | 600 | ||
Electrical life x104 | AC-3 | 100 | 100 | 100 | 100 | 80 | 80 | 60 | 60 | |
AC-4 | 20 | 20 | 20 | 20 | 20 | 15 | 15 | 15 | ||
Number of the contacts | 3P+NO+NC |
Model | A | B | C | D | a | b | ø |
TSC7-09-18 | 46 | 76 | 88 | 120 | 34 | 55 | 4.5 |
TSC7-22-38 | 56 | 87 | 101 | 135 | 40 | 60 | 4.5 |
Why Choose Us?
1. Client's benefit first