China Steady State Permanent Magetic Latching Vacuum Contact for Indoor Application, Find details about China Vacuum Contactor, Energy Saving from Steady State Permanent Magetic Latching Vacuum Contact for Indoor Application
Technical data | SHVC-7P-200/400/630 | SHVC-10P-200/400/630 | |
Rated voltage | Ur(kV) | 7.2 | 12 |
Rated current | Ie(A) | 200/400/630 | 200/400/630 |
Rated frequency | fr(Hz) | 50-60 | 50-60 |
Rated short-time withstand current | Ik(kA) | 4 | 6.3 |
Rated peak withstand current | Ip(kA) | 10 | 16 |
Rated short circuit breaking current | Io(kA) | 4 | 5 |
Rated short-circuit making current | Ic(kA) | 10 | 12.5 |
capacitive switch current | Itc(A) | 230 | 230 |
Operating frequency | (Times/hour) | 900 | 900 |
Mechanical life | (Times) | 30×104 | 30×104 |
Electrical life | (Times) | AC-3:25×104 | AC-3:25×104 |
(Times) | AC-4:10×104 | AC-4:10×104 | |
Rated lightning impulse withstand voltage | Up(kV) | 60 | 75 |
Rated power frequency withstand voltage (1min) | Ud(kV) | 32 | 42 |
Three-phase closing synchronization | (ms) | ≤2.0 | ≤2.0 |
Contact bounce time | (ms) | ≤5.0 | ≤5.0 |
Conductive loop resistance of each phase (20ºC) | (μΩ) | ≤180 | ≤180 |
Control loop | |||
Control module- rated operating voltage | Ur(V) | 110V/220V(AC,DC) | |
Rated operating voltage range | (V) | 0.85Ur~1.1Ur | |
Latching mode | Permanent magnet | ||
Operating power | DC110V,3A | ||
DC220V,1.5A | |||
AC220V,1A | |||
Closing time | (ms) | ≤50 | |
Inherent opening time | (ms) | ≤20 | |
1min power frequency withstand voltage | (kV) | 2 | |
Auxiliary contacts-quantity | 5 open 5 close | ||
Conventional heating current | (A) | 6 | |
Mechanical life | (Times) | 5×106 | |
Electrical life | (Times) | 2×106 | |
Rated working current | DC/AC110V,0.4A | ||
DC/AC220V,0.2A |