China DIN Rail Mounted Frequency Converter S800e Mini with CE, Find details about China Frequency Inverter, AC Drive from DIN Rail Mounted Frequency Converter S800e Mini with CE
Items | S800E | ||
Power Supply | Rated voltage, Frequency | One-phase/Three-phase AC 220V 50/60Hz | |
Voltage Range | 220V: 170~240V | ||
Output | Voltage Range | 220V: 0~220V | |
Frequency Range | 0.10~400.00Hz | ||
Control method | V/F control, Space vector control. | ||
Indication | Operating status/Alarm definition/interactive guidance: eg , frequency setting, the output frequency/ current, DC bus voltage, the temperature and so on. | ||
Control SpeciAlations | Output Frequency Range | 0.10Hz~400.00Hz | |
Frequency Setting Resolution | Digital input: 0.01Hz, analog input: 0.1% of maximum output frequency | ||
Output Frequency Accuracy | 0.01Hz | ||
V/F Control | Setting V/F curve to satisfy various load Requirements. | ||
Torque Control | Auto increase: auto raise torque by loading Condition; Manual increase: enable to set 0.0~20.0% of raising torque. | ||
Multifunctional Input Terminal | Four multi-function input terminals, realizing functions including fifteen section speed control, Program running, four-section acceleration/deceleration speed switch, UP/DOWN function and emergency stop and other functions | ||
Multifunctional Output Terminal | 1 multi-function output terminals for displaying of running, zero speed, counter, external abnormity, program operation and other Information and warnings. | ||
Acceleration/ deceleration Time Setting | 0~999.9s acceleration/deceleration time can be set individually. | ||
Other functions | PID Control | Built-in PID control | |
RS485 | Standard RS485 communication function(MODBUS) | ||
Frequency Setting | Analog input: 0 to 10 V, 0 to 20mA can be selected; Digital input:Input using the setting dial of the operation panel or RS485 or UP/DOWN. Note:AVI terminals can be used to select an analog voltage input(AV) and analog current input(AI) through the switch J2. Note: AVI terminals can be used to select an Analog voltage input (AV) and analog current Input(AI) through the switch J2. | ||
Multi-speed | Four multifunction input terminals, 15 section speed can be set | ||
Automatic voltage |
Model | Input | Power Output (KW) | Capacity (KVA) | Current Output (A) | Load Capacity (60s)(A) | Motor Equipped (KW) |
S800-2T0.4GE | 1PH/3PH 220V- 50/60HZ | 0.4 | 1.0 | 2.5 | 3.75 | 0.4 |
S800-2T0.75GE | 0.75 | 2.0 | 5.0 | 7.50 | 0.75 | |
S800-2T1.5GE | 1.5 | 2.8 | 7.0 | 10.50 | 1.5 |