China Fcs-15kv/200A-12.5ka Outdoor Pole Mounted Three Phase Vacuum Type Capacitor Switch, Find details about China Capacitor Switch, Capacitor Switches from Fcs-15kv/200A-12.5ka Outdoor Pole Mounted Three Phase Vacuum Type Capacitor Switch
Magnetic actuator operate mechanism | This advanced design monostable type magnetic actuator. With mechanical life 100,000 times. Intelligence capacitor switch controller |
Manual trip | Can be manual trip by hook sticker . |
Open/Close indicator | Visible from ground |
No. | Item | Unit | Data | |
1 | Rated voltage | KV | 15/27/38* | |
2 | Rated current | A | 200 up to 600 | |
3 | Rated frequency | HZ | 50/60 | |
4 | Power frequency 1min | Dry | KV | 60/79/85* |
Wet | 55/65/70* | |||
5 | Lightning impulse withstand voltage(peak value)alternate, opposite/fracture | KV | 125/150/170* | |
6 | Rated short circuit breaking current | KA | 12.5/8/6 | |
7 | Symmetrical fault-making current | KA | 16/12.5/10 | |
8 | Rated peak value withstand current | KA | 40/31.5/25(Max 50) | |
9 | Symmetrical short time withstand current | KA | 16/12.5/10 | |
10 | Rated operating circulate | O-0.3S-CO-3S-C ( 3S minimum ) | ||
11 | Single capacitor breaking | A | 630 | |
12 | Back to back capacitor bank breaking | A | 400 | |
13 | Mechanism life | times | 20,000 | |
14 | Secondary loop 1 min power frequency withstand voltage | KV | 2 | |
15 | Auxiliary voltage | V | 240 DC |
Offering: 1, ON/OFF signal light 2, Alarm(fault) light 3,Open&Close push button 4,Batteries 5,Capacitor 6, MCB 7,power Inverter 8,Intelligence Control device 9,Rotate switch 10, Auxiliary switch contacts 11, Cable connector 12, Terminals 13, Others | Specification of components: 1, ON&OFF signal light ON signal light red color,OFF light Green. Power from inner controller. 2, Alarm(fault)light Yellow color. Power from inner controller Power from inner controller. Power from inner controller. 3, Open&Close push button Open push button Green color. Close push button Red color. Power from inner controller. Note: For remote controlling can set additional circuit loop, power from outside. detail see secondary diagram. 4,Batteries, 2pcs 12Vdc,7AH/pcs Close push button Red color. Power from inner controller. 5,Capacitor,1pcs 250Vdc, 22000uF. 6, MCB, 2poles 1pcs, 1poles 1pcs. AC220Vac, 16A. for protection and switching. 7,Power inverter, capacitive&battery /1pcs. Capacitive type, 24Vdc exchange to 250Vdc.. battery inverter accordingly outside power. 8, Intelligence control device 1pcs. For switching&controlling coils. 9, Rotate switch,220Vac 1pcs. Control for remote circuit or local circuit. 10, Auxiliary switch contacts Backup for clients. 220Vac, 10A. Note: Others pls contact with Farady's Engineers. |