China 380V 50Hz Electric Power Inverter with DSP Control, Find details about China 380V Electric Power Inverter, 380V 50Hz Power Inverter from 380V 50Hz Electric Power Inverter with DSP Control
Model | ACME220 -3020 | ACME220 -3030 | ACME220 -3050 | ACME220 -3100 | |
DC input | input rating voltage (VDC) | 220 | |||
Input rating current (A) | 10.1 | 15.2 | 25.3 | 49.4 | |
Input DC voltage allowing range (VDC) | 180~300 | ||||
AC bypass input | Allowing input voltage range(VAC) | 380±15% | |||
Input rating current (A) | 3.0 | 4.5 | 7.6 | 15 | |
Bypass switch time (ms) | ≤4 | ||||
AC output | Rating capacity (KVA) | 2 | 3 | 5 | 10 |
Output rating power (KW) | 1.6 | 2.4 | 4.0 | 8.0 | |
Output rating voltage and frequency | 380VAC (Three phase four wire)50HZ | ||||
Output rating current (A) | 3.0 | 4.5 | 7.6 | 15 | |
Output voltage precision(V) | 380±2% | ||||
Three-phase unbalanced load capacity | ≤100% | ||||
THD | ≤3% | ||||
Dynamic response (load 0←→100%) | 5% | ||||
Power factor(PF) | 0.8 | ||||
Load ability | 150%, 10scends | ||||
Crest factor (CF) | 3:1 | ||||
Inverted efficiency | 92% | ||||
Working environment | Insulation strength(input and output) | 1500VAC,1minute | |||
Noise(1meter) | ≤50dB | ||||
using condition temperature | -10ºC~+50ºC | ||||
temperature | 0~90%,no condensing | ||||
Using altitude(m) | ≤2000 | ||||
Protection function | Input reversing protection, input low-voltage protection, output over-load protection, output short-circuit protection, over-heat protection |
Model | ACME220 -3200 | ACME220 -3450 | ACME220 -3600 | ACME220 -31000 | |
DC input | input rating voltage (VDC) | 220 | |||
Input rating current (A) | 99 | 222 | 296 | 496 | |
Input DC voltage allowing range (VDC) | 180~300 | ||||
AC bypass input | Allowing input voltage range(VAC) | 380±15% | |||
Input rating current (A) | 30.1 | 68.4 | 91.2 | 152 | |
Bypass switch time (ms) | ≤4 | ||||
AC output | Rating capacity (KVA) | 20 | 45 | 60 | 100 |
Output rating power (KW) | 16 | 36 | 48 | 80 | |
Output rating voltage and frequency | 380VAC (Three phase four wire),50HZ | ||||
Output rating current (A) | 30.1 | 68.4 | 91.2 | 152 | |
Output voltage precision(V) | 380±2% | ||||
Three-phase unbalanced load capacity | ≤100% | ||||
THD | ≤3% | ||||
Dynamic response (load 0←→100%) | 5% | ||||
Power factor(PF) | 0.8 | ||||
Load ability | 150%,10s | ||||
Crest factor (CF) | 3:1 | ||||
Inverted efficiency | 92% | ||||
Working environment | Insulation strength(input and output) | 1500VAC,1minute | |||
Noise(1meter) | ≤50dB | ||||
using condition temperature | -10ºC~+50ºC | ||||
temperature | 0~90%,no condensing | ||||
Using altitude(m) | ≤2000 | ||||
Protection function | Input reversing protection, input low-voltage protection, output over-load protection, output short-circuit protection, over-heat protection |