China Acrel Asj20-Ld1a Input 30mA-30A Panel Mounted Earth Leakage Current Protection Relay with Overcurrent Alarm, Find details about China Leakage Current Relay, Earth Leakage Protection Relay from Acrel Asj20-Ld1a Input 30mA-30A Panel Mounted Earth Leakage Current Protection Relay with Overcurrent Alarm
Types | Basic function | Installing way |
ASJ10-LD1 C | Measurement of AC-type after-current; Indicator of current off-limit alarm; The setting of rated residual action current ( see in the table 2); The setting of non-driving time of limitation ( see in the table 2); Two-pair relay output; Possessing the function of on-the-spot and long-distance testing and resetting | rail guiding (TS35mm ) |
ASJ10-LD1 A | The measurement of A-type after-current; The streamer display of current percentage; The setting of rated residual action current ( see in the table 2); The setting of non-driving time of limitation ( see in the table 2); Two- pair relay output(both of which can be set) *; Possessing the function of on-the-spot and long-distance testing and resetting | |
ASJ20-LD1 C | Measurement of AC-type after-current; Indicator of current off-limit alarm; The setting of rated residual action current ( see in the table 2); The setting of non-driving time of limitation ( see in the table 2); Two- pair relay output; Possessing the function of on-the-spot and long-distance testing and resetting | Screen structure (48 square) |
ASJ20-LD1 A | The measurement of A-type after-current; The streamer display of current percentage; The setting of rated residual action current ( see in the table 2); The setting of non-driving time of limitation ( see in the table 2); Two- pair relay output(both of which can be set) *; Possessing the function of on-the-spot and long-distance testing and resetting |
Technical parameter | Index | |||
Type AC | Type A | |||
input | Rated residual action current I△n | 0.03,0.1,0.3,0.5(A) | 0.03,0.05,0.1,0.3,0.5,1,3,5,10, 30(A) | |
Non-driving time of limitation △t | 0.1,0.5(s) | 0,0.06,0.1,0.2,0.3,0.5,0.8,1,4, 10(s) | ||
Rated residual non-action current I△no | 50%I△n | 50%I△n | ||
performance characteristics | simple sinusoidal alternating current | simple sinusoidal alternating current and pulsating direct current | ||
frequency | 50Hz±5Hz | 50Hz±5Hz | ||
action error | -20% ~ -10%I△n | -20% ~ -10%I△n | ||
output | output mode | one is the normal closing and the other | one is the normal closing or opening, and the other is for the transformation | |
is for the transformation | ||||
contact capacity | 5A 250VAC 5A 30VDC | AL1:8A 250VAC 5A 30VDC AL2:6A 250VAC 5A 30VDC | ||
reset mode | the on-the-spot one and the long-distance one, | the on-the-spot one, the long-distance one and the automatic one | ||
power supply | voltage range | AC110V,AC220V(permissible error±10%) | AC110V,AC220V,DC85-270V (permissible error±10%) | |
power dissipation | ≤5W | |||
power frequency withstand voltage | The effective value of alternating current between the power supply, input and output: 2kV/1min | |||
under the normal operation | temperature | operating temperature: -20ºC ~ +55ºC storage temperature: -30ºC ~ +70ºC | ||
humidity | ≤95%RH, with moisture condensation, and corrosive gas place | |||
height above sea level | ≤2000m | |||
class of pollution | Grade three | |||
installation category | Type Three |
instrument type | Panel size (mm) | Shell size (mm) | hole size(mm) |
ASJ20-LD1C ASJ20-LD1A | 48×48( width by height) | 43.8×43.8×100(width by height by depth) | 45×45(width by height) |