(Clamp on) C2-100A 200A 300A 400A 500A Open Loop Hall Effect Current Sensor 21mm Hole Diameter Split Core Current Transducer

China (Clamp on) C2-100A 200A 300A 400A 500A Open Loop Hall Effect Current Sensor 21mm Hole Diameter Split Core Current Transducer, Find details about China Hall Effect Sensor, Clamp on Current Sensor from (Clamp on) C2-100A 200A 300A 400A 500A Open Loop Hall Effect Current Sensor 21mm Hole Diameter Split Core Current Transducer

Model NO.
C2
IP Rating
IP65
Certification
ISO
Customized
Customized
Output
Analog Sensor
Usage
Hall Sensor
Theory
Hall Sensor
Supply Voltage
+-12, +-15
Power Consumption
<25
Offset Voltage
@IP=0 +-20
Galvanic Isolation
@ 50Hz, AC, 1min 2.5
Isolation Resistance
@ DC 500V 1000
Trademark
HEYI
Transport Package
Export and Air-Worthy Standard Carton
Specification
IEC 6044-1
Origin
Liushi, Yueqing, Zhejiang Province, China
HS Code
8542390000
Model NO.
C2
IP Rating
IP65
Certification
ISO
Customized
Customized
Output
Analog Sensor
Usage
Hall Sensor
Theory
Hall Sensor
Supply Voltage
+-12, +-15
Power Consumption
<25
Offset Voltage
@IP=0 +-20
Galvanic Isolation
@ 50Hz, AC, 1min 2.5
Isolation Resistance
@ DC 500V 1000
Trademark
HEYI
Transport Package
Export and Air-Worthy Standard Carton
Specification
IEC 6044-1
Origin
Liushi, Yueqing, Zhejiang Province, China
HS Code
8542390000


C2 series dismountable hall effect current sensor is an open loop device based on the measuring principle of the hall effect, with a galvanic isolation between primary and secondary circuit. It provides accurate electronic measurement of DC, AC or pulsed currents.
 
Electrical data (Ta=25ºC±5ºC,RL=2KΩ,CL=10000PF)
TypeC2-100AC2-200AC2-300AC2-400AC2-500AUnit
Rated current(Ipn)±100±200±300±400±500A
Measure range(Ip)0-±2000-±4000-±6000-±8000-±1000A
Rated output@Ip=±Ipn               ±4±1%V
Supply voltage±12,±15V
Power Consumption<25mA
Offset voltage@Ip=0                     ±20mV
Magnetic offset@Ip=±Ipn-0                ±20mV
Offset drift@ -40~+85ºC               ≤±1mV/ºC
Output drift@ -40~+85ºC               ≤±1mV/ºC
Linearity@Ip=0-±Ipn                 ≤1%FS
Response time@50A/μS, 10%-90%         ≤5μs
Galvanic isolation@ 50HZ,AC,1min             2.5KV
Isolation resistance@ DC 500V                 1000
 
Applications
·Variable speed drives
·Welding machine
·Battery supplied applications
·Uninterruptible Power Supplies (UPS)
·Electrochemical
 
Mechanical dimension(for reference only)
(Clamp on) C2-100A 200A 300A 400A 500A Open Loop Hall Effect Current Sensor 21mm Hole Diameter Split Core Current Transducer
Remarks:
1. All dimensions are in mm.
2. General tolerance ±1mm.
3. Elucidation:  1:+15V  2:-15V  3:V0UT  4:0V
 
Directions for use
1. When the current will be measured goes through a sensor, the voltage will be measured at the output end.(Note: The false wiring may result in the damage of the sensor)
2. Custom design in the different rated input current and the output voltage are available.
 
Standards
·UL94-V0.
·EN60947-1:2004
·IEC60950-1:2001
·EN50178:1998
·SJ 20790-2000
 
General date
 ValueUnit
Operating temperature(TA)-40 to +85ºC
Storage temperature(TS)-40 to +125ºC
Mass(approx) (M)70g
 
Characteristics chart
Pulse current signal response characteristic:
(Clamp on) C2-100A 200A 300A 400A 500A Open Loop Hall Effect Current Sensor 21mm Hole Diameter Split Core Current Transducer

Effects of impulse noise:


(Clamp on) C2-100A 200A 300A 400A 500A Open Loop Hall Effect Current Sensor 21mm Hole Diameter Split Core Current Transducer